54
-
F1
F1
R2rps
Decision rps
300 pulse
EEV control
Opening in relation to conditions
R1rps
Decision rps
0rps
Outdoor unit speed
After compressor software
has started
According to rps
Outdoor unit fan
OFF
ON
4-way valve
OFF
470 pulse
fully opened
250 pulse
Electronic expansion
valve EEV
(Operating unit)
EEV control
50 sec.
Opening in
relation to
conditions
Electronic expansion
valve EEV
(Stopped unit)
0 pulse
X1 pulse
X2 pulse
Start of defrost operation
Defrost end operation
Defrost operation
Defrost end condition
100 sec.
120 sec.
Indoor unit fan is
in response to Hot
Keep.
Notes (1)
3) Operation of function component in defrosting
◆
SCM40ZF-S
Outdoor unit speed
Outdoor unit fan
R1 (rps)
R2 (rps)
F1
1-room
2-room
1-room
2-room
6th speed
70
70
50
50
X1 pluse
X2 pluse
1-room
2-room
1-room
2-room
Operating unit
180
135
140
105
◆
SCM45ZF-S
Outdoor unit speed
Outdoor unit fan
R1 (rps)
R2 (rps)
F1
1-room
2-room
1-room
2-room
6th speed
70
70
50
50
X1 pluse
X2 pluse
1-room
2-room
1-room
2-room
Operating unit
135
180
105
140
◆
SCM48ZF-S
Outdoor unit speed
Outdoor unit fan
R1 (rps)
R2 (rps)
F1
1-room
2-room
3-room
1-room
2-room
3-room
6th speed
45
75
110
35
55
75
X1 pluse
X2 pluse
1-room
2-room
3-room
1-room
2-room
3-room
Operating unit
180
160
150
140
115
110