102
-
'20 • PAC-SM-351
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
E10
Excessive number of connected
indoor units (more than 17 units)
by controlling with one remote control
Keeps flashing
Stays OFF
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
Diagnosis
Countermeasure
Are more than 17
indoor units connected to one
remote control?
NO
YES
Defective remote control
➞
Replace.
Reduce to 16 or less units.
2. Error detection method
When it detects more than 17 of
indoor units connected to one
remote contorl
3.
Condition of error displayed
Same as above
4. Presumable cause
• Excessive number of indoor
units connected
• Defective remote control
Note:
Summary of Contents for SRK100VNXWPZSX
Page 181: ...180 20 PAC SM 351 1 e SRK series PHA012D402...
Page 182: ...181 20 PAC SM 351 Screw...
Page 183: ...182 20 PAC SM 351 3 PHA012D402...
Page 184: ...183 20 PAC SM 351 4 PHA012D402...