background image

12

9.4 Setting the temperature of the ZUBADAN 

ß

 ash injection function

The ZUBADAN 

ß

 ash injection function achieves high heating performance at low outdoor temperatures.

•  The SW9-3 and SW9-4 on the control board of the outdoor unit allow setting of the temperature available for the ZUBADAN 

ß

 ash injection function as shown in the below 

table. 

9.1. Low noise mode (on-site modi

Þ

 cation) (Fig. 9-1)

By performing the following modi

Þ

 cation, operation noise of the outdoor unit can be 

reduced by about 3-4 dB.
The low noise mode will be activated when a commercially available timer or the 
contact input of an ON/OFF switch is added to the CNDM connector (option) on the 
control board of the outdoor unit.
•   The ability varies according to the outdoor temperature and conditions, etc.

1

  Complete the circuit as shown when using the external input adapter  

(PAC-SC36NA). (Option)

2

  SW1 ON: Low noise mode

  SW1 OFF: Normal operation

Note:
When the Dip SW9-1 on the control board of the outdoor unit is ON, set Dip 
SW9-1 to OFF.

A

  Circuit diagram example (low noise mode)

B

  On-site arrangement

C

  External input adapter (PAC-SC36NA)

X: Relay

D

  Outdoor unit control board

E

  Max. 10 m

F

  Power supply for relay

9.3. Refrigerant collecting (pump down)

Perform the following procedures to collect the refrigerant when moving the indoor 
unit or the outdoor unit.

1

  Supply power (circuit breaker).

  *   When power is supplied, make sure that “CENTRALLY CONTROLLED” is not 

displayed  on  the  remote  controller.  If  “CENTRALLY  CONTROLLED”  is  dis-
played, the refrigerant collecting (pump down) cannot be completed normally.

2

  After the gas stop valve is closed, set the SWP switch on the control board of the 

outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor and 
outdoor units) start operating and refrigerant collecting operation begins. LED1 
and LED2 on the control board of the outdoor unit are lit.

  *   Only set the SWP switch (push-button type) to ON if the unit is stopped. How-

ever, even if the unit is stopped and the SWP switch is set to ON less than 
three minutes after the compressor stops, the refrigerant collecting operation 
cannot be performed. Wait until compressor has been stopped for three min-
utes and then set the SWP switch to ON again.

A

Fig. 9-1

3

  Because the unit automatically stops in about 2 to 3 minutes after the refrigerant 

collecting operation (LED1 and LED2 are lit), be sure to quickly close the gas 
stop valve. When LED1 and LED2 are lit and the outdoor unit is stopped, open 
the liquid stop valve completely, and then repeat step 

2

 after 3 minutes have 

passed.

  *   If the refrigerant collecting operation has been completed normally (LED1 and 

LED2 are lit), the unit will remain stopped until the power supply is turned off.

4

  Turn off the power supply (circuit breaker).

  *  Note that when the length of the extension piping is long, it may not be pos-

sible  to  perform  a  pump-down  operation.  When  performing  the  pump-down 
operation, make sure that the low pressure is lowered to near 0 MPa (gauge).

A

   Circuit diagram example (Demand function)

B

   On-site arrangement

C

  External input adapter (PAC-SC36NA)

Y: Relay

D

  Outdoor unit control board

E

  Max. 10 m

F

  Power supply for relay

9.2. Demand function (on-site modi

Þ

 cation) (Fig. 9-2)

By performing the following modi

Þ

 cation, energy consumption can be reduced to 0

–100% of the normal consumption.
The demand function will be activated when a commercially available timer or the 
contact input of an ON/OFF switch is added to the CNDM connector (option) on the 
control board of the outdoor unit.

1

  Complete the circuit as shown when using the external input adapter  

(PAC-SC36NA). (Option)

By setting SW7-1 and SW7-2 on the control board of the outdoor unit, the ener-

gy consumption (compared to the normal consumption) can be limited as shown 
below.

SW7-1

SW7-2

Energy consumption (SW2 ON)

OFF

OFF

0% (Stop)

ON

OFF

50%

OFF

ON

75%

9. Special Functions

SW1

Orange

1

3

Brown

Red

CNDM

X

X

C

D

SW2

Orange

1

3

Brown

Red

CNDM

Y

Y

Fig. 9-2

A

C

D

SW9-3

SW9-4

Outdoor temperatures

OFF

OFF

#

 3

û

C (Initial setting)

OFF

ON

#

 0

û

C

ON

OFF

#

 –3

û

C

ON

ON

#

 –6

û

C

01̲RG79D564H02̲EN.indd   12

2009/08/26   8:34:24

Summary of Contents for Mr. Slim PUHZ-HRP-HA2

Page 1: ...ees deze handleiding en de installatiehandleiding van het binnenapparaat zorgvuldig door voordat u met het installeren van de airconditioner begint MANUAL DE INSTALACI N Para un uso correcto y seguro...

Page 2: ...ctly overheating or re may result The terminal block cover panel of the outdoor unit must be rmly attached If the cover panel is mounted incorrectly and dust and moisture enter the unit electric shock...

Page 3: ...uch the pipes burns or frostbite may result After stopping operation be sure to wait at least ve minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 U...

Page 4: ...e space as shown Do not install the optional air outlet guides for upward air ow 3 Obstacles at front only Fig 2 14 When using the optional air outlet guides the clearance is 1000 mm or more 4 Obstacl...

Page 5: ...ible Vent Max 30 Set deep in the ground 600 600 Min 360 175 175 Min 10 950 25 330 370 4 Installing the refrigerant piping 4 1 Precautions for devices that use R410A refrigerant Refer to 1 5 for precau...

Page 6: ...C Local piping without oxygen 2 Connect the E Joint pipe to the gas side Stop valve Use 2 wrenches to tighten the are nut If order is reversed refrigerant leak occurs because of the part damaging by...

Page 7: ...to its original position Refrigerant pipes are protectively wrapped The pipes can be protectively wrapped up to a diameter of 90 before or after connecting the pipes Cut out the knockout in the pipe...

Page 8: ...The existing pipe thickness does not meet speci cations or the pipes are damaged Fig 4 9 Indoor unit Outdoor unit Main piping Branch piping Multi distribution pipe option Outdoor unit HRP200 A 9 52 65...

Page 9: ...efrigerant piping HRP71 100 125 HRP200 Drain socket PAC SG61DS E Drain pan PAC SG64DP E PAC SH97DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the...

Page 10: ...ire which is longer than the other cords so that it will not become disconnected when tension is applied A Control Outdoor Unit 3 poles isolator Power supply Isolator A Control Indoor Unit Warning In...

Page 11: ...operation Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the power switch turned on during the operational season The followi...

Page 12: ...the unit is stopped How ever even if the unit is stopped and the SWP switch is set to ON less than three minutes after the compressor stops the refrigerant collecting operation cannot be performed Wai...

Page 13: ...door unit C Master remote controller D Subordinate remote controller E Standard 1 1 Refrigerant address 00 F Simultaneous twin Refrigerant address 01 G Simultaneous triple Refrigerant address 02 E SW...

Reviews: