26
GB
<Permissible Lengths>
1
M-NET Remote controller [Fig. 11.3.1]
Max length via outdoor units: L
1
+L
2
+L
3
+L
4
and L
1
+L
2
+L
3
+L
5
and L
1
+L
2
+L
6
500 m [1,640 ft] (1.25 mm
2
[AWG 16] or more)
Max transmission cable length: L
1
and L
3
+L
4
and L
3
+L
5
and L
6
and L
2
+L
6
200 m [656 ft] (1.25 mm
2
[AWG 16] or more)
Remote controller cable length:
1
,
2
,
3
,
4
10 m [32 ft] (0.3 to 1.25 mm
2
[AWG 22 to 16])
If the length exceeds 10 m [32 ft], use a 1.25 mm
2
[AWG 16] shielded wire. The length of this section (L
8
) should be included in the
calculation of the maximum length and overall length.
2
MA Remote controller [Fig. 11.3.2]
Max length via outdoor unit (M-NET cable): L
1
+L
2
+L
3
+L
4
and L
1
+L
2
+L
6
500 m [1,640 ft] (1.25 mm
2
[AWG 16] or more)
Max transmission cable length (M-NET cable): L
1
and L
3
+L
4
and L
6
and L
2
+L
6
200 m [656 ft] (1.25 mm
2
[AWG 16] or more)
Remote controller cable length:
m
1
+
m
2
and
m
1
+
m
2
+
m
3
+
m
4
200 m [656 ft] (0.3 to 1.25 mm
2
[AWG 22 to 16])
3
Transmission booster [Fig. 11.3.3]
Max transmission cable length (M-NET cable):
1
L
11
+ L
12
+ L
13
+ L
14
+ L
16
+ L
17
200 m [656 ft] (1.25 mm
2
[AWG 16])
2
L
11
+ L
12
+ L
13
+ L
14
+ L
16
+ L
18
200 m [656 ft] (1.25 mm
2
[AWG 16])
3
L
11
+ L
12
+ L
13
+ L
15
200 m [656 ft] (1.25 mm
2
[AWG 16])
4
L
17
+ L
16
+ L
14
+ L
15
, L
15
+ L
14
+ L
16
+ L
18
200 m [656 ft] (1.25 mm
2
[AWG 16])
Remote controller cable length:
1
,
2
10 m [32 ft] (0.3 to 1.25 mm
2
[AWG 22 to 16])
If the length exceeds 10 m [32 ft], use 1.25 mm
2
[AWG 16] shielded cable and calculate the length of that portion (L
15
and L
18
) as
within the total extended length and the longest remote length.