10
11
11
Service Ref.
PKH-1.6GKL
PKH-1.6GKLH
PKH-2GKL
PKH-2GKLH
Refrigerant piping length(one way)
5m
10m
15m
20m
25m
30m
35m
40m
45m
50m
1.00
1.00
0.993
0.992
0.984
0.983
0.978
0.978
0.969
0.966
0.961
0.959
0.956
0.950
0.948
0.945
—
—
—
—
Cooling capacity correction factors
15
20
25
15
20
25
CA
3,184
3,049
2,930
4,280
4,098
3,939
P.C.
1.01
1.09
1.15
1.56
1.68
1.79
CA
3,650
3,506
3,364
4,905
4,713
4,521
P.C.
1.12
1.20
1.28
1.73
1.86
1.98
CA
4,160
4,003
3,844
5,591
5,380
5,167
P.C.
1.23
1.32
1.42
1.90
2.05
2.19
CA
4,714
4,538
4,370
6,336
6,100
5,874
P.C.
1.35
1.45
1.56
2.09
2.25
2.41
CA
5,312
5,112
4,942
7,139
6,871
6,643
P.C.
1.48
1.59
1.70
2.28
2.46
2.64
CA
5,952
5,724
5,560
8,000
7,693
7,473
P.C.
1.61
1.73
1.86
2.49
2.68
2.87
-10
-5
0
Service Ref.
Indoor
intake
air
D.B.(°C)
PKH-1.6GKL
PKH-1.6GKLH
PKH-2GKL
PKH-2GKLH
5
Outdoor intake air W.B.(°C)
10
15
2) HEATING CAPACITY
CA : Capacity (W)
P.C. : Power consumption (kW)
Service Ref.
PKH-1.6GKL
PKH-1.6GKLH
PKH-2GKL
PKH-2GKLH
Refrigerant piping length(one way)
5m
10m
15m
20m
25m
30m
35m
40m
45m
50m
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.998
0.998
0.995
0.995
—
—
—
—
Heating capacity correction factors
2. PERFORMANCE CURVE
1.4
1.2
1.0
0.8
0.6
1.4
1.2
1.0
0.8
0.6
0.4
-12-10 -5
0
5
10
15
OUTDOOR W.B. (°C)
INDOOR D.B. (°C)
INDOOR D.B. (°C)
15
20
25
25
20
15
TOT
AL
INPUT
(RA
TIO)
CAP
ACITY
(RA
TIO)
Heating
1.4
1.2
1.0
0.8
0.6
1.4
1.2
1.0
0.8
0.6
0.4
-5
5
15
25
35
46
OUTDOOR D.B.(°C)
TOT
AL
INPUT
(RA
TIO)
CAP
ACITY
(RA
TIO)
INDOOR W.B.(°C)
INDOOR W.B.(°C)
22
20
18
16
22
20
18
16
Cooling
OC229A