2. Installation and Wiring
2.8 Connection of stand-alone option units
2.8.2
Connection of the DC reactor
• When using the DC reactor, connect it to terminals P/+ and P1.
In this case, the jumper connected across terminals P/+ and P1 must be removed. Otherwise, the reactor will not be
effective.
• Select a DC reactor according to the applied motor capacity. (Refer to
NOTE
• The wiring distance must be within 5 m.
• As a reference, the cable gauge for the connection must be equal to or larger than that of the power cables (R/L1, S/L2, T/L3)
and the earthing (grounding) cable. (Refer to
.)
P1
DC reactor
Remove
the jumper
P/+