Basic Operations - Operation screen (GROUP screen)
Basic Operations - Operation screen (GROUP screen)
Hold function setting
HOLD-ON
HOLD-OFF
Touch
5
to enable/disable the Hold function.
* When the Hold function is enabled, the current operation status is retained until the Hold function is
disabled.
* The timer execution is prohibited when this function is enabled and the icon is displayed.
* The operations that have been scheduled from the other system controllers or remote controllers will also
be disabled.
* If the Hold setting is set to ON from the GROUP screen or with the HOLD button next to the touch panel
and the “Hold type” is set to “Forced”, the Hold setting can be cancelled only from this unit. If the “Hold
type” is set to “Normal”, the Hold setting can be cancelled from this unit, other system controllers, or
remote controllers.
* When remote controllers, system controllers, or units that do not support the Hold function are connected,
only the scheduled operations for this unit will be disabled.
* Refer to the Installation Manual for how to change the “Hold type”.
Interlocked ventilation units (LOSSNAY)/Fan speed/Air direction/
Louver settings
for Air conditioning unit groups only
Touch
4
to show the Interlocked ventilation
units (LOSSNAY)/Fan speed/Air direction/
Louver settings screen.
4
A
C
B
D
A
: Interlocked ventilation units (LOSSNAY)
Stop
Low
High
* When interlocked ventilation units are not connected,
A
does not appear.
B
: Fan speed (settable only while the unit is in operation)
Quiet
Low
Medium
High
Auto
*
B
does not appear when the model does not have this function.
* Available fan speed varies depending on the model.
C
: Air direction (settable only while the unit is in operation)
Setting 1
Setting 2
Setting 3
Setting 4
Setting 5
Swing
Auto
*
C
does not appear when the model does not have this function.
* Available air direction varies depending on the model.
D
: Louver (settable only while the unit is in operation)
ON
OFF
*
D
does not appear when the model does not have this function.
After setting
A
through
D
, touch the
[OK]