64
4 PROCEDURES PRIOR TO OPERATION
4.2 SD Memory Card
Operations for replacing new SD memory card
When replacing the new SD memory card, always stop file access following the procedure below.
*1 Can be omitted if auto logging function is set on a newly inserted SD memory card.
*2
Page 65 File access stop processing method
*3
*4
*5 When inserting the SD memory card on which the auto logging function has been set, the logging starts as the card is inserted.
*6 Update the settings in "Module diagnostics" of the configuration tool. (
MELSEC iQ-R High Speed Data Logger Module User's
Manual(Application))
• Not following the procedure shown above may cause a loss of logging data during processing, corruption of
data, or occurrence of a file system error on the SD memory card while accessing.
• If an error occurs on the SD memory card, refer to the following manual.
(
MELSEC iQ-R High Speed Data Logger Module User's Manual(Application))
• High speed data logger module settings are saved on the SD memory card. Therefore, the IP address of the
high speed data logger module returns to the initial status (192.168.3.3) when turning the power OFF to ON
or resetting the CPU module without a SD memory card inserted in the module or without the settings
written to the SD memory card.
As necessary, read the current settings before removing the SD memory card and after replacing the card,
promptly write those settings to the new card.
NO
YES
YES
NO
YES
*5
NO
Start
Is the power ON?
Turn the programmable controller power ON.
Start the Configuration Tool
and read the settings.
*1
Perform file access stop processing
to disable reading/writing to the SD Memory card.
*2
Eject the SD Memory card.
*3
Insert a new SD memory card.
*4
Is the CARD RDY LED ON?
Check if the SD memory card is correctly inserted
into the high speed data logger module.
Is the auto logging function
set on the inserted
SD Memory card?
Write the settings, and update the settings.
*6
Finish
Summary of Contents for RD81DL96
Page 2: ......
Page 80: ...78 7 INSTALLATION AND UNINSTALLATION 7 2 Uninstallation Procedure MEMO ...
Page 115: ...8 OPERATION EXAMPLE 8 3 Creating Reports from Continuously Logged Data 113 8 MEMO ...
Page 117: ...APPX Appendix 1 External Dimensions 115 A MEMO ...
Page 119: ...I 117 MEMO ...