44
2. Installation and Wiring
2.6 Control circuit
Ethernet model
• Recommended cable gauge: 0.3 to 0.75 mm
2
Wiring method
Power supply connection
Use crimp terminals and stripped wire for the control circuit wiring. For single wire, the stripped wire can be used without crimp
terminal.
Connect the end of wires (crimp terminal or stranded wire) to the terminal block.
1.
Strip the signal wires as shown below. If too much of the wire is stripped, a short circuit may occur with neighboring
wires. If not enough of the wire is stripped, wires may become loose and fall out.
Twist the stripped end of wires to prevent them from fraying. Do not solder it.
2.
Crimp the terminals on the wire.
Insert wires to the crimp terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the crimp terminals after crimping. Do not use the crimp terminals of which the crimping is
inappropriate, or the face is damaged.
Crimp terminals commercially available (as of December 2019)
S1 S2 PC D10 DI1 SD
10
2
5
4
SO SOC
A
B
C
Cable sheath stripping length
Crumpled tip
Wires are not inserted
into the sleeve
Unstranded
wires
Damaged
Wire
Wire
Sleeve
Sleeve
0 to 0.5mm
0 to 0.5mm