7. Installation, transferring works, and checking

Regarding place for installation

Consult with your dealer for details on installation and transferring the installation.

 Caution:

Never install the air conditioner where there is a risk of leakage of flammable
gas.
If gas leaks and accumulates around the unit, fire can result.

Never install the air conditioner at the following place:

where there is a lot of machine oil

near the ocean and beach areas where there is salt air.

where humidity is high

where there are hot springs nearby

where there is sulphurous gas

where there is a high-frequency processing machinery (a high-frequency welder,
etc.)

where acid solution is frequently used

where special sprays are frequently used

Install the indoor unit horizontally. Otherwise, water leakage can result.

Take sufficient measures against noise when installing the air conditioners at
hospitals or communication-related businesses.

If the air conditioner is used in any of the above-mentioned environments, frequent
operational failure can be expected. It is advisable to avoid these types of installa-
tion sites.
For further details, consult with your dealer.

Regarding electrical work

 Caution:

The electrical work must be undertaken by a person who is qualified as
an electrical engineer according to the [technical standard respecting
electrical installation], [internal wiring rules], and the installation instruc-
tion manual with the absolute use of exclusive circuits. The use of other
products with the power source can result in burnt-out beakers and fuses.

Never connect the grounding wire to a gas pipe, water pipe, arrester, or
telephone grounding wire. For details, consult with your dealer.

In some types of installation sites, the installation of an earth leakage
breaker is mandatory. For details, consult with your dealer.

Regarding transfer of installation

When removing and reinstalling the air conditioner when you enlarge your
home, remodel, or move, consult with your dealer in advance to ascertain the
cost of the professional engineering work required for transferring the installa-
tion.

 Caution:

When moving or reinstalling the air conditioner, consult with your dealer.
Defective installation can result in electric shock, fire, etc.

Regarding noise

In installing work, choose a place that can fully bear the weight of the air con-
ditioner, and where noise and vibration can be reduced.

Choose a place where cool or warm air and noise from the outdoor air outlet of
the air conditioner does not inconvenience the neighbors.

If any alien object is placed near the outdoor air outlet of the air conditioner,
decreased performance and increased noise can result. Avoid placing any
obstacles adjacent to the air outlet.

If the air conditioner produces any abnormal sound, consult with your dealer.

Maintenance and inspection

If the air conditioner is used throughout several seasons, the insides can get
dirty, reducing the performance.

Depending upon the conditions of usage, foul odors can be generated and
drainage can deteriorate due to dust and dirt, etc.

PEFY-P-NMAU-E series

8. Specifications

Item

Model

Power source

Btu/h

Cooling capacity*

1

 / Heating capacity*

1

kW

Height

mm[in]

Dimension Width

mm[in]

Depth

mm[in]

Net weight

kg[lb]

Airflow rate(Low-Mid-High)

CFM

Fan

in.WG

External static pressure*

2

[Pa]

Sound level(Low-Mid-High)*

*

3

dB(A)

Filter

P12NMAU-E

12,000/13,500

3.5/4.0

265-318-371

26-29-32

208, 230V 60Hz

P06NMAU-E

6,000/6,700

1.8/2.0

212-265-300

26-28-29

P08NMAU-E

8,000/9,000

2.3/2.6

212-265-300

26-28-29

P15NMAU-E

15,000/17,000

4.4/5.0

353-424-494

26-30-33

Standard filter

250[9-13/16]

732[28-13/16]

0.14-0.20-0.28-0.40-0.60

[35/50/70/100/150]

23[51]

700[27-9/16]

26[58]

900[35-7/16]

P18NMAU-E

18,000/20,000

5.3/5.9

424-512-600

28-32-35

Item

Model

Power source

Btu/h

Cooling capacity*

1

 / Heating capacity*

1

kW

Height

mm[in]

Dimension Width

mm[in]

Depth

mm[in]

Net weight

kg[lb]

Airflow rate(Low-Mid-High)

CFM

Fan

in.WG

External static pressure*

2

[Pa]

Sound level(Low-Mid-High)*

*

3

dB(A)

Filter

208, 230V 60Hz

P24NMAU-E

24,000/27,700

7.0/7.9

477-565-671

29-33-37

P27NMAU-E

27,000/30,000

7.9/8.8

512-636-742

30-33-38

250[9-13/16]

732[28-13/16]

0.14-0.20-0.28-0.40-0.60

[35/50/70/100/150]

32[71]

P30NMAU-E

30,000/34,000

8.8/10.0

512-636-742

30-33-38

1,100[39-3/8]

Standard filter

KB79P490H02_GB_e.p65

11.5.18, 15:10

9

Summary of Contents for City Multi PEFY-P06NMAU-E

Page 1: ...MHSU E GB F MANUEL D UTILISATION Pour une utilisation correcte sans risques veuillez lire le manuel d utilisation en entier avant de vous servir du climatiseur OPERATION MANUAL For safe and correct use please read this operation manual thoroughly before operating the air conditioner unit ...

Page 2: ...F FILTER CHECK CLEAR MENU ON OFF TEST TEMP CLOCK OPERATION BACK DAY MONITOR SET 1 2 3 4 D 5 6 8 9 C 0 A B 7 Remote controller Button Touche Commande à distance GB F 1 Touche Réglage de la température 2 Touche TIMER MENU 3 Touche Mode Touche MONITOR SET Touche BACK 4 Touche TIMER ON OFF 5 Touche Louvre Touche SET DAY Touche OPERATION 6 Touche Vitesse du ventilateur 7 Touche Commande des ailettes 8 ...

Page 3: ...pièce N Réglage des ailettes O Vitesse du ventilateur P Témoin de fonctionnement Remote controller Display Affichage Commande à distance GB F A Current time Timer time B Centralized control indicator C Timer OFF indicator D Timer mode indicator E Operation mode display COOL DRY AUTO FAN HEAT F Function mode indicator G Preset temperature H Power indicator I Louver J Ventilation K Filter sign L Sen...

Page 4: ...4 4 2 In case of bottom inlet En cas d entrée sur le dessous 1 In case of rear inlet En cas d entrée arrière A Filter Filtre Air Flow Flux d air A 1 A 2 Fig A PEFY P NMAU E PEFY P NMHSU E A ...

Page 5: ...annot be held responsible for mal functions or accidents resulting from the use of the wrong type of refrigerant 1 Outdoor unit Warning The outdoor unit must be installed on a stable level surface in a place where there is no accumulation of snow leaves or rubbish Do not stand on or place any items on the unit You may fall down or the item may fall causing injury Caution The outdoor unit should be...

Page 6: ...t turn the power supply OFF during seasons of heavy use Doing so can result in failure 1 3 Disposing of the unit Warning When you need to dispose of the unit consult your dealer If pipes are re moved incorrectly refrigerant fluorocarbon gas may blow out and come into contact with your skin causing injury Releasing refrigerant into the atmosphere also damages the environment 2 Names and functions o...

Page 7: ... 1 Until reaching room temperature of your choice The compressor and indoor fan function is linked motion according to the change of the room temperature and automatically repeat ON OFF 2 When reaching room temperature of your choice Both the compressor and indoor fan stop When stop continues for 10 minutes the compressor and indoor fan are oper ated for 3 minutes to keep the humidity low For heat...

Page 8: ...ower failure The power supply is turned OFF The fuse in the power supply is gone The earth leakage breaker is gone Improper temperature adjustment The filter is filled with dust and dirt There are some obstacles at the air inlet and outlet of the indoor and outdoor units Windows and doors are open The restart preventing circuit is in operation for 3 min utes Indoor unit operation was restarted dur...

Page 9: ...of the professional engineering work required for transferring the installa tion Caution When moving or reinstalling the air conditioner consult with your dealer Defective installation can result in electric shock fire etc Regarding noise In installing work choose a place that can fully bear the weight of the air con ditioner and where noise and vibration can be reduced Choose a place where cool o...

Page 10: ...s the data that was obtained in an anechoic room PEFY P NMHSU E Series P54NMAU E 54 000 60 000 15 8 17 6 1 600 63 46 102 1 042 1 254 1 483 39 43 48 1 400 55 1 8 Item Model Power source Btu h Cooling capacity 1 Heating capacity 1 kW Height mm in Dimension Width mm in Depth mm in Net weight kg lb Airflow rate Low Mid High CFM Fan in WG External static pressure 2 Pa Sound level Low Mid High 2 3 dB A ...

Page 11: ...ute de quoi l unité ou la tuyauterie pourrait éclater ou cela pourrait provoquer une explosion ou un incendie pendant l utilisation la réparation ou la mise au rebut de l unité Cela pourrait également constituer une violation des lois applicables MITSUBISHI ELECTRIC CORPORATION ne peut être tenue responsable de tout dysfonctionnement ou accident résultant de l utilisation du mauvais type de réfrig...

Page 12: ...revendeur S il n est pas remédié à la situation des accidents risquent de se produire suite à un manque d oxygène Lorsque le climatiseur ne doit pas être utilisé pendant une certaine période Si le climatiseur ne doit pas être utilisé pendant une certaine période à cause d un changement de climat etc le faire fonctionner pendant 4 5 heures avec la soufflerie d air jusqu à ce que l intérieur soit co...

Page 13: ...ans les cas suivants L air ne souffle pas lorsque le chauffage démarre Pour éviter le souffle d air froid le ventilateur interne est progressivement allumé par étapes entre un très léger souffle un léger souffle la soufflerie programmée en fonction de l augmentation de la température de l air pro pulsé Il faut attendre un moment avant que le ventilateur ne tourne comme indiqué Le ventilateur ne to...

Page 14: ...utilisation d appareils au gaz pendant le fonctionnement du climatiseur Si vous utilisez l appareil de ventilation LOSSNAY conçu par notre société vous pouvez aérer la pièce en perdant moins d énergie Pour plus de détails sur cet appareil veuillez contac ter votre revendeur 5 Entretien de l appareil Toujours demander à la personne responsable de la maintenance d effec tuer l entretien du filtre Av...

Page 15: ... pareil est en cours de fonctionnement Le code et la mention de vérification CONTROLE clignotent sur l affichage à cristaux liquides Tous les témoins sont éteints sauf le témoin de mise sous tension Tous les témoins sont éteints sauf le témoin de mise sous tension L affichage à cristaux li quides indique que l ap pareil est en cours de fonctionnement 6 Guide de dépannage Avant de faire appel au se...

Page 16: ...e habitation veuillez prendre contact au préalable avec le revendeur pour une estimation du coût des travaux requis pour le déménage ment de l installation Précaution Lors du déménagement et de la réinstallation du climatiseur veuillez pren dre contact avec votre revendeur car une installation défectueuse peut être la cause d électrocution d incendie etc Faire également attention au bruit Lors des...

Page 17: ...13 16 0 14 0 20 0 28 0 40 0 60 35 50 70 100 150 42 93 Filtre standard P54NMAU E 54 000 60 000 15 8 17 6 1 600 63 46 102 1 042 1 254 1 483 39 43 48 1 400 55 1 8 Elément Modèle Alimentation Btu h Capacité de refroidissement 1 Capacité de chauffage 1 kW Hauteur mm in Dimensions Largeur mm in Profondeur mm in Poids net kg lb Débit d air Faible Moyenne Grande CFM Ventilateur in WG Pression statique ext...

Page 18: ......

Page 19: ......

Page 20: ... for use in the residential commercial and light industrial environment Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: