background image

2

1.2. Before installation (relocation)

 Caution:

• Be extremely careful when transporting the units. Two or more persons are

needed to handle the unit, as it weighs 20 kg, 44 Ibs or more. Do not grasp
the packaging bands. Wear protective gloves to remove the unit from the
packaging and to move it, as you can injure your hands on the fins or other
parts.

• Be sure to safely dispose of the packaging materials. Packaging materials, such

as nails and other metal or wooden parts may cause stabs or other injuries.

 Warning:

• The unit must not be installed by the user. Ask a dealer or an authorized

technician to install the unit. If the unit is installed incorrectly, water leakage,
electric shock, or fire may result.

• For installation work, follow the instructions in the Installation Manual and use

tools and pipe components specifically made for use with R410A refrigerant.
The R410A refrigerant in the HFC system is pressurized 1.6 times the pressure
of usual refrigerants. If pipe components not designed for R410A refrigerant
are used and the unit is not installed correctly, the pipes may burst and cause
damage or injuries. In addition, water leakage, electric shock, or fire may result.

• The unit must be installed according to the instructions in order to minimize

the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.

• The unit must be securely installed on a structure that can sustain its weight.

If the unit is mounted on an unstable structure, it may fall down and cause
damage or injuries.

• If the air conditioner is installed in a small room, measures must be taken to

prevent the refrigerant concentration in the room from exceeding the safety
limit in the event of refrigerant leakage. Consult a dealer regarding the appro-
priate measures to prevent the allowable concentration from being exceeded.
Should the refrigerant leak and cause the concentration limit to be exceeded,
hazards due to lack of oxygen in the room may result.

• Ventilate the room if refrigerant leaks during operation. If refrigerant comes

into contact with a flame, poisonous gases will be released.

• All electric work must be performed by a qualified technician according to

local regulations and the instructions given in this manual. The units must be
powered by dedicated power lines and the correct voltage and circuit break-
ers must be used. Power lines with insufficient capacity or incorrect electri-
cal work may result in electric shock or fire.

• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,

to connect the refrigerant pipes. If the pipes are not connected correctly, the
unit will not be properly grounded and electric shock may result.

• Use only specified cables for wiring. The connections must be made securely

without tension on the terminals. If the cables are connected or installed in-
correctly, overheating or fire may result.

• The terminal block cover panel of the outdoor unit must be firmly attached. If

the cover panel is mounted incorrectly and dust and moisture enter the unit,
electric shock or fire may result.

• When installing or moving the air conditioner, use only the specified refriger-

ant (R410A) to charge the refrigerant lines. Do not mix it with any other refrig-
erant and do not allow air to remain in the lines. Air enclosed in the lines can
cause pressure peaks resulting in a rupture and other hazards.

• Use only accessories authorized by Mitsubishi Electric and ask a dealer or

an authorized technician to install them. If accessories are incorrectly in-
stalled, water leakage, electric shock, or fire may result.

• Do not alter the unit. Consult a dealer for repairs. If alterations or repairs are

not performed correctly, water leakage, electric shock, or fire may result.

• The user should never attempt to repair the unit or transfer it to another loca-

tion. If the unit is installed incorrectly, water leakage, electric shock, or fire
may result. If the air conditioner must be repaired or moved, ask a dealer or
an authorized technician.

• After installation has been completed, check for refrigerant leaks. If refriger-

ant leaks into the room and comes into contact with the flame of a heater or
portable cooking range, poisonous gases will be released.

1.1. Before installation

 Caution:

• Do not use the unit in an unusual environment. If the air conditioner is in-

stalled in areas exposed to steam, volatile oil (including machine oil), or sulfuric
gas, areas exposed to high salt content such as the seaside, or areas where
the unit will be covered by snow, the performance can be significantly re-
duced and the internal parts can be damaged.

• Do not install the unit where combustible gases may leak, be produced, flow,

or accumulate. If combustible gas accumulates around the unit, fire or explo-
sion may result.

• The outdoor unit produces condensation during the heating operation. Make

sure to provide drainage around the outdoor unit if such condensation is
likely to cause damage.

• When installing the unit in a hospital or communications office, be prepared

for noise and electronic interference. Inverters, home appliances, high-fre-
quency medical equipment, and radio communications equipment can cause
the air conditioner to malfunction or breakdown. The air conditioner may also
affect medical equipment, disturbing medical care, and communications equip-
ment, harming the screen display quality.

• The base and attachments of the outdoor unit must be periodically checked

for looseness, cracks or other damage. If such defects are left uncorrected,
the unit may fall down and cause damage or injuries.

• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all flare nuts to specification using a torque wrench. If tightened too

much, the flare nut can break after an extended period and refrigerant can
leak out.

Contents

1. Safety precautions ................................................................................... 2
2. Installation location .................................................................................. 3
3. Installing the outdoor unit ......................................................................... 4
4. Installing the refrigerant piping ................................................................. 5
5. Drainage piping work ............................................................................... 7

6. Electrical work .......................................................................................... 7
7. Test run .................................................................................................... 9
8. Special Functions .................................................................................. 10
9. System control (Fig. 9-1) ........................................................................ 10

1. Safety precautions

s

Before installing the unit, make sure you read all the “Safety precau-
tions”.

s

Please report to or take consent by the supply authority before connec-
tion to the system.

 Warning:

Describes precautions that must be observed to prevent danger of injury or
death to the user.

 Caution:

Describes precautions that must be observed to prevent damage to the unit.

After installation work has been completed, explain the “Safety Precautions,” use,
and maintenance of the unit to the customer according to the information in the Op-
eration Manual and perform the test run to ensure normal operation. Both the Instal-
lation Manual and Operation Manual must be given to the user for keeping. These
manuals must be passed on to subsequent users.

: Indicates a part which must be grounded.

 Warning:

Carefully read the labels affixed to the main unit.

 BG79U896H02_en

06.5.31, 14:31

2

Summary of Contents for PUY-A NHA

Page 1: ...indoor unit installation manual thoroughly before installing the air conditioner unit MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado Air Conditioners PUZ A NHA PUZ A NHA BS PUY A NHA PUY A NHA BS FOR INSTALLER PARA EL INSTALADOR ...

Page 2: ...ure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly in stalled water leakage electric shock or fire may result Do not alter the unit Consult a dealer for repairs If alterations or repairs are not performed correctly water leakage electric shock or fire m...

Page 3: ...kylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools specifically designed for use with R410A refrigerant The following tools are necessa...

Page 4: ...an optional air outlet guide the clearance for A42 models is 1000 mm 39 3 8 inch or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for A42 models is 1000 mm 39 3 8 inch or more 5 Single parallel unit arrangement Fig 2 16 When using an optional air outlet guide installed for upward airflow the clearance is 500 1000 mm 19 11 16 39 3 8 inch or m...

Page 5: ...occur When bending the pipes be careful not to break them Bend radii of 100 mm 3 15 16 inch to 150 mm 5 27 32 inch are sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1 Pipes must be connected starting from the indoor unit Flare nuts must be tightened with a torque wrench 2 Flare the liquid pipes and gas pipes and apply a thin layer of refrigerat...

Page 6: ...ps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result I Double spanner section Do not apply a spanner other than to this sec tion Doing so would cause coolant leaks J Seal section Seal the end of the heat insulation material at the pipe connection section with whatever seal material you have on hand so that water does not infiltrate the heat insulati...

Page 7: ...n drain piping is necessary use the drain socket or the drain pan option A12 A18 A24 A42 Drain socket PAC SG61DS E Drain pan PAC SG63DP E PAC SG64DP E A B C D E Fig 6 1 Fig 6 2 A24 A42 A12 A18 A Earth terminal B Terminal block C Clamp D Service panel E Wire the cables so that they do not contact the center of the service panel or the gas valve 6 1 Outdoor unit Fig 6 1 Fig 6 2 1 Remove the service ...

Page 8: ...8 A12 A18 CORD COVER CONDUIT COVER CABLE STRAP TERMINAL BED SERVICE PANEL CONDUIT PLATE accessory GR L2 L1 S1 S2 S3 A24 42 ...

Page 9: ... for refrigerant leakage looseness in the power supply or control wiring wrong polarity and no disconnection of one phase in the supply s Use a 500 volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1 0MΩ Ω Ω Ω Ω s Do not carry out this test on the control wiring low voltage circuit terminals Warning Do not use the air conditioner if the insulat...

Page 10: ...he contact input of an ON OFF switch is added to the CNDM connector option on the control board of the outdoor unit The capacity may be insufficient according to the outdoor temperature and condi tions etc 1 Complete the circuit as shown when using the external input adapter PAC SC36NA Option 2 SW1 ON Low noise mode SW1 OFF Normal operation 8 2 Refrigerant collecting pump down Perform the followin...

Page 11: ... 13 16 39 3 8 59 1 16 39 3 8 59 1 16 11 13 16 19 11 16 19 11 16 39 3 8 15 3 4 23 5 8 39 3 8 78 23 32 3 15 16 5 29 32 39 3 8 59 1 16 19 11 16 31 1 2 5 29 32 39 3 8 59 1 16 15 3 4 23 5 8 78 23 32 118 3 32 11 13 16 19 11 16 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 5 29 32 9 27 32 5 29 32 9 27 32 39 3 8 59 1 16 11 13 16 19 11 16 M...

Page 12: ...idad se pueden producir una descarga eléctrica o un incendio Cuando instale o mueva el equipo de aire acondicionado utilice sólo el refri gerante indicado R410A para cargar los tubos de refrigerante No lo mezcle con otro tipo de refrigerante y vacíe completamente de aire los tubos El aire que quede en los tubos puede provocar picos de presión que causarían su rotura y otros daños Utilice sólo acce...

Page 13: ...ón se puede producir el deterioro del aceite o una avería en el aparato Utilice aceite de éster de éter o alquilobenceno en pequeñas cantidades para recubrir las secciones abocardadas Si se mezcla aceite mineral con aceite de refrigeración se puede deteriorar el aceite No utilice otro refrigerante que no sea R410A Si utiliza otro refrigerante el cloro provocará el deterioro del aceite Utilice las ...

Page 14: ...ionales para corriente de aire hacia arriba 3 Obstáculos sólo en la parte delantera Fig 2 14 Si utiliza una guía para salida de aire opcional el espacio libre para los modelos A42 debe ser de 1000 mm 39 3 8 inch o más 4 Obstáculos sólo en la parte delantera y trasera Fig 2 15 Si utiliza una guía para salida de aire opcional el espacio libre para los modelos A42 debe ser de 1000 mm 39 3 8 inch o má...

Page 15: ...erías no tocan el compresor Podría producir ruidos o vibraciones extrañas 1 Las tuberías se deben conectar empezando por la unidad interior Las tuercas abocardadas se deben apretar con una llave dinamométrica 2 Caliente el tubo de líquido y el tubo de gas y aplique una fina capa de aceite de refrigeración aplicado directamente Tubo de cobre O D Dimensiones de abocinado dimensiones øA mm inch mm in...

Page 16: ...ir ruido o puede entrar agua o polvo y la unidad se podría averiar 4 6 Añadido de refrigerante No es necesario realizar una carga adicional si la longitud de la tubería no supera los 20 m 70 ft para A12 A36 o los 30 m 100 ft para A42 Si la longitud de la tubería es superior a la especificada cargue la unidad con refrigerante R410A adicional de acuerdo con las longitudes de tubería permitidas mostr...

Page 17: ...onal A12 A18 A24 A42 Toma de drenaje PAC SG61DS E Batería de drenaje PAC SG63DP E PAC SG64DP E 6 Trabajo eléctrico A B C D E Fig 6 1 Fig 6 2 A24 A42 A12 A18 E B A F C A Tierra del terminal B Bloque de terminales C Grapa D Panel de servicio E Enrute los cables de modo que no entren en contacto con el centro del panel de servicio o la válvula de gas 6 1 Unidad exterior Fig 6 1 Fig 6 2 1 Extraiga el ...

Page 18: ...LE STRAP TERMINAL BED SERVICE PANEL CONDUIT PLATE accessory GR L2 L1 S1 S2 S3 A24 A42 6 Trabajo eléctrico PLACA DEL CONDUCTO accesorio PANEL DE SERVICIO CUBIERTA DE CABLES CUBIERTA DEL CONDUCTO BANCO DE TERMINALES BRIDA DE SUJECIÓN DE CABLES ...

Page 19: ...que no se haya afloja do ni la fuente de alimentación ni el cableado de control que la polaridad no sea errónea y que no se haya desconectado ninguna fase de la alimenta ción s Utilice un megaohmímetro de 500V para comprobar que la resistencia entre los bornes de alimentación y la tierra es como mínimo de 1 0 MΩ Ω Ω Ω Ω s No efectúe esta prueba en los bornes de los cables de control circuito de ba...

Page 20: ... la unidad exterior esté parada abra completamente la válvula de parada de líquido y repita el paso tres al cabo de 3 minutos Si la operación de recuperación del refrigerante se ha completado con éxito los indicadores LED1 y LED2 están encendidos la unidad continuará para da hasta que se corte la corriente 5 Corte la corriente disyuntor Ajuste la dirección de refrigerante utilizando el interruptor...

Page 21: ...2 3 15 16 5 29 32 39 3 8 59 1 16 19 11 16 31 1 2 5 29 32 39 3 8 59 1 16 15 3 4 23 5 8 78 23 32 118 3 32 11 13 16 19 11 16 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 inch 7 7 8 11 13 16 39 3 8 Max 19 11 16 á 5 29 32 9 27 32 5 29 32 9 27 32 39 3 8 59 1 16 11 13 16 19 11 16 Max 19 11 16 á 39 3 8 59 1 16 11 13 16 19 11 16 39 3 8 59 ...

Page 22: ......

Page 23: ......

Page 24: ... on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U896H02 ...

Reviews: