9 -
7
EMC AND LOW VOLTAGE DIRECTIVES
9.
(b) When wiring with cable that exceeds 2m (6.56ft.), but is 10m (32.81ft.) or less
• Ground the shield section of the external wiring cable with the cable clamp.
(Ground the shield at the closest location to the A1SD75 external wiring
connector.)
• Install a ferrite core.
• Wire the external wiring cable to the drive unit and external device with the
minimum distance of cable.
(c) Ferrite core and cable clamp types and required quantities
• Cable clamp
• Ferrite core
• Required quantity
(d) Cable clamp mounting position
Type :
AD75CK (Manufactured by Mitsubishi Electric)
Type :
ZCAT3035-1330 (TDK ferrite core)
Contact: TDK Corporation
Cable length
Prepared part
Required Qty
1 axis
2 axes
3 axes
Within 2m (6.56ft.)
AD75CK
1
1
1
2m (6.56ft.) to 10m (32.81ft.)
AD75CK
1
1
1
ZCAT3035-1330
1
2
3
Inside control panel
A1SD75
AD75CK
20 to 30cm
(7.87 to 11.81inch)