25
GB
[Fig. 11.3.3] Combination of outdoor units and transmission booster unit
ME
IC
BC
M1M2 S
TB5
IC
M1M2 S
TB5
RP
A B
A B
A B
S
TB2
A B S
TB3
L
15
L
18
ME
IC
M1M2 S
TB5
IC
M1M2 S
TB5
L
17
L
16
L
14
L
13
M1M2 S
M1M2
TB3
M1M2
TB3
M1M2 S
TB7
M1M2 S
TB7
OC
(51)
L
11
L
12
OS
(52)
CN41
CN41
TB02
111
111
( ) Address
Daisy-chain terminals (TB3) on outdoor units in the same
refrigerant system together.
Leave the power jumper connector on CN41 as it is. When
connecting a system controller to the transmission line (TB7) for
centralized control, refer to [Fig. 11.3.1], [Fig. 11.3.2], or DATA
BOOK.
Ground
<Wiring Method and Address Settings>
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, OC-OS and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal
on the transmission line terminal block (TB3) of each outdoor unit (OC) to terminals M1,
M2 and terminal S on the transmission line block of the indoor unit (IC). For OC and OS, connect TB3 to TB3.
c. Connect terminals 1 (M1) and 2 (M2) on the transmission line terminal block of the indoor unit (IC) that has the most recent address within the same group to the
terminal block on the remote controller (RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit in a different refrigerant system (OC). For OC
and OS in the same refrigerant system, connect TB7 to TB7.
e. When the power supply unit is not installed on the central control transmission line, change the jumper connector on the control board from CN41 to CN40 on only
one outdoor unit in the system (except TKMU model). When the System controller is connected to TB7 side and TKMU outdoor unit model is used, connect a PAC-
SC51KUA to TB7 side. If a PAC-SC51KUA cannot be used, connect the System controller to TB3 side. Up to three System controllers can be connected to TB3 side.
f. Connect the terminal S on the terminal block for central control (TB7) for the outdoor unit (OC) for the unit into which the jumper connector was inserted into CN40 in
the step above to the ground terminal
in the electrical component box.
g. Set the address setting switch as follows.
*
To set the outdoor unit address to 100, the outdoor address setting switch must be set to 50.
Unit
Range
Setting Method
Indoor unit (Main)
01 to 50
Use the most recent address within the same group of indoor units. With an R2 system with sub BC
controllers, set the indoor unit address in the following order:
1
Indoor units connected to the main BC controller
2
Indoor units connected to BC sub controller 1
3
Indoor units connected to BC sub controller 2
Set the indoor unit addresses so that all the addresses of
1
are smaller than those of
2
, and that all
the addresses of
2
are smaller than those of
3
.
Indoor unit (Sub)
01 to 50
Use an address, other than that of the IC (Main) from among the units within the same group of indoor
units. This must be in sequence with the IC (Main)
Outdoor Unit (OC, OS)
51 to 100
Set the addresses of the outdoor units in the same refrigerant system in the order of sequential
QXPEHU2&DQG26DUHDXWRPDWLFDOO\LGHQWL¿HG
BC controller (Main)
51 to 100
Outdoor unit address plus 1. When the set indoor unit address duplicates the address of another
indoor unit, set the new address to a vacant address within the setting range.
BC controller (Sub)
51 to 100
Lowest address within the indoor units connected to the BC controller (sub) plus 50
M-NET R/C (Main)
101 to 150
Set at an IC (Main) address within the same group plus 100
M-NET R/C (Sub)
151 to 200
Set at an IC (Main) address within the same group plus 150
MA R/C
–
Unnecessary address setting (Necessary main/sub setting) (*2)
2&DQG26RIWKHRXWGRRUXQLWVLQWKHVDPHUHIULJHUDQWV\VWHPDUHDXWRPDWLFDOO\LGHQWL¿HG7KH\DUHLGHQWL¿HGDV2&DQG26LQGHVFHQGLQJRUGHURIFDSDFLW\,IWKH
FDSDFLW\LVWKHVDPHWKH\DUHLGHQWL¿HGLQWKHDVFHQGLQJRUGHURIWKHLUDGGUHVVQXPEHU
*2 When a PAR-30MAAU is connected to a group, no other MA remote controllers can be connected to the same group.
h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.
i. When the centralized remote controller is connected to the system, set centralized control switches (SW5-1) on control boards in all outdoor units (OC, OS) to “ON”.