22
GB
[1]
Supplied parts
This unit includes the following parts.
1
Band ··· 2 pcs.
[2]
Preparation for installation
&KHFNWKDWWKHPDLQSRZHURQWKHRXWGRRUXQLWLVWXUQHGRII
$IWHUWXUQLQJRIIWKHPDLQSRZHUOHDYHLWWXUQHGRIIIRUDWOHDVWPLQXWHVEHIRUHSURFHHGLQJWKHLQVWDOODWLRQZRUN
[3]
Installation
(1) Thread the power source cable through the rubber bushing on the left side. (Refer to Fig. 1, Note 1, and Note 2.)
(2) Thread the unit wiring (sensor wiring) and the transmission cable through the rubber bushing on the right side. (Refer to Fig. 1, Note 1, and Note 2.)
(3) Hold the power source cable and the transmission cable in place respectively with the cable straps. (Refer to Fig. 1)
(4) Connect the cables respectively to the power supply terminal block and the terminal block for transmission line. (Refer to Fig. 1)
(5) Secure each rubber bushing with the supplied band. (Refer to Fig. 1 and Note 3)
Cable strap
Rubber bushing
Band
¿HOGLQVWDOOHG
Power supply terminal block
M-NET
board
Terminal block for
transmission line
Cable strap
Band
¿HOGLQVWDOOHG
Rubber bushing
Wiring from the unit (sensor wiring)
Transmission cable
¿HOGZLULQJ
Power source cable
¿HOGZLULQJ
<Fig. 1>
Wiring from the unit
(wiring from trans box,
only YKMU model)
Note 1) Make sure the cables are not coming out of the rubber bushing cut. (Fig. 2 and Fig. 3)
Cut
Top view
Wiring
Rubber bushing
Wiring
Rubber bushing
(oval part)
Rubber bushing
(oval part)
Wiring
Cables are coming out of the rubber bushing.
Top view
Cross-sectional view
<Fig. 2>
<Fig. 3>
Note 2) When threading the wiring through the rubber bushing, make sure the rubber bushing will not come off the sheet metal on the control box guard.
(Fig. 4 and Fig. 5)
Rubber bushing
Sheet metal
on the guard
Sheet metal
on the guard
Rubber bushing
<Fig. 4>
<Fig. 5>
Note 3) When tying the supplied band around the rubber bushing, make sure to leave no gap between the ends. (Fig. 6 and Fig. 7)
<<Important>>
When putting the band on the rubber
bushing, make sure the ends of the
rubber bushing overlap each other as
shown in Fig. 6.
* If there is a gap, water from snow
or rain may enter, resulting in
equipment damage.
Approx. 20 mm [13/16 in]
Band
Overlapped
rubber bushing
Cut on the
rubber bushing
<Fig. 6: Back of the rubber bushing>
Cut on
the rubber
bushing
There is a gap
in the rubber
bushing.
<Fig. 7: Back of the rubber bushing>
*2: OC and OS of the outdoor units in the same refrigerant system are
DXWRPDWLFDOO\LGHQWL¿HG7KH\DUHLGHQWL¿HGDV2&DQG26LQGHVFHQGLQJ
order of capacity. (If the capacity is the same, they will be in ascending
order of their address number.)
4. In the case of indoor-outdoor transmission line, connect the shield ground
to the ground terminal
. In the case of transmission lines for centralized
control, connect it to the shield terminal (S) on the terminal block for
centralized control (TB7). Furthermore, in the case of the outdoor units
whose power supply connector CN41 is replaced with CN40, short circuit the
shield terminal (S) and the ground terminal
in addition to the above.
5. Fix the connected wires securely in place with the cable strap at the bottom
of the terminal block. External force applied to the terminal block may
GDPDJHLWDQGPD\FDXVHDVKRUWFLUFXLWJURXQGIDXOWRUD¿UH
6. When extending the transmission line, make sure to extend the shield cable
as well.