 6 

-

Bottom of the unit

Indoor unit A

Indoor unit B

Indoor unit C

25Hz

40Hz

60Hz

(5)  Energy consumption calculation  data (SLB-3-ER)

SLB-3-ER outputs energy consumption calculation  data using USB memory. These data can be edited using commercial 
spreadsheet software. 
Energy consumption calculation data are created for each individual month.

<Calculation procedure>

1

 The cumulative operating time is calculated for each air conditioner. (in minutes)

2

 The total operating time (Ki) for each air conditioner, and the operating time in each time band (regular hours, irregular 

hours) are calculated (in minutes).
Ki = Ki + K

M

K

M

 = Amount of air conditioner operation in 1 minute.

The amount of operation is calculated by the following 3 methods.
The amount of operation in the case calculated for the rated opening area value for that air conditioner, E.
• MULTI 1: The conversion value considering the amount of refrigerant flowing in the indoor unit is calculated 

(

 

Ej).

(Ej: Conversion value for the opening area of the indoor unit's expansion valve.)

• MULTI 2: The time that refrigerant flows through the indoor unit is additionally calculated. (Thermostat ON time

E)

• RUN/STOP: A conversion value for the time when the remote controller is ON is added. (Operating time

E)

(E: Conversion value for the capacity of the indoor unit.)
• Use the same kind of flow volume for the same type of dynamic flow meters (gas meters).
• If MULTI-1 and MULTI-2 are set, indoor units in the blower mode cease to be objects of proportional division. 

Set indoor units in the blower mode to ON or OFF if you 
want to make them objects of proportional division.

• As for the standby power in the case that the air conditioner is 

not used at night, etc. proportional division cannot be applied 
if there are no indoor units running, so the standby power 
readings will not match. Recalculate using spreadsheet 
software.

• Simple software is included for editing the energy consumption calculation 

data.See the included software concerning the operation method.

• Energy consumption calculation data are obtained from this unit using the USB memory.

(SLB-3-ER does not recognize commercial USB memory.)

(Example)  Method of proportional distribution in case of indoor units A, B, C operating as follows (the shaded part indicates the 

accumulated operating volume).

1

 In case of MULTI 1 setting: Conduct proportional distribution according to the results of accumulated answer Hz. 

Accumulation is not performed when the thermo is OFF or during the Fan mode operation.

Total value of operating volume
(Total value of answer Hz)

Operating volume of indoor unit A = accumulated pulse counts

power consumption per pulse

25 / 125 

(25 + 40 + 60)

Operating volume of indoor unit B = accumulated pulse counts

power consumption per pulse

40 / 125

Operating volume of indoor unit C = accumulated pulse counts

power consumption per pulse

60 / 125

2

 In case MULTI 2 setting: Conduct proportional distribution according to the Hz corresponding to the air conditioner capacity 

(capacity equivalent Hz: fixed value) and thermo ON operating time.
Capacity equivalent Hz: equivalent value of answer Hz when exerting the indicated capacity of indoor unit (fixed value 
determined according to capacity).

USB

Summary of Contents for SC-SLA3-ER

Page 1: ... 3 AIR CONDITIONING CONTROL SYSTEM TECHNICAL MANUAL Collection data Manual No 06 SC T 111 CENTER CONSOLE SLA 3 ER SC SLA3 ER SLB 3 ER SC SLB3 ER ...

Page 2: ...ERNAL VIEW 2 5 INSTALLATION 2 6 FUNCTIONS 4 7 ELECTRIC WIRING 9 8 SELECTING A NEW PULSE UNIT 10 These technical manual cover Center Consoles SLA 3 ER and SLB 3 ER Concerning other air conditioning control systems see page 675 in Part 5 Air Conditioning Control System of the 06 TECHNICAL MANUAL KX 4 ...

Page 3: ...umption calculation function is necessary use the SLB 3 ER 4 The lifetime of the keying of touch panel is one million times The lifetime of LCD is about 20 000 hours depending also upon the backlight OFF time setting The brightness will become half of the starting value 5 The touch panel has an endurance of approximately 1 million times 6 In the environment setting screen it is also possible to ch...

Page 4: ...cient air circulation space If the box is unused the center console will not work properly because of heat buildup inside the box Please be sure to use for protecting persons from the electric shock Please check that the sufficient space is available in the wall When the inside of the wall is divided and have a cavity please create space more than 0 08m3 Refer to the next page If there is no parti...

Page 5: ...ires to the terminal block c Confirm power supply voltage and connect correctly d Remove the upper case 1 Take out two screws using a cross slot screwdriver Don t lose the screws 2 Pull the upper case a little forward and push above Then upper case can be removed M4 screws 4 pieces accessory of the unit Fix the unit to the SLA3R BX with the M4 screws 4 places Wire separately the power supply wire ...

Page 6: ...tions enables or disables mode setting and enables or disables temperature setting Sets Hi Me or Lo fan speed Sets auto swing ON or OFF and sets positions 1 4 Resets turns off the filter sign Operating state Mode Set temperature Room temperature Operation enabled Fan speeds Air direction Filter sign Maintenance Inspections 1 2 or backup Breakdown Monitors the operating and stopped state of the air...

Page 7: ...tc Annual Anno Domini Month Day Hour 24 hr system Minute Displays the error occurrence and recovery history for up to 300 occasions in air conditioner units Calculates the cumulative operating hours for each air conditioner dividing them between regular hours or irregular hours and saves them Starts the fan or Prohibits operation for air conditioners which have previously been set by external dema...

Page 8: ...Set indoor units in the blower mode to ON or OFF if you want to make them objects of proportional division As for the standby power in the case that the air conditioner is not used at night etc proportional division cannot be applied if there are no indoor units running so the standby power readings will not match Recalculate using spreadsheet software Simple software is included for editing the e...

Page 9: ...hen the thermo is OFF and during the air supply operation Indoor unit A Indoor unit B Indoor unit C 30Hz 50Hz 70Hz Indoor unit A Indoor unit B Indoor unit C 40Hz 60Hz 70Hz Different from 1 the fixed value is accumulated irrespective of the answer Hz Accumulation is not performed when the thermo is OFF and during the Fan mode operation User login For owners the fee apportionment for multi machine a...

Page 10: ...d the overtime in the SL 1 SL 3 system b 2 Daily cumulative pulses from meters 1 8 for each period PC input 1 Pulse meter electricity or gas group definition 2 Pulse constant definition kWh pulse m3 pulse 3 Setting of the calculation period the end of the month the 20th of the month or etc 4 Group definition for each tenant 5 Setting of energy charge the unit price and the basic charge of electric...

Page 11: ...e round crimping terminal with the insulation sleeve for wiring to the unit Perform ground wiring Please do not connect the ground wire to the gas pipe the water pipe the lightning rod and the telephone ground wire Please do not turn on the power supply hand switch until all work finishes Please turn on the power supply two minutes or more after turning on the power supply of the indoor unit and t...

Page 12: ... should be 1000 m or less per line Recommended signal wire list 1 5 9 11 13 15 17 19 21 23 25 39 27 29 31 33 35 37 Power input from gas meter or wattmeter 8 points in case of SLB 3 ER COM PI1 COM PI2 COM PI3 COM PI4 COM PI5 COM PI6 COM PI7 COM PI8 3 7 b The lower tier of terminal block No 1 2 3 4 Name Symbol Vinyl cabtire roung cord Vinyl cabtire round cable Control vinyl insulated vinyl sheathed ...

Page 13: ...er pulses ask an electric meter manufacturer for details 4 Inspection while electricity consumption is at 120kWh When pulse input is highest Use 0 1kWh P then 1200P h 20P min exactly 1 minute 20 pulse 300pulses or fewer 10 minutes 200 pulses OK Use 1kWh P then 120P h 2P min exactly 1 minute 2 pulses 10 minutes 20 pulses OK Use 10kWh P then 12P h 0 2P min so 1 minute no pulses 10 minutes 2 pulses O...

Page 14: ...lse h If you use 15m3 h 30 pulse h If you use 30m3 h 60 pulse h If you use 50m3 h 100 pulse h If you use 90m3 h 180 pulse h If you use 120m3 h 240 pulse h d Largest electric pulse input value Gas amount pulse unit 0 01kWh P 4 320kWh B 180kWh h 0 1kWh P 43 200kWh B 1 800kWh h 1kWh P 432 000kWh B 18 000kWh h 10kWh P 4320 000kWh B 180 000kWh h Note 1 Electricity meter pulse unit please select 10kWh P...

Page 15: ... 2 No 042 2A R Air Conditioning Refrigeration Systems Headquarters 16 5 2 chome Kounan Minato ku Tokyo 108 8215 Japan Fax 03 6716 5926 ...

Reviews: