Caution:

Make sure to perform the “7. Test run” and con

Þ

 rm the unit works without 

any problems, before starting the following settings.

'

 How to select the “Refrigerant Leakage Detection” mode

Detection is possible regardless the unit’s operation (ON or OFF).

1

 Press             button for more than three seconds to switch to the maintenance

mode.
[Display    ] 

MAINTENANCE

'

 How to start the initial learning

2

 Press                          button and select the [GAS LEAK TEST START] (Fig. 8-2)

* The initial learning for the leakage detection is always done once after the new

installation or the data reset.

TEST

A

 CLOCK 

7. Test run

7.1. Before test run

'

  After completing installation and the wiring and piping of the indoor and 

outdoor units, check for refrigerant leakage, looseness in the power sup-
ply or control wiring, wrong polarity, and no disconnection of one phase in 
the supply.

'

  Use a 500-volt megohmmeter to check that the resistance between the 

power supply terminals and ground is at least 1.0M

"

.

'

  Do not carry out this test on the control wiring (low voltage circuit) termi-

nals.

 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0M

"

.

Insulation resistance

After installation or after the power source to the unit has been cut for an extended 
period, the insulation resistance will drop below 1 M

"

 due to refrigerant accumulat-

ing in the compressor. This is not a malfunction. Perform the following procedures.
1.   Remove the wires from the compressor and measure the insulation resistance of 

the compressor.

2.   If the insulation resistance is below 1 M

"

, the compressor is faulty or the resis-

tance dropped due the accumulation of refrigerant in the compressor.

3.   After connecting the wires to the compressor, the compressor will start to warm 

up after power is supplied. After supplying power for the times indicated below, 
measure the insulation resistance again.

  •   The insulation resistance drops due to accumulation of refrigerant in the com-

pressor. The resistance will rise above 1 M

"

 after the compressor is warmed 

up for 4 hours.

     (The  time  necessary  to  warm  up  the  compressor  varies  according  to  atmo-

spheric conditions and refrigerant accumulation.)

  •   To operate the compressor with refrigerant accumulated in the compressor, 

the compressor must be warmed up at least 12 hours to prevent breakdown.

4.   If the insulation resistance rises above 1 M

"

, the compressor is not faulty.

 Caution:

•   The compressor will not operate unless the power supply phase connec-

tion is correct.

•   Turn on the power at least 12 hours before starting operation.

-   Starting operation immediately after turning on the main power switch can result 

in severe damage to internal parts. Keep the power switch turned on during the 
operational season.

'

  The followings must be checked as well.

•   The outdoor unit is not faulty. LED1 and LED2 on the control board of the out-

door unit 

ß

 ash when the outdoor unit is faulty.

•   Both the gas and liquid stop valves are completely open.
•   A  protective  sheet  covers  the  surface  of  the  DIP  switch  panel  on  the  control 

board  of  the  outdoor  unit.  Remove  the  protective  sheet  to  operate  the  DIP 
switches easily.

7.2. Test run

7.2.1. Using SW4 in outdoor unit

SW4-1

ON

Cooling operation

SW4-2

OFF

SW4-1

ON

Heating operation

SW4-2

ON

*  After performing the test run, set SW4-1 to OFF.
•   After power is supplied, a small clicking noise may be heard from the inside of 

the outdoor unit. The electronic expansion valve is opening and closing. The unit 
is not faulty.

•   A few seconds after the compressor starts, a clanging noise may be heard from 

the inside of the outdoor unit. The noise is coming from the check valve due to 
the small difference in pressure in the pipes. The unit is not faulty.

The test run operation mode cannot be changed by DIP switch SW4-2 during 
the test run. (To change the test run operation mode during the test run, stop 
the test run by DIP switch SW4-1. After changing the test run operation mode, 
resume the test run by switch SW4-1.)

7.2.2. Using remote controller

Refer to the indoor unit installation manual.

Note : Occasionally, vapor that is made by the defrost operation may seem
           as if smoke come up from the outdoor unit.

8. Initial settings for refrigerant leakage detection function

[Display

]

Remote control button positions

D

A

C

B

Operation mode

Compressor information Outdoor unit information Indoor unit information

Confirm

Activate/cancel maintenance mode

GAS LEAK
JUDGE

GAS LEAK
TEST START 

Refrigerant leakage
detection judgment

Refrigerant
leakage detection
(initial teaching)

A

Fig. 8-1

Fig. 8-2

[Display  ] Waiting for stabilization

Stabilized

After 45 minutes

D

Fig. 8-3

Press

FILTER

 ( ) button to confirm. (Fig. 8-3)

How to finish the initial learning

Once the unit’s operation is stabilized, the initial learning is completed.

Press

TEST

 button for more than three seconds to cancel the initial learning.

The initial learning can also be cancelled by pressing 

ON/OFF

 button.

* Refer to the Technical Manual for the refrigerant leakage detection judgment method.

This air conditioner (outdoor unit) can detect refrigerant leakage which may happen
during a long period of use. In order to enable the leakage detection, the following
settings are required to let the unit memorize the initial conditions (initial learning).
       * Except HRP200.

01̲RG79D564H02̲EN.indd   11

2009/08/26   8:34:22

Summary of Contents for Mr. Slim PUHZ-HRP-HA2

Page 1: ...ees deze handleiding en de installatiehandleiding van het binnenapparaat zorgvuldig door voordat u met het installeren van de airconditioner begint MANUAL DE INSTALACI N Para un uso correcto y seguro...

Page 2: ...ctly overheating or re may result The terminal block cover panel of the outdoor unit must be rmly attached If the cover panel is mounted incorrectly and dust and moisture enter the unit electric shock...

Page 3: ...uch the pipes burns or frostbite may result After stopping operation be sure to wait at least ve minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 U...

Page 4: ...e space as shown Do not install the optional air outlet guides for upward air ow 3 Obstacles at front only Fig 2 14 When using the optional air outlet guides the clearance is 1000 mm or more 4 Obstacl...

Page 5: ...ible Vent Max 30 Set deep in the ground 600 600 Min 360 175 175 Min 10 950 25 330 370 4 Installing the refrigerant piping 4 1 Precautions for devices that use R410A refrigerant Refer to 1 5 for precau...

Page 6: ...C Local piping without oxygen 2 Connect the E Joint pipe to the gas side Stop valve Use 2 wrenches to tighten the are nut If order is reversed refrigerant leak occurs because of the part damaging by...

Page 7: ...to its original position Refrigerant pipes are protectively wrapped The pipes can be protectively wrapped up to a diameter of 90 before or after connecting the pipes Cut out the knockout in the pipe...

Page 8: ...The existing pipe thickness does not meet speci cations or the pipes are damaged Fig 4 9 Indoor unit Outdoor unit Main piping Branch piping Multi distribution pipe option Outdoor unit HRP200 A 9 52 65...

Page 9: ...efrigerant piping HRP71 100 125 HRP200 Drain socket PAC SG61DS E Drain pan PAC SG64DP E PAC SH97DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the...

Page 10: ...ire which is longer than the other cords so that it will not become disconnected when tension is applied A Control Outdoor Unit 3 poles isolator Power supply Isolator A Control Indoor Unit Warning In...

Page 11: ...operation Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the power switch turned on during the operational season The followi...

Page 12: ...the unit is stopped How ever even if the unit is stopped and the SWP switch is set to ON less than three minutes after the compressor stops the refrigerant collecting operation cannot be performed Wai...

Page 13: ...door unit C Master remote controller D Subordinate remote controller E Standard 1 1 Refrigerant address 00 F Simultaneous twin Refrigerant address 01 G Simultaneous triple Refrigerant address 02 E SW...

Reviews: