27
GB
11.4. Wiring of main power supply and equipment capacity
Schematic Drawing of Wiring (Example)
[Fig. 11.4.1]
B
A
C
TKMU:
3~208-230V
YKMU:
3~460V
L
1
, L
2
, L
3
B
A
~208–230V
L
1
, L
2
Ground
Ground
Ground
E
Ground
Ground
E
F
F
'
D
E
E
A
Switch (Breakers for wiring and current leakage)
B
Breakers for current leakage
C
Outdoor unit
D
Pull box
E
Indoor unit
F
BC controller (standard or main)
F
' BC controller (sub)
Thickness of wire for main power supply, ON/OFF capacities
Model
Unit combination
Recommended setting
MCA
(A)
MOCP
(A)
Minimum wire thickness
(mm
2
[AWG])
Switch
(A)
MAX.
CKT.
BKR (A)
Breaker for current leakage
Main
cable
Branch Ground Capacity
Outdoor unit
PURY-HP72TKMU-A-H(-BS)
-
13.3 [6]
-
13.3 [6]
60
60
60A 100mA 0.1sec. or less
44/40
76/69
PURY-HP96TKMU-A-H(-BS)
-
21.2 [4]
-
21.2 [4]
80
80
80A 100mA 0.1sec. or less
60/54
104/94
PURY-HP144TSKMU-A-H(-BS)
PURY-HP72TKMU-A-H(-BS) 13.3 [6]
-
13.3 [6]
60
60
60A 100mA 0.1sec. or less
44/40
76/69
PURY-HP72TKMU-A-H(-BS) 13.3 [6]
-
13.3 [6]
60
60
60A 100mA 0.1sec. or less
44/40
76/69
PURY-HP192TSKMU-A-H(-BS)
PURY-HP96TKMU-A-H(-BS) 21.2 [4]
-
21.2 [4]
80
80
80A 100mA 0.1sec. or less
60/54
104/94
PURY-HP96TKMU-A-H(-BS) 21.2 [4]
-
21.2 [4]
80
80
80A 100mA 0.1sec. or less
60/54
104/94
Outdoor unit
PURY-HP72YKMU-A-H(-BS)
-
5.3 [10]
-
5.3 [10]
30
30
30A 100mA 0.1sec. or less
26
45
PURY-HP96YKMU-A-H(-BS)
-
5.3 [10]
-
5.3 [10]
35
35
35A 100mA 0.1sec. or less
32
56
PURY-HP144YSKMU-A-H(-BS)
PURY-HP72YKMU-A-H(-BS) 5.3 [10]
-
5.3 [10]
30
30
30A 100mA 0.1sec. or less
26
45
PURY-HP72YKMU-A-H(-BS) 5.3 [10]
-
5.3 [10]
30
30
30A 100mA 0.1sec. or less
26
45
PURY-HP192YSKMU-A-H(-BS)
PURY-HP96YKMU-A-H(-BS) 5.3 [10]
-
5.3 [10]
35
35
35A 100mA 0.1sec. or less
32
56
PURY-HP96YKMU-A-H(-BS) 5.3 [10]
-
5.3 [10]
35
35
35A 100mA 0.1sec. or less
32
56
1. Use dedicated power supplies for the outdoor unit and indoor unit. Ensure OC and OS are wired individually.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter.
Make sure the power-supply voltage does not drop more than 10%. Make sure that the voltage imbalance between the phases is 2% or less.
6SHFL¿FZLULQJUHTXLUHPHQWVVKRXOGDGKHUHWRWKHZLULQJUHJXODWLRQVRIWKHUHJLRQ
3RZHUVXSSO\FRUGVRISDUWVRIDSSOLDQFHVIRURXWGRRUXVHVKDOOQRWEHOLJKWHUWKDQSRO\FKORURSUHQHVKHDWKHGÀH[LEOHFRUGGHVLJQ,(&)RU
example, use wiring such as YZW.
6. A switch with at least 3 mm [1/8 in] contact separation in each pole shall be provided when the Air Conditioner is installed.
Warning:
%HVXUHWRXVHVSHFL¿HGZLUHVIRUFRQQHFWLRQVDQGHQVXUHQRH[WHUQDOIRUFHLVLPSDUWHGWRWHUPLQDOFRQQHFWLRQV,IFRQQHFWLRQVDUHQRW¿[HG¿UPO\
KHDWLQJRU¿UHPD\UHVXOW
Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
Caution:
The breakers for current leakage should support Inverter circuit. (e.g. Mitsubishi Electric’s NV-C series or equivalent). If no earth leakage breaker is
installed, it may cause an electric shock.
Breakers for current leakage should combine using of switch.
'RQRWXVHDQ\WKLQJRWKHUWKDQDEUHDNHUZLWKWKHFRUUHFWFDSDFLW\8VLQJDEUHDNHURIWRRODUJHFDSDFLW\PD\FDXVHPDOIXQFWLRQRU¿UH
,IDODUJHHOHFWULFFXUUHQWÀRZVGXHWRPDOIXQFWLRQRUIDXOW\ZLULQJHDUWKOHDNDJHEUHDNHUVRQWKHXQLWVLGHDQGRQWKHXSVWUHDPVLGHRIWKHSRZHUVXSSO\
system may both operate.
Depending on the importance of the system, separate the power supply system or take protective coordination of breakers.