3
-
Example1
Example2
Example3
Minimum
a(Height)(mm)
900
180
0
100
0
600 or larger
b(Width)(mm)
800
400
400
400 or larger
c(Depth)(mm)
110
110
200
110 or larger
0.08
0.08
0.08
Beam of
building
Inner wall
SLA3R-BX
more than
105mm
<No partition>
a
b
c
Inner wall
Partition
Center
console
<With partition>
䢇
SLA3R-BX (Sold separately)
4-ø6
2- ø35
15
20
113
132
30
153
113
20
20
60
20
50
15
80
(Knock out)
Incorrect
Incorrect
Correct
1
Caution
1
2
3
1
Caution
2
Caution
(e) In case of installing on the control board
(f) In case of embedding in a wall
Please be sure to use the special box, SLA3R-BX (sold separately).
25
15
48 17
228
17
48 15
220
70
155
170
198
54
120
54
178
25
Space(m
3
)
(3) Installation method
(a) Embed signal wire and power supply wire in a wall beforehand.
(b) Connect wires to the terminal block.
(c) Confirm power supply voltage and connect correctly.
(d) Remove the upper case
1) Take out two screws using a cross slot screwdriver. (Don't lose the screws)
2) Pull the upper case a little forward and push above. Then, upper case can be removed.
M4 screws, 4 pieces
(accessory of the unit)
Fix the unit to the SLA3R-BX with the M4 screws. (4 places)
Wire separately the power supply wire and the signal wire for
preventing malfunctions.
Please do not install other units on the same
control board that will cause temperature rise.
Please do not
install facing
upward or in
slanted position.
Please do not install multiple controllers on the
same control board. They can cause the temperature
rise of the control board interior and the center
consoles will not work properly.
When there is no choice but to install the multiple
controllers,please adjust the tempereture inside the
control board 40 degrees or less. (for example
cooling fan installation)