4
-
Item
Models
STM25ZF-S
STM35ZF-S
STM50ZF-S
STM60ZF-S
Cooling capacity
W
2500
3500
5000
6000
Heating capacity
W
3400
4500
5800
6800
Noise level
Cooling
35
38
40
47
dB
51
54
56
63
Heating
35
38
40
47
51
54
56
63
Exterior dimensions
Main unit
248
×
570
×
570
Height
×
Width
×
Depth
Panel
mm
35
×
700
×
700
Color
–
Net weight
Main unit
kg
14
14.5
Panel
3.5
Air handling equipment
Fan type & Q’ty
Turbo fan
×
1
Motor
W
40
Cooling
8.0
9.0
10.0
13.0
Air flow (at high)
Heating
CMM
9.0
10.0
11.0
14.0
Air filter, Q’ty
Long life filter
×
1 (Washable)
Operation switch
Wireless-Remote control
Room temperature control
Microcomputer thermostat
Pilot lamp
RUN (Green), TIMER (Yellow), HI POWER (Green), ECONO (Orange)
Safety equipment
O.D
mm (in)
φ
6.35 (1/4
″
)
φ
9.52 (3/8
″
)
φ
12.7 (1/2
″
)
Connecting method
Flare connecting
Attached length of piping
—
Insulation
Necessary (Both Liquid & Gas lines)
Drain hose
Connectable
Accessories (including)
Mounting kit
Optional parts
Wired remote control
Outdoor unit to be combined
SCM40, 45, 48, 60, 80ZF-S SCM45, 48, 60, 80ZF-S
SCM60, 80ZF-S
Models
STM25ZF-S, 35ZF-S, 50ZF-S, 60ZF-S
(2) Capacity indicated is the rated capacity with one unit operating under ISO-T1 standards conditions.
Refrigerant
piping
Liquid line
Gas line
Frost protection, Serial error protection
Fan motor error protection, Drain error protection
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27
°
C
19
°
C
35
°
C
24
°
C
ISO-T1, JIS C9612
Heating
20
°
C
–
7
°
C
6
°
C
ISO-T1, JIS C9612