background image

3

2. Installation location

1. Safety precautions

1.3. Before electric work

 Caution:

• Be sure to install circuit breakers. If not installed, electric shock may result.
• For the power lines, use standard cables of sufficient capacity. Otherwise, a

short circuit, overheating, or fire may result.

• When installing the power lines, do not apply tension to the cables. If the

connections are loosened, the cables can snap or break and overheating or
fire may result.

1.4. Before starting the test run

 Caution:

• Turn on the main power switch more than 12 hours before starting operation.

Starting operation just after turning on the power switch can severely dam-
age the internal parts. Keep the main power switch turned on during the op-
eration season.

• Before starting operation, check that all panels, guards and other protective

parts are correctly installed. Rotating, hot, or high voltage parts can cause
injuries.

• Do not touch any switch with wet hands. Electric shock may result.

• Be sure to ground the unit. Do not connect the ground wire to gas or water

pipes, lighting rods, or telephone grounding lines. If the unit is not properly
grounded, electric shock may result.

• Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and

molded case circuit breaker) with the specified capacity. If the circuit breaker
capacity is larger than the specified capacity, breakdown or fire may result.

• Do not touch the refrigerant pipes with bare hands during operation. The

refrigerant pipes are hot or cold depending on the condition of the flowing
refrigerant. If you touch the pipes, burns or frostbite may result.

• After stopping operation, be sure to wait at least five minutes before turning

off the main power switch. Otherwise, water leakage or breakdown may re-
sult.

1.5. Using R410A refrigerant air conditioners

 Caution:

• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,

to connect the refrigerant pipes. Make sure the insides of the pipes are clean
and do not contain any harmful contaminants such as sulfuric compounds,
oxidants, debris, or dust. Use pipes with the specified thickness. (Refer to
page 5) Note the following if reusing existing pipes that carried R22 refriger-
ant.

- Replace the existing flare nuts and flare the flared sections again.
- Do not use thin pipes. (Refer to page 5)

• Store the pipes to be used during installation indoors and keep both ends of

the pipes sealed until just before brazing. (Leave elbow joints, etc. in their
packaging.) If dust, debris, or moisture enters the refrigerant lines, oil dete-
rioration or compressor breakdown may result.

• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil

applied to the flared sections. If mineral oil is mixed in the refrigeration oil, oil
deterioration may result.

• Do not use refrigerant other than R410A refrigerant. If another refrigerant is

used, the chlorine will cause the oil to deteriorate.

• Use the following tools specifically designed for use with R410A refrigerant.

The following tools are necessary to use R410A refrigerant. Contact your
nearest dealer for any questions.

Tools (for R410A)

Gauge manifold

Flare tool

Charge hose

Size adjustment gauge

Gas leak detector

Vacuum pump adapter

Torque wrench

Electronic refrigerant charging scale

• Be sure to use the correct tools. If dust, debris, or moisture enters the refrig-

erant lines, refrigeration oil deterioration may result.

• Do not use a charging cylinder. If a charging cylinder is used, the composi-

tion of the refrigerant will change and the efficiency will be lowered.

2.1. Refrigerant pipe (Fig. 2-1)

s

Check that the difference between the heights of the indoor and outdoor
units, the length of refrigerant pipe, and the number of bends in the pipe are
within the limits shown below.

Models

A

 Pipe length

B

 Height

C

 Number of

 (one way)

difference

bends (one way)

A12, A18

Max. 30 m, 100 ft

Max. 30 m, 100 ft

Max. 15

A24, A30, A36, A42

Max. 50 m, 165 ft

Max. 30 m, 100 ft

Max. 15

• Height difference limitations are binding regardless of which unit, indoor or outdoor,

is positioned higher.

D

Indoor unit

E

Outdoor unit

2.2. Choosing the outdoor unit installation location

• Avoid locations exposed to direct sunlight or other sources of heat.
• Select a location from which noise emitted by the unit will not inconvenience

neighbors.

• Select a location permitting easy wiring and pipe access to the power source and

indoor unit.

• Avoid locations where combustible gases may leak, be produced, flow, or accumulate.
• Note that water may drain from the unit during operation.
• Select a level location that can bear the weight and vibration of the unit.
• Avoid locations where the unit can be covered by snow. In areas where heavy snow

fall is anticipated, special precautions such as raising the installation location or
installing a hood on the air intake must be taken to prevent the snow from blocking
the air intake or blowing directly against it. This can reduce the airflow and a mal-
function may result.

• Avoid locations exposed to oil, steam, or sulfuric gas.
• Use the transportation handles of the outdoor unit to transport the unit. If the unit is

carried from the bottom, hands or fingers may be pinched.

2.3. Outline dimensions (Outdoor unit) (Fig. 2-2)

The figure in parenthesis is for A42 model.

D

E

C

B

A

Fig. 2-1

Fig. 2-2

A24, A30, A36, A42

(inch)

A12, A18

(inch)

37-13/32

13+1-3/16

37-1/8(53-5/32)

6-7/8

23-5/8

14-9/16

31-1/2

11-13/16+29/32

23-5/8

5-29/32

2-23/32

19-11/16

13

 BG79U896H02_en

06.5.31, 14:31

3

Summary of Contents for PUY-A NHA

Page 1: ...indoor unit installation manual thoroughly before installing the air conditioner unit MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado Air Conditioners PUZ A NHA PUZ A NHA BS PUY A NHA PUY A NHA BS FOR INSTALLER PARA EL INSTALADOR ...

Page 2: ...ure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly in stalled water leakage electric shock or fire may result Do not alter the unit Consult a dealer for repairs If alterations or repairs are not performed correctly water leakage electric shock or fire m...

Page 3: ...kylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools specifically designed for use with R410A refrigerant The following tools are necessa...

Page 4: ...an optional air outlet guide the clearance for A42 models is 1000 mm 39 3 8 inch or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for A42 models is 1000 mm 39 3 8 inch or more 5 Single parallel unit arrangement Fig 2 16 When using an optional air outlet guide installed for upward airflow the clearance is 500 1000 mm 19 11 16 39 3 8 inch or m...

Page 5: ...occur When bending the pipes be careful not to break them Bend radii of 100 mm 3 15 16 inch to 150 mm 5 27 32 inch are sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1 Pipes must be connected starting from the indoor unit Flare nuts must be tightened with a torque wrench 2 Flare the liquid pipes and gas pipes and apply a thin layer of refrigerat...

Page 6: ...ps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result I Double spanner section Do not apply a spanner other than to this sec tion Doing so would cause coolant leaks J Seal section Seal the end of the heat insulation material at the pipe connection section with whatever seal material you have on hand so that water does not infiltrate the heat insulati...

Page 7: ...n drain piping is necessary use the drain socket or the drain pan option A12 A18 A24 A42 Drain socket PAC SG61DS E Drain pan PAC SG63DP E PAC SG64DP E A B C D E Fig 6 1 Fig 6 2 A24 A42 A12 A18 A Earth terminal B Terminal block C Clamp D Service panel E Wire the cables so that they do not contact the center of the service panel or the gas valve 6 1 Outdoor unit Fig 6 1 Fig 6 2 1 Remove the service ...

Page 8: ...8 A12 A18 CORD COVER CONDUIT COVER CABLE STRAP TERMINAL BED SERVICE PANEL CONDUIT PLATE accessory GR L2 L1 S1 S2 S3 A24 42 ...

Page 9: ... for refrigerant leakage looseness in the power supply or control wiring wrong polarity and no disconnection of one phase in the supply s Use a 500 volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1 0MΩ Ω Ω Ω Ω s Do not carry out this test on the control wiring low voltage circuit terminals Warning Do not use the air conditioner if the insulat...

Page 10: ...he contact input of an ON OFF switch is added to the CNDM connector option on the control board of the outdoor unit The capacity may be insufficient according to the outdoor temperature and condi tions etc 1 Complete the circuit as shown when using the external input adapter PAC SC36NA Option 2 SW1 ON Low noise mode SW1 OFF Normal operation 8 2 Refrigerant collecting pump down Perform the followin...

Page 11: ... 13 16 39 3 8 59 1 16 39 3 8 59 1 16 11 13 16 19 11 16 19 11 16 39 3 8 15 3 4 23 5 8 39 3 8 78 23 32 3 15 16 5 29 32 39 3 8 59 1 16 19 11 16 31 1 2 5 29 32 39 3 8 59 1 16 15 3 4 23 5 8 78 23 32 118 3 32 11 13 16 19 11 16 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 5 29 32 9 27 32 5 29 32 9 27 32 39 3 8 59 1 16 11 13 16 19 11 16 M...

Page 12: ...idad se pueden producir una descarga eléctrica o un incendio Cuando instale o mueva el equipo de aire acondicionado utilice sólo el refri gerante indicado R410A para cargar los tubos de refrigerante No lo mezcle con otro tipo de refrigerante y vacíe completamente de aire los tubos El aire que quede en los tubos puede provocar picos de presión que causarían su rotura y otros daños Utilice sólo acce...

Page 13: ...ón se puede producir el deterioro del aceite o una avería en el aparato Utilice aceite de éster de éter o alquilobenceno en pequeñas cantidades para recubrir las secciones abocardadas Si se mezcla aceite mineral con aceite de refrigeración se puede deteriorar el aceite No utilice otro refrigerante que no sea R410A Si utiliza otro refrigerante el cloro provocará el deterioro del aceite Utilice las ...

Page 14: ...ionales para corriente de aire hacia arriba 3 Obstáculos sólo en la parte delantera Fig 2 14 Si utiliza una guía para salida de aire opcional el espacio libre para los modelos A42 debe ser de 1000 mm 39 3 8 inch o más 4 Obstáculos sólo en la parte delantera y trasera Fig 2 15 Si utiliza una guía para salida de aire opcional el espacio libre para los modelos A42 debe ser de 1000 mm 39 3 8 inch o má...

Page 15: ...erías no tocan el compresor Podría producir ruidos o vibraciones extrañas 1 Las tuberías se deben conectar empezando por la unidad interior Las tuercas abocardadas se deben apretar con una llave dinamométrica 2 Caliente el tubo de líquido y el tubo de gas y aplique una fina capa de aceite de refrigeración aplicado directamente Tubo de cobre O D Dimensiones de abocinado dimensiones øA mm inch mm in...

Page 16: ...ir ruido o puede entrar agua o polvo y la unidad se podría averiar 4 6 Añadido de refrigerante No es necesario realizar una carga adicional si la longitud de la tubería no supera los 20 m 70 ft para A12 A36 o los 30 m 100 ft para A42 Si la longitud de la tubería es superior a la especificada cargue la unidad con refrigerante R410A adicional de acuerdo con las longitudes de tubería permitidas mostr...

Page 17: ...onal A12 A18 A24 A42 Toma de drenaje PAC SG61DS E Batería de drenaje PAC SG63DP E PAC SG64DP E 6 Trabajo eléctrico A B C D E Fig 6 1 Fig 6 2 A24 A42 A12 A18 E B A F C A Tierra del terminal B Bloque de terminales C Grapa D Panel de servicio E Enrute los cables de modo que no entren en contacto con el centro del panel de servicio o la válvula de gas 6 1 Unidad exterior Fig 6 1 Fig 6 2 1 Extraiga el ...

Page 18: ...LE STRAP TERMINAL BED SERVICE PANEL CONDUIT PLATE accessory GR L2 L1 S1 S2 S3 A24 A42 6 Trabajo eléctrico PLACA DEL CONDUCTO accesorio PANEL DE SERVICIO CUBIERTA DE CABLES CUBIERTA DEL CONDUCTO BANCO DE TERMINALES BRIDA DE SUJECIÓN DE CABLES ...

Page 19: ...que no se haya afloja do ni la fuente de alimentación ni el cableado de control que la polaridad no sea errónea y que no se haya desconectado ninguna fase de la alimenta ción s Utilice un megaohmímetro de 500V para comprobar que la resistencia entre los bornes de alimentación y la tierra es como mínimo de 1 0 MΩ Ω Ω Ω Ω s No efectúe esta prueba en los bornes de los cables de control circuito de ba...

Page 20: ... la unidad exterior esté parada abra completamente la válvula de parada de líquido y repita el paso tres al cabo de 3 minutos Si la operación de recuperación del refrigerante se ha completado con éxito los indicadores LED1 y LED2 están encendidos la unidad continuará para da hasta que se corte la corriente 5 Corte la corriente disyuntor Ajuste la dirección de refrigerante utilizando el interruptor...

Page 21: ...2 3 15 16 5 29 32 39 3 8 59 1 16 19 11 16 31 1 2 5 29 32 39 3 8 59 1 16 15 3 4 23 5 8 78 23 32 118 3 32 11 13 16 19 11 16 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 inch 7 7 8 11 13 16 39 3 8 Max 19 11 16 á 5 29 32 9 27 32 5 29 32 9 27 32 39 3 8 59 1 16 11 13 16 19 11 16 Max 19 11 16 á 39 3 8 59 1 16 11 13 16 19 11 16 39 3 8 59 ...

Page 22: ......

Page 23: ......

Page 24: ... on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U896H02 ...

Reviews: