8
6. Setting from GX Developer
Set the mode, default operation, battery error detection, logging monitor and
response monitoring time for Web server module on the "Intelligent function
module switch setting" screen.
Item Description
Switch 1
Mode setting
Switch 2
Default operation setting/Battery error detection
setting/Logging monitor setting
Switch 3 (lower byte)
Response monitoring time setting
Switch 4 to 5
For system use (Do not set)
(1) Mode setting (Switch 1)
Select the operation mode for Web server module.
Setting number
Item
Description
0000
H
Online
Normal
operation
mode
0001
H
Hardware
test
Tests the ROM/RAM/switch
settings
0002
H
CH1
Self-loopback
test
Tests the self diagnostics for
CH1.
0003
H
CH2
Self-loopback
test
Tests the self diagnostics for
CH2.
9999
(270F
H
)
Module initialization
mode
Initializes the module to default
setting.