background image

S3

S3

S2

S1

N

L

S2

S1

L N

9

Fig. 4-10

4.8. For twin/triple/quadruple combination (Fig. 4-10)

• When this unit is used as a FREE COMPO MULTI unit, install the refrigerant

piping with the restrictions indicated in the drawing on the left. In addition, if the
restrictions are going to be exceeded, or if there are going to be combinations of
indoor and outdoor units, refer to installation instructions for the indoor unit for
details about the installation.

Outdoor unit

Permissible total

piping length

A+B+C+D+E

A+B or A+C

or

A+D or A+E

Charge-less

piping length

A+B+C+D+E

HRP200

HRP200          

 : A+B+C(+D)(+E)

!

80 m

* “D” is for triple“.

* “E” is for four (quadruple).

Indoor unit

Outdoor unit

Multi distribution pipe (option)

Height difference (Indoor unit-
Outdoor unit) Max. 30 m

Height difference (Indoor unit-
Indoor unit) Max. 1 m

A: Main piping

B, C, D, E: Branch

Max. 20m

piping

<Limits of refrigerant piping installation>

| B-C | or | B-D | or
| B-E | or | C-D | or

| C-E | or | D-E |

No. of bends

HRP71 - 200

Within 15

HRP71, 100, 125

75 m and less

80 m and less

70 m and less

30 m and less

30 m and less

Outdoor unit

8 m and less

HRP71, 100, 125 : A+B+C

!

75 m

4. Installing the refrigerant piping

HRP71, 100, 125

HRP200

Drain socket

PAC-SG61DS-E

Drain pan

PAC-SG64DP-E

PAC-SH97DP-E

5. Drainage piping work

Outdoor unit drainage pipe connection

When drain piping is necessary, use the drain socket or the drain pan (option).

6. Electrical work

6.1. Outdoor unit (Fig. 6-1, Fig. 6-2)

 

1

  Remove the service panel.

 

2

  Wire the cables referring to the Fig. 6-1 and the Fig. 6-2.

C

Fig. 6-1

* With  Heater 

model only

A

  Indoor unit

B

  Outdoor unit

C

  Remote controller

D

  Main switch (Breaker)

E

  Earth

Fig. 6-2

A

D

B

D

D

D

D

D

A

A

A

B

C

E

E

E

E

For Heater

For Power

For Power

For Heater

For Heater

For Heater

L

N

S1 S2 S3

HRP71, 100V

L1 L2 L3 N

S1 S2 S3

HRP100-200Y

Terminal block

Indoor/Outdoor connection terminal block (S1, S2, S3)

Service panel

Clamp

*   Clamp the cables so that they do not contact the center of the service panel or the gas valve.

Note : 

If the protective sheet for the electrical box is removed during servicing, be sure to 

reinstall it.

 Caution:

Be sure to install N-Line. Without N-Line, it could cause damage to the unit.

E

E

Note: Only for Air to water application
When multiple indoor units (Hydro boxes) are connected to the outdoor 
unit, wire the PCB of either one of the indoor unit and the outdoor unit 
(S1,S2,S3).

It is impossible to connect the PCBs of multiple indoor units to the outdoor 
unit.

01̲RG79D564H02̲EN.indd   9

2009/08/26   8:34:18

Summary of Contents for Mr. Slim PUHZ-HRP-HA2

Page 1: ...ees deze handleiding en de installatiehandleiding van het binnenapparaat zorgvuldig door voordat u met het installeren van de airconditioner begint MANUAL DE INSTALACI N Para un uso correcto y seguro...

Page 2: ...ctly overheating or re may result The terminal block cover panel of the outdoor unit must be rmly attached If the cover panel is mounted incorrectly and dust and moisture enter the unit electric shock...

Page 3: ...uch the pipes burns or frostbite may result After stopping operation be sure to wait at least ve minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 U...

Page 4: ...e space as shown Do not install the optional air outlet guides for upward air ow 3 Obstacles at front only Fig 2 14 When using the optional air outlet guides the clearance is 1000 mm or more 4 Obstacl...

Page 5: ...ible Vent Max 30 Set deep in the ground 600 600 Min 360 175 175 Min 10 950 25 330 370 4 Installing the refrigerant piping 4 1 Precautions for devices that use R410A refrigerant Refer to 1 5 for precau...

Page 6: ...C Local piping without oxygen 2 Connect the E Joint pipe to the gas side Stop valve Use 2 wrenches to tighten the are nut If order is reversed refrigerant leak occurs because of the part damaging by...

Page 7: ...to its original position Refrigerant pipes are protectively wrapped The pipes can be protectively wrapped up to a diameter of 90 before or after connecting the pipes Cut out the knockout in the pipe...

Page 8: ...The existing pipe thickness does not meet speci cations or the pipes are damaged Fig 4 9 Indoor unit Outdoor unit Main piping Branch piping Multi distribution pipe option Outdoor unit HRP200 A 9 52 65...

Page 9: ...efrigerant piping HRP71 100 125 HRP200 Drain socket PAC SG61DS E Drain pan PAC SG64DP E PAC SH97DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the...

Page 10: ...ire which is longer than the other cords so that it will not become disconnected when tension is applied A Control Outdoor Unit 3 poles isolator Power supply Isolator A Control Indoor Unit Warning In...

Page 11: ...operation Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the power switch turned on during the operational season The followi...

Page 12: ...the unit is stopped How ever even if the unit is stopped and the SWP switch is set to ON less than three minutes after the compressor stops the refrigerant collecting operation cannot be performed Wai...

Page 13: ...door unit C Master remote controller D Subordinate remote controller E Standard 1 1 Refrigerant address 00 F Simultaneous twin Refrigerant address 01 G Simultaneous triple Refrigerant address 02 E SW...

Reviews: