Limit switch anomaly
Stays OFF
Keeps flashing
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
NO
YES
Is the inlet
panel set correctly?
Are limit switch OK?
Note (1) Check the operation of limit switch by checking if
the error can be reset or not by pushing the limit switch
by finger when the inlet panel is removed.
⑴
YES
Correction, re-set
Defective limit switch
➞
Replace.
Defective indoor unit control
PCB
➞
Replace.
(Defective limit switch
input circuit)
2. Error detection method
The limit switch operates when
the indoor unit is stopped.
3.
Condition of error displayed
Same as above
4. Presumable cause
• Defective limit switch
• Faulty indoor unit control PCB
Note:
Error code
Remote control:
Indoor
display
RUN light TIMER light
Green LED Red LED
Outdoor unit
control PCB
Content