7
-
Total value of operating volume
(capacity equivalent Hz
⳯
remote controller ON time)
Operating volume of indoor unit A = accumulated pulse counts
⳯
power consumption per pulse
⳯
40 / 160
(40 + 50 + 70)
Operating volume of indoor unit B = accumulated pulse counts
⳯
power consumption per pulse
⳯
50 / 160
Operating volume of indoor unit C = accumulated pulse counts
⳯
power consumption per pulse
⳯
70 / 160
Total value of operating volume
(capacity equivalent Hz
⳯
thermo ON time)
Operating volume of indoor unit A = accumulated pulse counts
⳯
power consumption per pulse
⳯
30 /150
(30 + 50 + 70)
Operating volume of indoor unit B = accumulated pulse counts
⳯
power consumption per pulse
⳯
50 / 150
Operating volume of indoor unit C = accumulated pulse counts
⳯
power consumption per pulse
⳯
70 / 150
3
In case of RUN/STOP setting: Conduct proportional distribution according to the Hz corresponding to the air conditioner
capacity (capacity equivalent Hz: fixed value) and remote controller ON time.
Same as
2
, the capacity equivalent Hz (fixed value) is accumulated according to the remote controller ON time only.
Accumulation is also performed when the thermo is OFF and during the air supply operation.
Indoor unit A
Indoor unit B
Indoor unit C
30Hz
50Hz
70Hz
Indoor unit A
Indoor unit B
Indoor unit C
40Hz
60Hz
70Hz
Different from
1
, the fixed value is accumulated irrespective of the answer Hz. Accumulation is not performed when the
thermo is OFF and during the Fan mode operation.
User login
For owners the fee apportionment for multi machine air conditioners is more complicated and harder to explain to
customers. In many cases it's best to use simple explanations.
In addition, consumption for multi machines are calculated based on volume, making it easy for excessive cooling
and differences in building load to lead to discrepancies in electricity consumption.
These different values are hard to explain. Therefore, it is easier to explain how many horsepower were used for
how long.
At this point, recommend [RUN/STOP] registration.
Both multi machines and single machines use [RUN/STOP] registration.
Recommend that separate electricity meters be installed for single machine and multi machine systems.
Display every unit of electricity (kW) on the electricity consumption board. For example, register P280H as 28.0.
Current operational value = electricity volume
⳯
time of operation, calculated according to the electricity volume ratio.
夝