LGH-100RX5-E

21 Spl nut (12)

R50 218 067

2

Left-handed

22 Washer (12)

K83 466 113

2

23 Centrifugal fan

R50 543 480

2

φ 245

24 Fan base

R50 543 709

2

25 Inlet ring

R50 543 708

2

26 Nut (6)

H00 061 050

8

27 Key

Y50 033 104

2

5×5×11.5

28 Motor

Y50 118 451

2

29 Motor fix plate

Y50 117 712

2

30 PTT screw 5×10

H00 189 007

16

31 Spl washer (6)

M34 043 080

8

32 PT screw 6×20

H00 157 008

8

33 Cord bush

M45 649 226

4

34 Connector cover

Y50 115 709

2

35 Cord band

M45 017 228

2

36 Connector plate

Y50 115 710

2

37 PTT screw 4×6

H00 312 007

2

38 Separator

R50 543 489

2

39 Lead wire clip

D41 123 223

1

No.

Name of part

Parts No.

Q'ty

pcs/unit

Critical

for

safety

Remarks

108

Summary of Contents for LGH-100RX5-E

Page 1: ...HANDBOOK Model LGH 15RX5 E LGH 25RX5 E LGH 35RX5 E LGH 50RX5 E LGH 65RX5 E LGH 80RX5 E LGH 100RX5 E Nameplate LGH 150RX5 E LGH 200RX5 E Nameplate Model PZ 60DR E Model PZ 25RF8 E PZ 35RF8 E PZ 50RF8...

Page 2: ...5 Basic circuit diagram 21 6 Fundamentals of operation 22 44 7 Troubleshooting 45 65 8 Disassembly and assembly 66 68 9 Parts catalog 69 123 LGH 15RX5 E 70 75 LGH 25RX5 E 76 81 LGH 35RX5 E 82 87 LGH 5...

Page 3: ...struction Electric shock If you must inspect the circuitry while the power is on do not touch the live parts Failure to heed this warning may result in elec tric shock Caution for electric shock Modif...

Page 4: ...4 2 Specifications...

Page 5: ...5...

Page 6: ...6...

Page 7: ...7...

Page 8: ...8...

Page 9: ...Unit mm LGH 15RX5 E 3 Outside dimensions 9...

Page 10: ...Unit mm LGH 25RX5 E 10...

Page 11: ...Unit mm LGH 35RX5 E 11...

Page 12: ...12 Unit mm LGH 50RX5 E...

Page 13: ...Unit mm LGH 65RX5 E 13...

Page 14: ...14 Unit mm LGH 80RX5 E...

Page 15: ...Unit mm LGH 100RX5 E 15...

Page 16: ...16 Unit mm LGH 150RX5 E...

Page 17: ...Unit mm LGH 200RX5 E 17...

Page 18: ...18 Unit mm PZ 60DR E Unit mm PZ 25RF8 E PZ 35RF8 E PZ 50RF8 E PZ 65RF8 E PZ 80RF8 E PZ 100RF8 E...

Page 19: ...trical regulations Always use double insulated PVC cable for the transmission cables Wiring work must be performed by qualified professionals All supply circuits must be disconnected before obtaining...

Page 20: ...al electrical regulations Always use double insulated PVC cable for the transmission cables Wiring work must be performed by qualified professionals All supply circuits must be disconnected before obt...

Page 21: ...ventilation When SW5 6 is ON During operation and when the outdoor air temperature is 5 C to 15 C 0 While stopped or when the outdoor air temperature is 15 C TM3 6 7 Thermistor RA OA CN5 LED 2 Red Wh...

Page 22: ...e controller PZ 60DR E or PZ 41SLB E One remote controller oper ates one Lossnay unit Two remote controllers oper ate one Lossnay unit Last touch priority operation PZ 60DR E and PZ 41SLB E cannot be...

Page 23: ...rom an air conditioner remote con troller Having PZ 60DR E or PZ 52SF E last touch priority operation is permitted with the air conditioner remote controller and the Lossnay remote controller 1 PZ 41S...

Page 24: ...troller MA remote controller PAR 20 21MAA Wireless remote controller PAR FA FL 31MA Compact remote controller PAC YT51CRA Compact remote controller PAC SE51CRA ME remote controller PAR F27MEA PAR 21MA...

Page 25: ...lection is not available from the K control remote controller Extra Low fan speed selection is not available from the A control and K control remote controllers System interlocked with Mr Slim None Fi...

Page 26: ...ance is adjusted to suit the usage environment or the place of installation Multi venti lation mode Power supply exhaust when operation starts ON Refer to page 41 During the first 30 minutes of operat...

Page 27: ...Ventilation mode control Lossnay heat exchange ventilation or bypass normal ventilation is achieved by switching the air duct inside the Lossnay unit with a damper 1 Ventilation mode There are 3 contr...

Page 28: ...em interlocked with City Multi indoor units Up to two of the Lossnay remote controllers PZ 60DR E PZ 41SLB E and PZ 52SF E can be used in the same group but they cannot be used together with a differe...

Page 29: ...ture map Ventilation mode switching of Lossnay ventilation Bypass ventilation in the automatic ventilation mode is in accordance with the following map a Systems interlocked with Mr Slim and City Mult...

Page 30: ...tained Lossnay ventilation area Bypass ventilation area Undetermined area Bypass Ventilation Bypass Ventilation Undetermined area b When there is no interlocking with Mr Slim and City Multi indoor uni...

Page 31: ...te controller or ME remote con troller and the ventilation setting The City Multi indoor unit operation mode target tempera ture and other internal information can also be brought in Systems interlock...

Page 32: ...he pulse signal is input Stopping is by remote controller ON interlock Lossnay will start with the start signal of the external device Stopping is by remote controller Interlock mode setting on SW5 7...

Page 33: ...s a common terminal with bypass operation monitor operation monitor with delay function 2 output 7 2 Terminal 7 of TM3 is a common terminal with malfunction monitor output 7 3 The operation monitor ca...

Page 34: ...rd and input the signal uncharged a contact from a CO2 sensor to the brown and red lines When the contacts in the diagram below are ON closed the system will switch to High Extra High fan speed regard...

Page 35: ...s within the same group When not using PZ 60DR E input bypass ventilation switching into each Lossnay unit The setting is applied only to the Lossnay units that have received input Operation Multiple...

Page 36: ...accumulated heat and there by reduce the air conditioning load the next morning If Night purge is enabled per the Installation Manual 5 Function Selection 5 8 night purge operation will be performed...

Page 37: ...satisfied Night Purge mode is active no operation 1 00 A M Outdoor temperature 17 C 28 C or more within 24 hours Temperature monitoring operation 5 minutes Night Purge operation Bypass ventilation 55...

Page 38: ...lter cleaning dis play ON 3 000 hours OFF No filter maintenance display Factory setting 5 TM3 6 7 output setting ON Operation monitor output with delay functions 2 Refer to 3 2 Fan speed control by fu...

Page 39: ...in In systems with multiple Lossnay units be sure that one unit is set to Main and that all the others are set to Sub When interlocked with an external device be sure to connect the external device to...

Page 40: ...tion lock Factory setting no2 All button lock oFF Stops operation by pressing the ON OFF button during operation Factory setting on Extra Low fan speed operation by pressing the ON OFF button during o...

Page 41: ...H L Fixed at Low fan speed Multiple ventilation mode L Do not execute power supply exhaust when operation starts Factory setting oFF Execute power supply exhaust when opera tion starts 30 minutes on I...

Page 42: ...the ventilation mode will not be possible during night purge operation Bypass ventilation fixed 11 Refer to 4 5 Automatic ventilation algorithm temperature map 12 External input priority will not be p...

Page 43: ...witch condition of the Main Lossnay Example 001 will be displayed when the address is number 01 Lossnay address switch condition Self diagnosis Error history Error history clear Returns all of the rem...

Page 44: ...truction by Lossnay remote controller or external device Extra Low fan speed operation when using PZ 60DR E other than the LGH 150 and 200 types High Extra High fan speed Low fan speed High Extra High...

Page 45: ...eshooting 4 Check the checklist for the remote controllers Table 3 1 to 3 2 Check the Lossnay checklist Table 4 Yes No No This is normal No No Yes Yes Yes 45 7 Troubleshooting I Work precautions When...

Page 46: ...41SLB E TM4 1 2 M NET control TAB5 A B 7 Is the wiring length of the transmission cable within the regulations Basic system PZ 60DR E PZ 41SLB E Total extension within 500 m M NET control Maximum ext...

Page 47: ...ith level signal pulse signal output devices and Mr Slim units 8 Do the external signals meet specifications Level signal Charged 12 V DC 24 V DC uncharged a contact Pulse signal Charged 12 V DC 24 V...

Page 48: ...r supply fan operation monitor mal function monitor bypass operation monitor and operation monitor with delay function 8 When using the operation monitor is the setting of the output signal cor rect W...

Page 49: ...gth of the trans mission cable wiring Using suitable cables wire the transmission cables so that they are separated from one another Use the same type of remote controller 3 Interlock operation with e...

Page 50: ...an address corresponding to interlock operation Check the length of the trans mission cable wiring See the technical manual for details about the regulations Change to the PZ 60DR E or PZ 52SF E remo...

Page 51: ...2SF E goes blank and the system does not start The restricted number of connected PZ 52SF E units have been exceeded The length of the transmission cable wiring is longer than specified longer than ma...

Page 52: ...ot been performed by PZ 52SF E Lossnay address setting SA1 SA2 is wrong Lossnay address setting SA1 SA2 was changed The transmission cable power supply restric tions have been exceeded Group setting h...

Page 53: ...wer supply cable Check the transmission cable connection Check the length of the transmission cable wiring Error Cause Action RC6608 SRC 6608 Communica tion error between remote con trollers when two...

Page 54: ...nger than specified longer than 500 m Turn off the main power and set the Main Sub selection switch SW1 Set the first unit to Main and the second and following units to Sub Using suitable cables wire...

Page 55: ...e external devices When external devices are not con nected check the TM3 6 7 output setting switch SW5 6 Refer to page 38 3602 3 blinks Damper related error Damper board operation is not cor rect Con...

Page 56: ...o Sub Using suitable cables wire the transmission cables so that they are separated from one another Wire the transmission cable at least 5 cm away from the power supply cable Check the transmission c...

Page 57: ...cal switching CN32 is set to Remote Check the setting of the MELANS Check the interlock mode set ting Refer to page 32 Check the remote local switching CN32 Refer to page 35 6 Cannot switch fan speed...

Page 58: ...n will not be in accordance with the setting Perform the timer setting with one remote controller only and use the other remote controller as Timer off indicator Error Cause Action 10 The fan does not...

Page 59: ...E or MELANS Power is not supplied to Lossnay Power that does not follow specifications is used Transmission cable to the Lossnay is not con nected Transmission cable is connected to the wrong terminal...

Page 60: ...device Uncharged a contact Longer than 500 m Mr Slim signal Longer than 500 m The Delay operation is set with the function selection of PZ 60DR E or PZ 41SLB E or the function selection switch SW5 1 o...

Page 61: ...ing for air conditioner defrost ing with the PZ 60DR E function selection or the function selec tion switch SW5 3 Refer to page 38 and 42 7 Fan speed will not change High Low Extra Low fan speed switc...

Page 62: ...ion monitor out put setting with the PZ 60DR E function selection or the function selection switch SW5 2 on the Lossnay circuit board Refer to page 38 and 41 11 Night purge operation does not work eve...

Page 63: ...mal dis play of PZ 60DR E or when returning to the normal display from the function selection mode or the maintenance mode Button operations may not be accepted immediately depending on commu nication...

Page 64: ...following circum stances The night purge conditions have not been satisfied Lossnay has been started or stopped during the display of Night purge Night purge operation will not be performed when CENT...

Page 65: ...3 1 20 32 8 5 16 5 10 8 8 25 5 0 40 3 0 19 31 2 4 15 7 11 8 5 26 4 8 41 2 8 18 29 8 3 15 1 12 8 1 27 4 7 42 2 7 17 28 4 2 14 5 13 7 8 28 4 5 43 2 7 16 27 1 1 13 8 14 7 6 29 4 3 44 2 6 15 25 8 0 13 3 1...

Page 66: ...ns according to the instructions described in the troubleshooting When servicing always keep proper footing When servicing make sure that the power cord is pulled out of the outlet or the power supply...

Page 67: ...Unscrew the fixing screws two special screws 4 x 22 5 indicated by 67 4 Slide the connector covers with the connector toward the Lossnay core side and then take them off from the unit 5 Remove the co...

Page 68: ...di cated by for the motor fix plate SA side Remove the EA side motor in the same way Separator Instructions When reassembling the unit assemble it in the reverse order of disassembly Always make sure...

Page 69: ...screw PTT screw PT screw SET screw SQ SET screw P SET screw PMT screw HS SET screw P R W screw P C W screw P R C W screw R W screw PW PP screw SW PW PP screw Description Cross recess flat head machin...

Page 70: ...50 541 380 4 6 Cover R50 541 717 2 7 Flange Y50 115 619 4 8 PTT screw 4 8 H00 000 487 46 9 Maint cover R50 541 487 1 10 Filter X50 039 717 4 11 Lossnay core R50 541 718 2 With filter stoppers 12 Core...

Page 71: ...71 LGH 15RX5 E 8 8 8 8 8 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 4 7 8 8 10 5 1 2 2 5 7 7 2 shows accessory parts...

Page 72: ...te R50 214 708 4 27 PTT screw 4 10 H00 000 332 13 28 Motor fix plate R50 541 712 2 29 Cord clamper D43 008 223 2 30 Motor Y50 115 453 1 31 PTT screw 4 6 H00 312 007 16 32 Cord bush M45 649 226 2 33 Co...

Page 73: ...73 21 22 23 24 25 26 27 28 29 30 31 34 33 32 35 27 32 31 26 27 27 26 29 28 26 24 23 22 21 31 31 27 36 36 31 LGH 15RX5 E...

Page 74: ...440VAC 55 PPT screw 3 8 H00 003 005 1 56 Circuit board Y50 115 171 1 LG X3 E 57 Lock washer 4 H00 013 076 2 58 Transformer Y50 115 216 1 AC230V 59 PT screw 4 8 BS H00 011 008 1 60 Cord band M45 017 2...

Page 75: ...75 42 48 43 41 50 51 49 52 53 54 55 56 57 58 59 60 61 62 63 68 69 70 71 72 64 65 66 67 44 46 45 47 70 54 64 57 31 45 8 8 8 8 8 8 8 8 8 8 8 8 8 shows accessory parts LGH 15RX5 E...

Page 76: ...50 541 380 4 6 Cover R50 541 717 2 7 Flange Y50 075 609 4 8 PTT screw 4 8 H00 000 487 46 9 Maint cover R50 541 487 1 10 Filter X50 039 717 4 11 Lossnay core R50 541 718 2 With filter stoppers 12 Core...

Page 77: ...77 8 8 8 8 8 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 4 7 8 8 10 5 1 2 2 5 7 7 2 LGH 25RX5 E shows accessory parts...

Page 78: ...te R50 214 708 4 27 PTT screw 4 10 H00 000 332 13 28 Motor fix plate R50 541 712 2 29 Cord clamper D43 008 223 2 30 Motor Y50 115 455 1 31 PTT screw 4 6 H00 312 007 14 32 Cord bush M45 649 226 2 33 Co...

Page 79: ...79 21 22 23 24 25 26 27 28 29 30 31 34 33 32 35 27 32 31 26 27 27 26 29 28 26 24 23 22 21 31 31 27 36 36 31 LGH 25RX5 E...

Page 80: ...440VAC 55 PPT screw 3 8 H00 003 005 1 56 Circuit board Y50 115 171 1 LG X3 E 57 Lock washer 4 H00 013 076 2 58 Transformer Y50 115 216 1 AC230V 59 PT screw 4 8 BS H00 011 008 1 60 Cord band M45 017 2...

Page 81: ...81 42 48 43 41 50 51 49 52 53 54 55 56 57 58 59 60 61 62 63 68 69 70 71 72 64 65 66 67 44 46 45 47 70 54 64 57 31 45 8 8 8 8 8 8 8 8 8 8 8 8 8 LGH 25RX5 E shows accessory parts...

Page 82: ...50 541 380 4 6 Cover R50 541 717 2 7 Flange Y50 075 609 4 8 PTT screw 4 8 H00 000 487 48 9 Maint cover R50 542 486 1 10 Filter Y50 116 717 4 11 Lossnay core R50 542 710 2 With filter stoppers 12 Core...

Page 83: ...83 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 7 8 10 5 1 2 2 5 7 7 8 4 2 8 8 8 8 8 LGH 35RX5 E shows accessory parts...

Page 84: ...ate Y50 116 712 2 28 PTT screw 5 10 H00 189 007 8 29 Cord clamper D43 008 223 2 30 Cord bush M45 649 226 4 31 Connector cover Y50 115 709 2 32 PTT screw 4 6 H00 312 007 15 33 Connector plate Y50 115 7...

Page 85: ...85 21 22 23 24 25 26 27 28 29 29 27 26 24 23 22 21 36 37 25 34 31 32 30 33 30 31 30 32 8 8 30 33 28 38 35 36 37 38 35 LGH 35RX5 E...

Page 86: ...k washer 4 H00 013 076 2 53 Transformer Y50 115 216 1 AC230V 54 PT screw 4 8 BS H00 011 008 1 55 TB fix plate Y50 115 712 1 56 Cord band K83 170 228 2 White 57 PCB fix plate R50 546 705 1 58 Bush R50...

Page 87: ...87 42 41 44 43 46 47 45 48 49 50 51 57 56 58 65 62 64 63 67 66 8 8 8 8 8 8 8 66 62 8 8 8 8 34 8 32 52 53 54 59 60 61 55 59 52 8 LGH 35RX5 E shows accessory parts...

Page 88: ...50 541 380 4 6 Cover R50 542 706 2 7 Flange R50 429 609 4 8 PTT screw 4 8 H00 000 487 48 9 Maint cover R50 542 486 1 10 Filter R50 521 717 4 11 Lossnay core R50 542 711 2 With filter stoppers 12 Core...

Page 89: ...89 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 7 8 10 5 1 2 2 5 7 7 8 4 2 8 8 8 8 8 LGH 50RX5 E shows accessory parts...

Page 90: ...ate Y50 116 712 2 28 PTT screw 5 10 H00 189 007 8 29 Cord clamper D43 008 223 2 30 Cord bush M45 649 226 4 31 Connector cover Y50 115 709 2 32 PTT screw 4 6 H00 312 007 15 33 Connector plate Y50 115 7...

Page 91: ...91 21 22 23 24 25 26 27 28 29 29 27 26 24 23 22 21 36 37 25 34 31 32 30 33 30 31 30 32 8 8 30 33 28 38 35 36 37 38 35 LGH 50RX5 E...

Page 92: ...k washer 4 H00 013 076 2 53 Transformer Y50 115 216 1 AC230V 54 PT screw 4 8 BS H00 011 008 1 55 TB fix plate Y50 115 712 1 56 Cord band K83 170 228 2 White 57 PCB fix plate R50 546 705 1 58 Bush R50...

Page 93: ...93 42 41 44 43 46 47 45 48 49 50 51 57 56 58 65 62 64 63 67 66 8 8 8 8 8 8 8 66 62 8 8 8 8 34 8 32 52 53 54 59 60 61 55 59 52 8 LGH 50RX5 E shows accessory parts...

Page 94: ...50 543 380 4 6 Cover R50 542 706 2 7 Flange R50 429 609 4 8 PTT screw 4 8 H00 000 487 55 9 Maint cover R50 543 486 1 10 Filter R50 524 717 4 11 Lossnay core R50 543 710 2 With filter stoppers 12 Core...

Page 95: ...95 8 8 8 8 8 2 1 13 12 14 11 10 9 3 4 5 6 7 8 5 7 7 7 8 10 13 5 1 2 2 2 5 8 4 LGH 65RX5 E shows accessory parts...

Page 96: ...sher 6 M34 043 080 8 28 Key Y50 033 104 2 5 5 11 5 29 Motor Y50 117 453 2 30 Motor fix plate R50 543 712 2 31 PTT screw 5 10 H00 189 007 16 32 Nut 6 H00 061 050 8 33 Cord bush M45 649 226 4 34 Connect...

Page 97: ...97 31 31 25 24 23 22 21 31 30 29 31 37 28 31 34 33 33 36 26 27 33 31 32 21 22 23 24 25 27 26 28 29 30 31 32 35 34 33 36 38 38 37 LGH 65RX5 E...

Page 98: ...k washer 4 H00 013 076 2 63 Transformer Y50 115 216 1 AC230V 64 PT screw 4 8 BS H00 011 008 1 65 TB fix plate Y50 115 712 1 66 Cord band K83 170 228 2 White 67 PCB fix plate R50 546 705 1 68 Bush R50...

Page 99: ...99 51 52 54 53 56 57 55 58 59 60 61 67 68 75 72 74 73 77 76 8 8 8 8 8 8 8 8 76 72 8 8 8 8 35 8 62 63 64 66 69 70 71 65 69 62 8 LGH 65RX5 E shows accessory parts...

Page 100: ...50 095 380 4 6 Cover R50 543 704 2 7 Flange Y50 021 609 4 8 PTT screw 4 8 H00 000 487 54 9 Maint cover R50 543 487 1 10 Filter R50 529 717 4 11 Lossnay core R50 543 711 2 With filter stoppers 12 Core...

Page 101: ...101 8 8 8 8 8 2 1 13 12 14 11 10 9 3 4 5 6 7 8 5 7 7 7 8 14 10 5 1 2 2 2 5 8 4 LGH 80RX5 E shows accessory parts...

Page 102: ...otor Y50 117 454 2 29 Motor fix plate Y50 117 712 2 30 PTT screw 5 10 H00 189 007 16 31 Spl washer 6 M34 043 080 8 32 PT screw 6 20 H00 157 008 8 33 Cord bush M45 649 226 4 34 Connector cover Y50 115...

Page 103: ...103 30 30 25 24 23 22 21 30 30 32 29 28 30 37 30 27 34 33 33 36 26 33 30 31 21 22 23 24 25 26 27 28 29 30 31 32 39 35 34 33 36 38 38 37 LGH 80RX5 E...

Page 104: ...washer 4 H00 013 076 2 63 Transformer Y50 115 216 1 AC230V 64 PT screw 4 8 BS H00 011 008 1 65 TB fix plate Y50 115 712 1 66 Cord band K83 170 228 2 White 67 PCB fix plate R50 546 705 1 68 Bush R50 4...

Page 105: ...105 51 52 54 53 56 57 55 58 59 60 61 67 68 75 72 74 73 77 76 8 8 8 8 8 8 8 8 76 72 8 8 8 8 35 8 62 63 64 66 69 70 71 65 8 62 69 LGH 80RX5 E shows accessory parts...

Page 106: ...50 095 380 4 6 Cover R50 543 704 2 7 Flange Y50 021 609 4 8 PTT screw 4 8 H00 000 487 54 9 Maint cover R50 543 487 1 10 Filter R50 522 717 4 11 Lossnay core R50 544 710 2 With filter stoppers 12 Core...

Page 107: ...107 2 1 13 14 11 12 10 9 3 4 5 6 7 8 5 7 8 10 14 5 1 2 2 2 5 8 7 7 4 8 8 8 8 8 LGH 100RX5 E shows accessory parts...

Page 108: ...Motor Y50 118 451 2 29 Motor fix plate Y50 117 712 2 30 PTT screw 5 10 H00 189 007 16 31 Spl washer 6 M34 043 080 8 32 PT screw 6 20 H00 157 008 8 33 Cord bush M45 649 226 4 34 Connector cover Y50 115...

Page 109: ...109 30 30 25 24 23 22 21 30 30 32 30 29 28 27 30 34 37 33 33 36 26 33 30 31 21 22 23 24 25 26 27 28 29 30 39 31 32 35 34 33 36 38 37 38 LGH 100RX5 E...

Page 110: ...76 2 63 Transformer Y50 115 216 1 AC230V 64 PT screw 4 8 BS H00 011 008 1 65 TB fix plate Y50 115 712 1 66 Cord band K83 170 228 2 White 67 PCB fix plate R50 546 705 1 68 Bush R50 476 225 1 69 PP scre...

Page 111: ...to the new capacitors 2 No 78 during production so there are two types of the capacitors on the market Check the production number production year and month shown on the nameplate and choose the appli...

Page 112: ...7 99 6 Flange R50 545 704 2 7 Hinge R50 466 344 2 8 Hanger R50 111 381 8 9 PT screw 6 12 H00 000 244 40 10 Filter R50 529 717 8 11 Lossnay core R50 543 711 4 With filter stoppers 12 Core guide R R50 5...

Page 113: ...113 8 8 8 8 8 8 2 1 3 4 11 10 12 13 15 14 6 8 7 9 5 3 3 3 2 10 8 8 8 9 8 8 13 15 14 15 15 5 6 5 9 5 5 LGH 150RX5 E shows accessory parts...

Page 114: ...otor Y50 117 454 4 29 Motor fix plate Y50 117 712 4 30 PTT screw 5 10 H00 189 007 32 31 Spl washer 6 M34 043 080 16 32 PT screw 6 20 H00 157 008 16 33 Cord bush M45 649 226 8 34 Connector cover Y50 11...

Page 115: ...115 30 30 25 24 23 22 21 30 29 28 30 30 37 30 27 34 33 33 36 26 33 30 31 32 21 22 23 24 25 26 27 28 29 39 30 31 32 35 34 33 36 37 38 38 LGH 150RX5 E...

Page 116: ...d band K83 170 228 3 White 67 PPT screw 3 6 H00 000 384 12 68 Relay Y50 009 268 6 LY 2F 69 Circuit board Y50 115 171 1 LG X3 E 70 PCB case D40 169 382 1 71 PP screw 4 8 H00 000 003 6 72 Transformer Y5...

Page 117: ...117 51 52 53 55 54 66 75 76 85 81 82 73 56 59 60 61 68 67 72 71 70 69 62 63 64 65 57 58 35 71 71 71 82 52 55 5 5 64 64 5 64 5 5 5 52 74 80 79 78 77 83 84 LGH 150RX5 E shows accessory parts...

Page 118: ...7 99 6 Flange R50 545 704 2 7 Hinge R50 466 344 2 8 Hanger R50 111 381 8 9 PT screw 6 12 H00 000 244 40 10 Filter R50 522 717 8 11 Lossnay core R50 544 710 4 With filter stoppers 12 Core guide R R50 5...

Page 119: ...119 8 8 8 8 8 8 2 1 3 4 11 10 12 13 15 14 6 8 7 9 5 3 3 3 2 10 8 8 8 9 8 8 13 15 14 15 15 5 6 5 9 5 5 LGH 200RX5 E shows accessory parts...

Page 120: ...otor Y50 118 451 4 29 Motor fix plate Y50 117 712 4 30 PTT screw 5 10 H00 189 007 32 31 Spl washer 6 M34 043 080 16 32 PT screw 6 20 H00 157 008 16 33 Cord bush M45 649 226 8 34 Connector cover Y50 11...

Page 121: ...121 30 30 25 24 23 22 21 30 29 28 30 30 37 30 27 34 33 33 36 26 33 30 31 32 21 22 23 24 25 26 27 28 29 39 30 31 32 35 34 33 36 37 38 38 LGH 200RX5 E...

Page 122: ...384 12 67 Relay Y50 009 268 6 LY 2F 68 Control base Y50 118 708 1 69 Support plate Y50 118 710 1 70 Circuit board Y50 115 171 1 LG X3 E 71 PCB case D40 169 382 1 72 PP screw 4 8 H00 000 003 6 73 Tran...

Page 123: ...1 No 64 were changed to the new capacitors 2 No 86 during production so there are two types of the capacitors on the market Check the production number production year and month shown on the nameplat...

Reviews: