—47—
Do the transmission cables meet regulations? (Type, diameter)
Checkpoint
1
No.
2
Is the signal cable wired at least 5 cm away from the power supply cable?
3
Are multiple transmission or signal cables wired to the same power cable
duct?
4
Are multiple signal cables wired with multi core cables?
5
Are the signal cables securely connected to the terminals?
6
Are the signal cables connected to the specified terminal blocks?
Mr. Slim control signal
: TM2
1
,
2
Charged signal
: TM2
1
,
2
Uncharged a-contact signal: TM2
1
,
3
7
Is the wiring length of the signal cable within the regulations?
Mr. Slim control signal
: Total extension within 500 m
Charged signal
: Within limitation of the external device
Uncharged a-contact signal: Total extension within 500 m
Action
Use specified cables.
Wire the signal cable at least 5 cm
away from the power supply cable.
Wire the transmission cables away
from the signal cables.
Using suitable cables, wire the sig-
nal cables so that they are separat-
ed from one another.
Connect them securely.
Connect them to the specified termi-
nal blocks.
Wire within the regulations.
Signal cables from external devices (Table 1-1-3)
Check the following checkpoints when connecting with level signal/pulse signal output devices, and Mr. Slim units.
8
Do the external signals meet specifications?
Level signal: Charged 12 V DC/ 24 V DC, uncharged a-contact
Pulse signal: Charged 12 V DC/ 24 V DC, uncharged a-contact
(A pulse width of 200 ms or greater is required)
Input a signal that suits the specifi-
cations.
9
Are the type of input signal and the setting of the pulse input matched?
Pulse signal
: ON setting
Other than pulse signal: OFF setting
<When using PZ-60DR-E>
Check the pulse input setting from
the function selection. (Refer to page 42)
<When not using PZ-60DR-E>
Check the setting of the pulse input
switch (SW2-2) on the Lossnay cir-
cuit board. (Refer to page 38)
10
In a system with multiple Lossnay units, are the signal cables connected to
the specified Lossnay unit?
Basic system (PZ-60DR-E, PZ-41SLB-E):
Lossnay unit for which the Main/Sub selection switch (SW1) is set to “Main”
M-Net control:
Lossnay unit that is set to the address with the smallest number within the group
Connect the signal cables to the
specified Lossnay unit.
11
When PZ-60DR-E is not used, are the function selection switches (SW2,
SW5) on the Lossnay circuit board set correctly?
Set the switches correctly to corre-
spond with the application.
(Refer to page 38 and 39)
12
When PZ-60DR-E is used, is the function selection set correctly?
Set it correctly to correspond with
the application.
(Refer to page 40 to 42)
Summary of Contents for LGH-100RX5-E
Page 4: ...4 2 Specifications...
Page 5: ...5...
Page 6: ...6...
Page 7: ...7...
Page 8: ...8...
Page 9: ...Unit mm LGH 15RX5 E 3 Outside dimensions 9...
Page 10: ...Unit mm LGH 25RX5 E 10...
Page 11: ...Unit mm LGH 35RX5 E 11...
Page 12: ...12 Unit mm LGH 50RX5 E...
Page 13: ...Unit mm LGH 65RX5 E 13...
Page 14: ...14 Unit mm LGH 80RX5 E...
Page 15: ...Unit mm LGH 100RX5 E 15...
Page 16: ...16 Unit mm LGH 150RX5 E...
Page 17: ...Unit mm LGH 200RX5 E 17...