3 - 1 3 - 1
MELSEC-F
3 SPECIFICATIONS
3
3 SPECIFICATIONS
This section explains the Ethernet module performance specifications and
transmission specifications.
For more details on the general specifications, refer to the User's Manual for the PLC
base module.
3.1 Performance Specifications
The following explains the performance specifications of the Ethernet module.
Item Specification
Data transmission speed
100 M bps
10 M bps
Communication mode
Full-duplex/Half-duplex
Transmission method
Base band
Maximum segment length
100 m (328’ 1”) *1
Transmission
specifications
Maximum number of
nodes/connection
Cascade connection Maximum 2 stages
Cascade connection Maximum 4 stages
Number of simultaneously open
connections allowed
8 connections
(Connections usable by the sequence program)
Fixed buffer
1023 word
×
8
Attached file
2048 words
×
1
Transmission
data storage
memory
Main text
256 words
×
1
Number of I/O occupied points
8 points
Power supply
24V DC +20%, -15%, ripple (p-p) less than 5%
External 24V current consumption
240 mA
Number of connectable units to the main unit
1
Applicable PLC
FX
3U
/FX
3UC
PLC
Ver. 2.21 or later
External dimensions
90 (3.55”) (H)
×
55 (2.17”) (W)
×
87 (3.43”) (D) [mm] (inches)
Weight
0.3 kg (0.66 lbs)
Attached file
2048 words x 1
Data size
Main text
256 words x 1
Data transfer method
When sending: Sends either a file as attachment or main text (select one).
When receiving: Receives a file as attachment.
Subject
US-ASCII format or ISO-2022-JP (Base64)
Attached file format
MIME format
MIME
Version 1.0
Data of attached file format
Binary/ASCII/CSV can be selected.
File name: XXXX.bin (binary), XXXX.asc (ASCII), XXXX.csv (CSV)
(CSV: Comma Separated Value)
Division of attached file
Cannot be divided (only one file can be sent/received)
* If any divided files are received, only the first file will be received and the remaining files will be
discarded.
When sending (encode)
Subject : Base64/7 bits
Main text : 7 bits
Attached file : Base64
When receiving (decode)
Subject : (Does not decode)
Main text : (Cannot be received)
Attached file : Base64/7 bits/Quoted Printable
* If e-mail is sent from the external device to the PLC side, specify the encoding method (Base64/7 bits
of the attached file.
Encryption
No
Compression No
Communication with mail server
SMTP (sending server) Port number = 25
POP3 (receiving server) Port number = 110
Transmission
specifications
Transmission
and reception
data
Operation check mailer
Microsoft
®
Corporation (Outlook Express 6.0)
1 Length between the Hub and node.