3.3.  Indoor unit (Fig. 3-3)

Heat insulation for refrigerant pipes:

1  Wrap the enclosed large-sized pipe cover around the gas pipe, making sure that 

the end of the pipe cover touches the side of the unit.

2  Wrap the enclosed small-sized pipe cover around the liquid pipe, making sure 

that the end of the pipe cover touches the side of the unit.

3  Secure both ends of each pipe cover with the enclosed bands. (Attach the 

bands 20 mm, 25/32 inch from the ends of the pipe cover.)

•  After connecting the refrigerant piping to the indoor unit, be sure to test the pipe 

connections for gas leakage with nitrogen gas. (Check that there is no refrigerant 
leakage from the refrigerant piping to the indoor unit.)

Fig. 3-3

3.  Refrigerant pipe and drain pipe

3.4.  Drainage piping work (Fig. 3-4)

• Use VP25 (O.D. ø32 mm, 1-1/4 inch PVC TUBE) for drain piping and provide 

1/100 or more downward slope.

•  Be sure to connect the piping joints using a polyvinyl type adhesive.
• Observe the 

fi

 gure for piping work.

•  Use the included drain hose to change the extraction direction.

1

 

Correct piping

2

 

Wrong piping

A

 

Insulation (9 mm, 23/64 inch or more)

B

 

Downward slope (1/100 or more)

C

 

Support metal

K

 

Air bleeder

L

 

Raised

M

 

Odor trap

Grouped piping

D

 

O. D. ø32 mm, 1-1/4 inch PVC TUBE

E

 

Make it as large as possible

F

 

Indoor unit

G

 

Make the piping size large for grouped piping.

H

 

Downward slope (1/100 or more)

I

 

O. D. ø38 mm, 1-1/2 inch PVC TUBE for grouped piping.

  (9 mm or more insulation)

J

 

Up to 850 mm, 33-7/16 inch

1.  Connect the drain socket (supplied with the unit) to the drain port. (Fig. 3-5)
 

(Fix the tube using PVC adhesive then secure it with a band.)

2.  Install a locally purchased drain pipe (PVC pipe, O.D. ø32 mm, 1-1/4 inch).
 

(Fix the pipe using PVC adhesive then secure it with a band.)

3.  Insulate the tube and pipe. (PVC pipe, O.D. ø32 mm, 1-1/4 inch and socket)
4.  Check that drain 

fl

 ows smoothly.

5.  Insulate the drain port with insulating material, then secure the material with a 

band.  (Both insulating material and band are supplied with the unit.)

A

 

Unit

B

 

Insulating material

C

 

Band (large)

D

 

Drain port (transparent)

E

 

Insertion margin

F

 

Matching

G

 

Drain pipe (O.D. ø32 mm, 1-1/4 inch PVC TUBE)

H

 

Insulating material (purchased locally)

I

 

Transparent PVC pipe

J

 

O.D. ø32 mm, 1-1/4 inch PVC TUBE (Slope 1/100 or more)

K

 

Band (small)

L

 

Drain socket

7/16

1

1

1

 

 

,

Max. 65 ft

5 to 7 ft

 

Max. 6 inch

Fig. 3-4

Fig. 3-5

(inch)

B

 

Refrigerant pipe sizes & Flare nut tightening torque

C

 Apply refrigerating machine oil over the entire 

fl

 are seat surface.

 Refrigerant pipe and 

     insulating material

 Pipe cover (large)

 Pipe cover (small)

 Refrigerant pipe (gas)

 Refrigerant pipe (liquid)

Band

Cross-sectional view of connection

 Pipe

 Insulating material

Squeeze

,

 

Liquid pipe

Gas pipe

Flare nut O.D.

Pipe size

(mm)

(inch)

Tightening

torque (N.m)

(ft. Ibs)

Pipe size

(mm)

(inch)

Tightening

torque (N.m)

(ft. Ibs)

Liquid pipe

(mm)

(inch)

Gas pipe

(mm)

(inch)

P08, P12, P15, P18

ODø6.35

1/4"

14 - 18
10 - 13

ODø12.7

1/2"

49 - 61
35 - 44

17

43/64

26

1-1/32

P24, P30, P36

ODø9.52

3/8"

34 - 42
25 - 30

ODø15.88

5/8"

68 - 82
49 - 59

22

7/8

29

1-9/64

Summary of Contents for PLFY-P-NBMU-E2

Page 1: ...r conditioner unit FOR INSTALLER MANUEL D INSTALLATION Avant d installer le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil ext rieur pour une utilisation s r...

Page 2: ...s authorized by Mitsubishi Electric and ask the dealer or an authorized technician to install them Do not touch the heat exchanger fins Install the air conditioner according to this Installation Manua...

Page 3: ...e duct holes cut out located at the positions shown in Fig 2 3 as and when required A fresh air intake hole for the optional multi function casement can also be made Note The figure marked with in the...

Page 4: ...etc Confirm that the main unit is horizontally levelled using a level or a vinyl tube filled with water After checking the position of the main unit tighten the nuts of the suspension bolts securely...

Page 5: ...for grouped piping 9 mm or more insulation J Up to 850 mm 33 7 16 inch 1 Connect the drain socket supplied with the unit to the drain port Fig 3 5 Fix the tube using PVC adhesive then secure it with...

Page 6: ...rrent sensitivity 3 F0 20A or less 2 3 3 12 3 3 12 3 3 12 20 20 20 20A current sensitivity 3 F0 30A or less 2 5 3 10 5 3 10 5 3 10 30 30 30 30A current sensitivity 3 Apply to IEC61000 3 3 about max pe...

Page 7: ...ecting remote controller indoor and outdoor transmission cables Fig 4 3 Connect indoor unit TB5 and outdoor unit TB3 Non polarized 2 wire The S on indoor unit TB5 is a shielding wire connection For sp...

Page 8: ...P08 P30NBMU E2 SWA SWB 1 2 3 Silent Standard High ceiling 4 4 direction 2 5 m 8 2 ft 2 7 m 8 9 ft 3 5 m 11 5 ft 3 3 direction 2 7 m 8 9 ft 3 0 m 9 8 ft 3 5 m 11 5 ft 2 2 direction 3 0 m 9 8 ft 3 3 m 1...

Page 9: ...e corner panel Fig 5 4 Remove the screw from the corner of the corner panel Slide the corner panel as indicated by the arrow 1 to remove the corner panel Fig 5 3 5 4 A Intake grille B Grille C Intake...

Page 10: ...up or down orientations depending upon the environment of use Set according to the preference of the customer The operation of the fixed up down vanes and all automatic controls cannot be performed u...

Page 11: ...ooseness in the power sup ply or control wiring wrong polarity and no disconnection of one phase in the supply Use a 500 volt megohmmeter to check that the resistance between the power supply terminal...

Page 12: ...Electric et de mander votre revendeur ou une soci t agr e de les installer Ne touchez jamais les ailettes de l changeur de chaleur Installez le climatiseur en respectant les instructions du manuel d i...

Page 13: ...st risque sur le sch ma repr sente les dimensions de l appareil principal sans tenir compte des dimensions du bo tier multifonctions disponible en option Lors de l installation de ce bo tier multifonc...

Page 14: ...en vinyle rempli d eau v rifier que l appareil principal soit bien l horizontale Lorsque la bonne position de l appareil principal est d finie avec certitude serrer convenablement les crous des boulo...

Page 15: ...33 7 16 pouces 1 Raccorder la prise d ecoulement fourni avec l appareil au port de drainage Fig 3 5 Apposer le tube l aide de ruban adh sif en PVC puis le fixer avec une sangle 2 Installer un tuyau de...

Page 16: ...doit tre assur par l installation de climatisation Fig 4 2 A Disjoncteur de fuite la terre B Commutateur local Disjoncteur C Appareil int rieur D Bo te de tirage Fig 4 1 D C TB2 TB5 TB15 S 1 2 M1 L1...

Page 17: ...Raccorder l unit int rieure TB5 et l unit int rieure TB3 2 fils non polaris s Le S sur l unit int rieure TB5 est une connexion pour c bles blind Pour les sp cifications techniques des c bles de connex...

Page 18: ...bon positionnement de l interrupteur curseur marqu SWA et SWB pour viter tout probl me de refroidissement chauffage PLFY P08 P30NBMU E2 SWA SWB 1 2 3 Silencieux Standard Haut plafond 4 4 directions 2...

Page 19: ...our le d poser Fig 5 3 5 4 A Grille d admission B Grille C Leviers de la grille d admission D Crochet de la grille E Orifice pour le crochet de la grille F Panneau en coin G Vis H D tail 5 3 S lection...

Page 20: ...t l commande 1 Mettre l interrupteur principal hors tension Si le ventilateur de l appareil devait fonctionner vous risqueriez de vous blesser ou de recevoir une d charge lectrique 2 D brancher le con...

Page 21: ...surer que la r sistance entre les terminaux d alimentation lectrique et la terre soit au moins de 1 0 M A Pompe d arriv e d eau B Eau environ 1000 cc C Bouchon de vidange D Verser l eau travers le con...

Page 22: ...en este manual de instalaci n Todas las conexiones el ctricas deber n ser realizadas por un electricista autorizado de acuerdo con la normativa local Si el aire acondicionado se instala en una habitac...

Page 23: ...e fresco para la caja multifuncional opcional Nota Las cifras marcadas mediante en el gr fico representan el tama o de la uni dad principal sin tener en cuenta la caja multifuncional opcional Cuando i...

Page 24: ...ue la unidad principal est nivelada horizontalmente mediante un nivel o tubo de vinilo relleno de agua Una vez comprobada la posici n de la unidad principal apriete firmemente las tuercas de los torni...

Page 25: ...3 7 16 pulgadas 1 Conecte el tubo de desag e suministrado con la unidad al orificio de desag e Fig 3 5 Sujete el tubo con cinta aislante y asegure la conexi n con una abrazadera 2 Instale un tubo de d...

Page 26: ...0 20 A o menos 2 3 3 12 3 3 12 3 3 12 20 20 20 Sensibilidad de corriente de 20 A 3 F0 30 A o menos 2 5 3 10 5 3 10 5 3 10 30 30 30 Sensibilidad de corriente de 30 A 3 Apl quese el IEC61000 3 3 para la...

Page 27: ...ia y de las unidades exterior e interior Fig 4 3 Conecte TB5 de la unidad interior y TB3 de la unidad exterior cable no polari zado de 2 hilos La S en TB5 de la unidad interior indica una conexi n de...

Page 28: ...sici n correcta ya que de no estarlo podr an producirse problemas como la falta de expulsi n de aire PLFY P08 P30NBMU E2 SWA SWB 1 2 3 Silencio Est ndar Techo alto 4 4 direcciones 2 5 m 8 2 pies 2 7 m...

Page 29: ...5 4 A Rejilla de admisi n B Rejilla C Palancas de la rejilla de admisi n D Gancho de la rejilla E Orificio para el gancho de la rejilla F Panel angular G Tornillo H Detalle 5 3 Selecci n de las salid...

Page 30: ...posici n indicada en el con trolador remoto 1 Apague el interruptor principal Pueden producirse da os o descargas el ctricas mientras gire el ventilador de la unidad 2 Desconecte el conector del moto...

Page 31: ...alimentaci n Utilice un megaohm metro de 500 V para comprobar que la resistencia en tre los bornes de alimentaci n y la tierra es como m nimo de 1 0 M A Bomba de alimentaci n de agua B Agua aprox 100...

Page 32: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment Printed in JAPAN RG79D308K06 HEAD OFFICE T...

Reviews: