background image

2

2.1.  Check the indoor unit accessories (Fig. 2-1)

The indoor unit should be supplied with the following accessories.

Accessory name

Q’ty

Installation template

1

Washers (with insulation)
Washers (without insulation)

4
4

Pipe cover (for refrigerant piping joint)
small diameter
large diameter

1
1

Band (large)
Band (small)

6
2

Screw with washer (M5 × 25) for mounting grille

4

Drain socket

1

Insulation

1

  Before installing the unit, make sure you read all the “Safety precau-

tions”.

  Please report to your supply authority or obtain their consent before 

connecting this equipment to the power supply system. 

1. Safety precautions

2.  Installing the indoor unit

Fig. 2-1

Contents

1. Safety 

precautions 

..................................................................................... 2

2.  Installing the indoor unit ............................................................................ 2
3.  Refrigerant pipe and drain pipe ................................................................. 4

4. Electrical 

work 

........................................................................................... 6

5.  Installing the grille ...................................................................................... 9
6. Test 

run 

.................................................................................................... 11

 Warning:

Describes precautions that must be observed to prevent danger of injury or 
death to the user.

 Caution:

Describes precautions that must be observed to prevent damage to the unit.

After installation work has been completed, explain the “Safety Precautions,” use, 
and maintenance of the unit to the customer according to the information in the 
Operation Manual and perform the test run to ensure normal operation. Both the 
Installation Manual and Operation Manual must be given to the user for keeping. 
These manuals must be passed on to subsequent users.

   : Indicates an action that must be avoided.

  : Indicates that important instructions must be followed.

  : Indicates a part which must be grounded.

  : Indicates that caution should be taken with rotating parts.

  : Indicates that the main switch must be turned off before servicing. 

 : Beware of electric shock.

 : Beware of hot surface.

ELV

 : At servicing, please shut down the power supply for both the Indoor and 

Outdoor Unit.

 Warning:

Carefully read the labels af

fi

 xed to the main unit.

 Caution:

Appliances not accessible to the general public.
Install the indoor unit at least 2.4 m (94-1/2 inch) above 

fl

 oor or grade level.

 Warning:

•  Ask the dealer or an authorized technician to install the air conditioner.
•  Install the unit at a place that can withstand its weight.
•  Use the speci

fi

 ed cables for wiring.

•  Use only accessories authorized by Mitsubishi Electric and ask the dealer 

or an authorized technician to install them.

•  Do not touch the heat exchanger 

fi

 ns.

•  Install the air conditioner according to this Installation Manual.
• Have all electric work done by a licensed electrician according to local 

regulations.

•  If the air conditioner is installed in a small room, measures must be taken 

to prevent the refrigerant concentration from exceeding the safety limit 
even if the refrigerant should leak.

 Caution:

•  Do not use the existing refrigerant piping, when use R410A or R407C refrig-

erant.

•  Use ester oil, either oil or alkylbenzene (small amount) as the refrigerator oil 

to coat 

fl

 ares and 

fl

 ange connections, when use R410A or R407C refrigerant.

• Do not use the air conditioner where food, pets, plants, precision instru-

ments, or artwork are kept.

•  Do not use the air conditioner in special environments.

•  Ground the unit.
•  Install an leak circuit breaker, as required.
•  Use power line cables of suf

fi

 cient current carrying capacity and rating.

•  Use only a circuit breaker and fuse of the speci

fi

 ed capacity.

•  Do not touch the switches with wet 

fi

 ngers.

•  Do not touch the refrigerant pipes during and immediately after operation.
•  Do not operate the air conditioner with the panels and guards removed.
•  Do not turn off the power immediately after stopping operation.

1

2

3

4

5

6

7

1
2

3

4
5

6

7

•  The cut face punched parts may cause injury by cut, etc. The installers are 

requested to wear protective equipment such as gloves, etc.

•  When installing or relocating, or servicing the air conditioner, use only the 

speci

fi

 ed refrigerant (R410A) to charge the refrigerant lines. Do not mix it 

with any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high 
pressure in the refrigerant line, and may result in an explosion and other 
hazards.
The use of any refrigerant other than that speci

fi

 ed for the system will cause 

mechanical failure or system malfunction or unit breakdown. In the worst 
case, this could lead to a serious impediment to securing product safety.

Note:
The phrase “Simple MA Remote controller” in this installation manual refers to the PAC-YT53CRAU.
If you need any information for the other remote controller, please refer to either the installation manual or initial setting manual which are included in these box.

Summary of Contents for PLFY-P-NBMU-E2

Page 1: ...r conditioner unit FOR INSTALLER MANUEL D INSTALLATION Avant d installer le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil ext rieur pour une utilisation s r...

Page 2: ...s authorized by Mitsubishi Electric and ask the dealer or an authorized technician to install them Do not touch the heat exchanger fins Install the air conditioner according to this Installation Manua...

Page 3: ...e duct holes cut out located at the positions shown in Fig 2 3 as and when required A fresh air intake hole for the optional multi function casement can also be made Note The figure marked with in the...

Page 4: ...etc Confirm that the main unit is horizontally levelled using a level or a vinyl tube filled with water After checking the position of the main unit tighten the nuts of the suspension bolts securely...

Page 5: ...for grouped piping 9 mm or more insulation J Up to 850 mm 33 7 16 inch 1 Connect the drain socket supplied with the unit to the drain port Fig 3 5 Fix the tube using PVC adhesive then secure it with...

Page 6: ...rrent sensitivity 3 F0 20A or less 2 3 3 12 3 3 12 3 3 12 20 20 20 20A current sensitivity 3 F0 30A or less 2 5 3 10 5 3 10 5 3 10 30 30 30 30A current sensitivity 3 Apply to IEC61000 3 3 about max pe...

Page 7: ...ecting remote controller indoor and outdoor transmission cables Fig 4 3 Connect indoor unit TB5 and outdoor unit TB3 Non polarized 2 wire The S on indoor unit TB5 is a shielding wire connection For sp...

Page 8: ...P08 P30NBMU E2 SWA SWB 1 2 3 Silent Standard High ceiling 4 4 direction 2 5 m 8 2 ft 2 7 m 8 9 ft 3 5 m 11 5 ft 3 3 direction 2 7 m 8 9 ft 3 0 m 9 8 ft 3 5 m 11 5 ft 2 2 direction 3 0 m 9 8 ft 3 3 m 1...

Page 9: ...e corner panel Fig 5 4 Remove the screw from the corner of the corner panel Slide the corner panel as indicated by the arrow 1 to remove the corner panel Fig 5 3 5 4 A Intake grille B Grille C Intake...

Page 10: ...up or down orientations depending upon the environment of use Set according to the preference of the customer The operation of the fixed up down vanes and all automatic controls cannot be performed u...

Page 11: ...ooseness in the power sup ply or control wiring wrong polarity and no disconnection of one phase in the supply Use a 500 volt megohmmeter to check that the resistance between the power supply terminal...

Page 12: ...Electric et de mander votre revendeur ou une soci t agr e de les installer Ne touchez jamais les ailettes de l changeur de chaleur Installez le climatiseur en respectant les instructions du manuel d i...

Page 13: ...st risque sur le sch ma repr sente les dimensions de l appareil principal sans tenir compte des dimensions du bo tier multifonctions disponible en option Lors de l installation de ce bo tier multifonc...

Page 14: ...en vinyle rempli d eau v rifier que l appareil principal soit bien l horizontale Lorsque la bonne position de l appareil principal est d finie avec certitude serrer convenablement les crous des boulo...

Page 15: ...33 7 16 pouces 1 Raccorder la prise d ecoulement fourni avec l appareil au port de drainage Fig 3 5 Apposer le tube l aide de ruban adh sif en PVC puis le fixer avec une sangle 2 Installer un tuyau de...

Page 16: ...doit tre assur par l installation de climatisation Fig 4 2 A Disjoncteur de fuite la terre B Commutateur local Disjoncteur C Appareil int rieur D Bo te de tirage Fig 4 1 D C TB2 TB5 TB15 S 1 2 M1 L1...

Page 17: ...Raccorder l unit int rieure TB5 et l unit int rieure TB3 2 fils non polaris s Le S sur l unit int rieure TB5 est une connexion pour c bles blind Pour les sp cifications techniques des c bles de connex...

Page 18: ...bon positionnement de l interrupteur curseur marqu SWA et SWB pour viter tout probl me de refroidissement chauffage PLFY P08 P30NBMU E2 SWA SWB 1 2 3 Silencieux Standard Haut plafond 4 4 directions 2...

Page 19: ...our le d poser Fig 5 3 5 4 A Grille d admission B Grille C Leviers de la grille d admission D Crochet de la grille E Orifice pour le crochet de la grille F Panneau en coin G Vis H D tail 5 3 S lection...

Page 20: ...t l commande 1 Mettre l interrupteur principal hors tension Si le ventilateur de l appareil devait fonctionner vous risqueriez de vous blesser ou de recevoir une d charge lectrique 2 D brancher le con...

Page 21: ...surer que la r sistance entre les terminaux d alimentation lectrique et la terre soit au moins de 1 0 M A Pompe d arriv e d eau B Eau environ 1000 cc C Bouchon de vidange D Verser l eau travers le con...

Page 22: ...en este manual de instalaci n Todas las conexiones el ctricas deber n ser realizadas por un electricista autorizado de acuerdo con la normativa local Si el aire acondicionado se instala en una habitac...

Page 23: ...e fresco para la caja multifuncional opcional Nota Las cifras marcadas mediante en el gr fico representan el tama o de la uni dad principal sin tener en cuenta la caja multifuncional opcional Cuando i...

Page 24: ...ue la unidad principal est nivelada horizontalmente mediante un nivel o tubo de vinilo relleno de agua Una vez comprobada la posici n de la unidad principal apriete firmemente las tuercas de los torni...

Page 25: ...3 7 16 pulgadas 1 Conecte el tubo de desag e suministrado con la unidad al orificio de desag e Fig 3 5 Sujete el tubo con cinta aislante y asegure la conexi n con una abrazadera 2 Instale un tubo de d...

Page 26: ...0 20 A o menos 2 3 3 12 3 3 12 3 3 12 20 20 20 Sensibilidad de corriente de 20 A 3 F0 30 A o menos 2 5 3 10 5 3 10 5 3 10 30 30 30 Sensibilidad de corriente de 30 A 3 Apl quese el IEC61000 3 3 para la...

Page 27: ...ia y de las unidades exterior e interior Fig 4 3 Conecte TB5 de la unidad interior y TB3 de la unidad exterior cable no polari zado de 2 hilos La S en TB5 de la unidad interior indica una conexi n de...

Page 28: ...sici n correcta ya que de no estarlo podr an producirse problemas como la falta de expulsi n de aire PLFY P08 P30NBMU E2 SWA SWB 1 2 3 Silencio Est ndar Techo alto 4 4 direcciones 2 5 m 8 2 pies 2 7 m...

Page 29: ...5 4 A Rejilla de admisi n B Rejilla C Palancas de la rejilla de admisi n D Gancho de la rejilla E Orificio para el gancho de la rejilla F Panel angular G Tornillo H Detalle 5 3 Selecci n de las salid...

Page 30: ...posici n indicada en el con trolador remoto 1 Apague el interruptor principal Pueden producirse da os o descargas el ctricas mientras gire el ventilador de la unidad 2 Desconecte el conector del moto...

Page 31: ...alimentaci n Utilice un megaohm metro de 500 V para comprobar que la resistencia en tre los bornes de alimentaci n y la tierra es como m nimo de 1 0 M A Bomba de alimentaci n de agua B Agua aprox 100...

Page 32: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment Printed in JAPAN RG79D308K06 HEAD OFFICE T...