11 Buffer Memory (Parameters & Monitored Data)
11.3 Monitor Data
232
FX
3U
-20SSC-H Positioning Block User's Manual
11.3.19 Model code [BFM #30]
The model code of the 20SSC-H is stored.
11.3.20 Status information 2 [BFM #32, BFM #132]
Status of the 20SSC-H can be checked by ON/OFF statuses of each bit.
11.3.21 Current address when an interrupt occurs (INT0) [BFM #35, #34, BFM #135, #134],
Current address when an interrupt occurs (INT1) [BFM #37, #36, BFM #137, #136]
The current address when an interrupt input (INT0/INT1) occurs in target positioning operation is stored in
user units. (Ver. 1.30 or later)
Target positioning operations.
Note
The error in the calculation of user units is included in the value of the current address when an interrupt
occurs.
11.3.22 Deviation counter value [BFM #51, #50, BFM #151, #150]
The deviation counter value of the servo amplifier is stored.
BFM Number
Description
Value Format
Default
X-axis
Y-axis
BFM #30
-
The model code of the 20SSC-H is K5220.
Decimal
-
BFM Number
Bit
Number
Description
Value Format
Default
X-axis
Y-axis
BFM #32
BFM #132
b0
Positioning parameter change completion flag
(Ver. 1.20 or later)
•
Turns ON when positioning parameter change is
completed.
•
Automatically turns OFF when the positioning parameters
enable command turns OFF.
Bit
H0000
b1 to b15
Not available
BFM Number
Description
Value Format
Default
X-axis
Y-axis
BFM #35, #34
BFM
#135, #134
Current address when an interrupt input (INT0) occurs (in user units)
Decimal
-
BFM #37, #36
BFM
#137, #136
Current address when an interrupt input (INT1) occurs (in user units)
Decimal
-
Positioning operation
Current address when an interrupt occurs
(INT0)
Current address when an interrupt occurs
(INT1)
Interrupt 1-speed constant quantity feed
9
-
Interrupt 1-speed constant Quantity feed
(constant position stop mode)
9
-
Interrupt 2-speed constant quantity feed
9
9
Interrupt stop operation
9
-
Linear interpolation operation
(interrupt stop)
9
-
BFM Number
Description
Value Format
Default
X-axis
Y-axis
BFM #51,#50
BFM
#151,#150
Deviation counter value of the servo amplifier (PLS)
Decimal
-