−77−
■
A list of error code (Continue)
Remote
controller
Error code
LED on heat source unit
7-segment
display
Contents of inspection
Green
Red
E61
Keep fl ashing
1-time fl ash
E61-1
Communication error between master unit and slave unit 1
2-time fl ash
E61-2
Communication error between master unit and slave unit 2
3-time fl ash
E61-3
Communication error between master unit and slave unit 3
E63
Keep fl ashing
1-time fl ash
E63
Emergency stop , AF anomaly (set at adding active fi lter)
E64
Keep fl ashing
1-time fl ash
E64
Water pump anomaly (no operation)
Water pump anomaly (excessive operation)
E89
Keep fl ashing
1-time fl ash
E89
Communication error between control PCB and CPU
No hot water comes out (1)
Keeps fl ashing
Stays off
Normally
See troubleshooting
No hot water comes out (2)
Keeps fl ashing
Stays off
Normally
See troubleshooting
No hot water comes out (3)
Keeps fl ashing
Stays off
Normally
See troubleshooting
Anomalous sound
and vibration (1)
Keeps fl ashing
Stays off
Normally
See troubleshooting
Anomalous sound
and vibration (2)
Keeps fl ashing
Stays off
Normally
See troubleshooting
7-segment display
RC display
Items
Remarks
No.
No.
Compressor operation hours
oPE-1
M1
When the cumulative operation hours of compressor has elapsed 5,000hr
since the last maintenance, and it is between 4,900hr and 5,100hr.
Synchronizing with the timing of alarming by
the simple remote monitoring equipment
oPE-2
M2
When the cumulative operation hours of compressor
has elapsed 10,000hr since the last maintenance.
oPE-3
M3
When the cumulative operation hours of compressor
has elapsed 30,000hr since the last maintenance.
Water pump operation hours
oPE-11
M11
When the cumulative operation hours of water pump has elapsed 5,000hr
since the last maintenance, and it is between 4,900hr and 5,100hr.
Synchronizing with the timing of alarming by
the simple remote monitoring equipment
oPE-12
M12
When the cumulative operation hours of water pump
has elapsed 10,000hr since the last maintenance.
oPE-13
M13
When the cumulative operation hours of water pump
has elapsed 20,000hr since the last maintenance.
Setting error
oPE-20
M20
Setting error for type of cylinder
Check setting of SW3-3 is OFF for unvented cylinder
oPE-21
M21
Setting error of heat pump unit model
Kept SW4-1, -2, -3, -4 “OFF” (Factory default)
oPE-22
M22
Setting error of master/slave units
Check setting of SW4-7 and -8
Error information
oPE-30
M30
Detection of AF error
But E63 is not displayed
oPE-32
M32
Detection of drying up water
It is always displayed at test run
oPE-33
M33
Detection of disconnection of cylinder water temp sensor
oPE-34
M34
Detection of suspension of water supply
oPE-35
M35
Detection of water pump error
oPE-40
M40
An error has occurred to either unit at master
and slave operation.
Normal units are in automatic backup
operation.
Please service the unit which an error has
occurred according to error code.
· Message of [disconnection of cylinder
temperature sensor]
Hot water temperature sensor on
the cylinder (Tht-1 to Tht-9) may be
disconnected.
· Check the connection and the
characteristics of all hot water temperature
sensors on the cylinder and if there is a
problem, connect it securely or replace it.
· If no problem on sensors, replace control
PCB.
■
Maintenance code
Maintenance code is the signal for prompt service and maintenance, not to show anomaly.