background image

8

GB

D

F

E

I

NL

P

GR

RU

TR

GB

GB

GB

GB

GB

5. Caring for the machine

Always have filter maintenance performed by a service person.
Before care-taking, turn the power supply OFF.

 Caution:

Before you start cleaning, stop operation and turn OFF the power supply.
Remember that the fan is rotating inside at high speed, posing a serious
risk of injury.

Indoor units are equipped with filters to remove the dust of sucked-in air.
Clean the filters using the methods shown in the following sketches. (The
standard filter should normally be cleaned once a week, and the long-life
filter at the beginning of each season.)

The life of the filter depends on where the unit is installed and how it is
operated.

How to clean

Clear dust away lightly or clean it up with a vacuum cleaner. In the case of
severe staining, wash the filter in lukewarm water mixed with dissolved neutral
detergent or water, and then rinse off the detergent completely. After washing,
dry it and fix it back into place.

 Caution:

Do not dry the filter by exposing it to direct sunlight or warming it using
fire, etc. Doing so can result in the deformation of the filter.

Washing it in hot water (more than 50 °C [122 °F]) can also result in defor-
mation.

 Caution:

Never pour water or flammable sprays onto the air conditioner. Cleaning using
these methods can result in the failure of the air conditioner, electric shock,
or fire.

6. Troubleshooting

Before you ask for repair service, check the following points:

State of Machine

It does not run.

Air flows out but it does
not cool enough or heat
enough.

Cool air or warm air
does not come out.

It runs briefly, but soon
stops.

The sound of the ex-
haust and rotation of
the motor can still be
heard after stop of run-
ning.
The sound of the ex-
haust and the rotation
of the motor can be
heard intermittently af-
ter stop of running.
Warm air comes out in-
termittently when the
thermostat is OFF or
during fan operation.

Troubleshooting

Press the [ON/OFF] button after power restoration.
Turn the power supply ON.
Replace fuse.
Put in the earth leakage breaker.
After checking the set temperature and inlet temperature
on the liquid crystal display, refer to [Room temperature
adjustment], and operate the adjustment button.
Clean up the filter.
(Refer to [Caring for the machine].)

Remove.

Close.
Wait for a while.
(To protect the compressor, a 3-minute restart-preventing
circuit is built into the indoor unit. Therefore, there are occa-
sions sometimes when the compressor does not start run-
ning immediately. There are cases when it does not run for
as long as 3 minutes.)
Wait for a while.
(Heating operation starts after ending defrosting operation.)

Rerun after removal

Rerun after cleaning the filter. (Refer to [Caring for the ma-
chine].)

Wait for 3 minutes.

It soon stops. (If the noise occurs more than 2-3 times in an
hour, ask for repair service.)

It soon stops. (If the room temperature rises uncomfortably
high in a small room, stop operation.)

Cause

Power failure
The power supply is turned OFF.
The fuse in the power supply is gone.
The earth leakage breaker is gone.

Improper temperature adjustment

The filter is filled with dust and dirt.

There are some obstacles at the air inlet and outlet of
the indoor and outdoor units.
Windows and doors are open.

The restart-preventing circuit is in operation for 3 min-
utes.

Indoor unit operation was restarted during the heating
and defrosting operation.
There are some obstacles at the air inlet and outlet of
the indoor and outdoor units.

The filter is filled with dust and dirt.

When other indoor units are engaged in cooling opera-
tion, the machine stops after running a drain-up mecha-
nism for 3 minutes when air-cooling operation is
stopped.

When other indoor units are engaged in cooling opera-
tion, drained water is brought in. If the drain water is
collected, the drain-up mechanism initiates a draining
operation.

When other indoor units are engaged in heating op-
eration, the control valves are opened and closed from
time to time to maintain the stability of the system.

Remote Controller

'

” display is not lit up.

No display appears even
when the [ON/OFF] but-
ton is pressed.

The liquid crystal display
shows that it is in the
state of operation.

The liquid crystal display
shows that it is in opera-
tion.

The “CHECK” and check
code flashes on the liquid
crystal display.

All lights are out except
the powered display of

'

”.

All lights are out except
the powered display of

'

”.

The liquid crystal display
shows that it is in the
state of operation.

If operation stops due to a power failure, the [restart-preventing circuit at power failure] operates and disables unit operation even after power restoration. In this case,
press the [ON/OFF] button again and start operation.

If malfunctions persist after you have checked the above, turn the power supply OFF and contact your dealer with information about the product name, the nature of the
malfunction, etc. If the display of “[CHECK]” and (4 digit) check code flashes, tell the dealer contents of the display (check code). Never attempt to repair by yourself.

The following symptoms are not air conditioner failures:

The air blown out from the air conditioner can sometimes give off odors. This is due to cigarette smoke contained in the air of the room, the smell of cosmetics, the walls,
furniture, etc., absorbed in the air conditioner.

A hissing noise can be heard immediately after the air conditioner is started or stopped. This is the sound of the refrigeration flowing inside the air conditioner. This is
normal.

The air conditioner sometimes snaps or clicks at the beginning or end of cooling/heating operation. This is the sound of friction on the front panel and other sections due
to expansion and contraction caused by temperature change. This is normal.

The fan speed changes in spite of not changing the setting. Not to blow out cold air at the beginning of heating operation, the air conditioner automatically adjusts the fan
speed gradually from lower to the set speed. It also adjust its fan speed to protect the fan motor when return air temperature or fan speed excessively rises.

KB79P490H02_GB_e.p65

11.5.18, 15:10

8

Summary of Contents for City Multi PEFY-P06NMAU-E

Page 1: ...MHSU E GB F MANUEL D UTILISATION Pour une utilisation correcte sans risques veuillez lire le manuel d utilisation en entier avant de vous servir du climatiseur OPERATION MANUAL For safe and correct use please read this operation manual thoroughly before operating the air conditioner unit ...

Page 2: ...F FILTER CHECK CLEAR MENU ON OFF TEST TEMP CLOCK OPERATION BACK DAY MONITOR SET 1 2 3 4 D 5 6 8 9 C 0 A B 7 Remote controller Button Touche Commande à distance GB F 1 Touche Réglage de la température 2 Touche TIMER MENU 3 Touche Mode Touche MONITOR SET Touche BACK 4 Touche TIMER ON OFF 5 Touche Louvre Touche SET DAY Touche OPERATION 6 Touche Vitesse du ventilateur 7 Touche Commande des ailettes 8 ...

Page 3: ...pièce N Réglage des ailettes O Vitesse du ventilateur P Témoin de fonctionnement Remote controller Display Affichage Commande à distance GB F A Current time Timer time B Centralized control indicator C Timer OFF indicator D Timer mode indicator E Operation mode display COOL DRY AUTO FAN HEAT F Function mode indicator G Preset temperature H Power indicator I Louver J Ventilation K Filter sign L Sen...

Page 4: ...4 4 2 In case of bottom inlet En cas d entrée sur le dessous 1 In case of rear inlet En cas d entrée arrière A Filter Filtre Air Flow Flux d air A 1 A 2 Fig A PEFY P NMAU E PEFY P NMHSU E A ...

Page 5: ...annot be held responsible for mal functions or accidents resulting from the use of the wrong type of refrigerant 1 Outdoor unit Warning The outdoor unit must be installed on a stable level surface in a place where there is no accumulation of snow leaves or rubbish Do not stand on or place any items on the unit You may fall down or the item may fall causing injury Caution The outdoor unit should be...

Page 6: ...t turn the power supply OFF during seasons of heavy use Doing so can result in failure 1 3 Disposing of the unit Warning When you need to dispose of the unit consult your dealer If pipes are re moved incorrectly refrigerant fluorocarbon gas may blow out and come into contact with your skin causing injury Releasing refrigerant into the atmosphere also damages the environment 2 Names and functions o...

Page 7: ... 1 Until reaching room temperature of your choice The compressor and indoor fan function is linked motion according to the change of the room temperature and automatically repeat ON OFF 2 When reaching room temperature of your choice Both the compressor and indoor fan stop When stop continues for 10 minutes the compressor and indoor fan are oper ated for 3 minutes to keep the humidity low For heat...

Page 8: ...ower failure The power supply is turned OFF The fuse in the power supply is gone The earth leakage breaker is gone Improper temperature adjustment The filter is filled with dust and dirt There are some obstacles at the air inlet and outlet of the indoor and outdoor units Windows and doors are open The restart preventing circuit is in operation for 3 min utes Indoor unit operation was restarted dur...

Page 9: ...of the professional engineering work required for transferring the installa tion Caution When moving or reinstalling the air conditioner consult with your dealer Defective installation can result in electric shock fire etc Regarding noise In installing work choose a place that can fully bear the weight of the air con ditioner and where noise and vibration can be reduced Choose a place where cool o...

Page 10: ...s the data that was obtained in an anechoic room PEFY P NMHSU E Series P54NMAU E 54 000 60 000 15 8 17 6 1 600 63 46 102 1 042 1 254 1 483 39 43 48 1 400 55 1 8 Item Model Power source Btu h Cooling capacity 1 Heating capacity 1 kW Height mm in Dimension Width mm in Depth mm in Net weight kg lb Airflow rate Low Mid High CFM Fan in WG External static pressure 2 Pa Sound level Low Mid High 2 3 dB A ...

Page 11: ...ute de quoi l unité ou la tuyauterie pourrait éclater ou cela pourrait provoquer une explosion ou un incendie pendant l utilisation la réparation ou la mise au rebut de l unité Cela pourrait également constituer une violation des lois applicables MITSUBISHI ELECTRIC CORPORATION ne peut être tenue responsable de tout dysfonctionnement ou accident résultant de l utilisation du mauvais type de réfrig...

Page 12: ...revendeur S il n est pas remédié à la situation des accidents risquent de se produire suite à un manque d oxygène Lorsque le climatiseur ne doit pas être utilisé pendant une certaine période Si le climatiseur ne doit pas être utilisé pendant une certaine période à cause d un changement de climat etc le faire fonctionner pendant 4 5 heures avec la soufflerie d air jusqu à ce que l intérieur soit co...

Page 13: ...ans les cas suivants L air ne souffle pas lorsque le chauffage démarre Pour éviter le souffle d air froid le ventilateur interne est progressivement allumé par étapes entre un très léger souffle un léger souffle la soufflerie programmée en fonction de l augmentation de la température de l air pro pulsé Il faut attendre un moment avant que le ventilateur ne tourne comme indiqué Le ventilateur ne to...

Page 14: ...utilisation d appareils au gaz pendant le fonctionnement du climatiseur Si vous utilisez l appareil de ventilation LOSSNAY conçu par notre société vous pouvez aérer la pièce en perdant moins d énergie Pour plus de détails sur cet appareil veuillez contac ter votre revendeur 5 Entretien de l appareil Toujours demander à la personne responsable de la maintenance d effec tuer l entretien du filtre Av...

Page 15: ... pareil est en cours de fonctionnement Le code et la mention de vérification CONTROLE clignotent sur l affichage à cristaux liquides Tous les témoins sont éteints sauf le témoin de mise sous tension Tous les témoins sont éteints sauf le témoin de mise sous tension L affichage à cristaux li quides indique que l ap pareil est en cours de fonctionnement 6 Guide de dépannage Avant de faire appel au se...

Page 16: ...e habitation veuillez prendre contact au préalable avec le revendeur pour une estimation du coût des travaux requis pour le déménage ment de l installation Précaution Lors du déménagement et de la réinstallation du climatiseur veuillez pren dre contact avec votre revendeur car une installation défectueuse peut être la cause d électrocution d incendie etc Faire également attention au bruit Lors des...

Page 17: ...13 16 0 14 0 20 0 28 0 40 0 60 35 50 70 100 150 42 93 Filtre standard P54NMAU E 54 000 60 000 15 8 17 6 1 600 63 46 102 1 042 1 254 1 483 39 43 48 1 400 55 1 8 Elément Modèle Alimentation Btu h Capacité de refroidissement 1 Capacité de chauffage 1 kW Hauteur mm in Dimensions Largeur mm in Profondeur mm in Poids net kg lb Débit d air Faible Moyenne Grande CFM Ventilateur in WG Pression statique ext...

Page 18: ......

Page 19: ......

Page 20: ... for use in the residential commercial and light industrial environment Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: