OCH668G
8-1-2. Countermeasures for Error During Test Run
• If a problem occurs during test run, a code number will appear on the remote controller (or LED on the outdoor unit), and the
air conditioning system will automatically cease operating.
Determine the nature of the abnormality and apply corrective measures.
1 2 3 4 5 6 7 8
[Example]
When the compressor and
SV1 are turned during cooling
operation.
Bit
Indication
1
Compressor
operated
2
52C
3
21S4
4
SV1
5
(SV2)
6
—
7
—
8
Always lit
• Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch
(SW1) and LED1, LED2 (LED indication) found on the multi-controller of the outdoor unit.
LED indication: Set all contacts of SW1 to OFF.
• During normal operation
The LED indicates the drive state of the controller in the outdoor unit.
Check
code
(2 digits)
Check
code
(4 digits)
Trouble
Detected Unit
Remarks
Indoor
Outdoor
Remote
Controller
Ed
0403 Serial communication error
Outdoor unit outdoor multi controller circuit board
– Power circuit board communication trouble
U2
1102 Compressor temperature trouble
Check delay code 1202
UE
1302 High pressure trouble
Check delay code 1402
U7
1500
Superheat due to low discharge temperature trouble
Check delay code 1600
U2
1501
Refrigerant shortage trouble
Check delay code 1601
Closed valve in cooling mode
Check delay code 1501
P6
1503
Freeze protection of branch box or indoor unit
EF
1508
4-way valve trouble in heating mode
Check delay code 1608
L6
2135
Circulation water freeze protection
PA
2500
Water leakage
P5
2502
Drain overflow protection
P4
2503 Drain sensor abnormality
UF
4100
Compressor current interruption (locked compressor)
Check delay code 4350
Pb
4114 Fan trouble (Indoor unit)
UP
4210 Compressor overcurrent interruption
U9
4220 Voltage shortage/overvoltage/PAM error/L1 open phase/
primary current sensor error/power synchronization signal error
Check delay code 4320
U5
4230
Heat sink temperature trouble
Check delay code 4330
U6
4250
Power module trouble or Overcurrent trouble
Check delay code 4350
U8
4400 Fan trouble (Outdoor unit)
Check delay code 4500
U3
5101
Air inlet thermistor (TH21) open/short
Compressor temperature thermistor (TH4) open/short
Check delay code 1202
U4
5102
Liquid pipe temperature thermistor (TH22) open/short
Suction pipe temperature thermistor (TH6) open/short
Check delay code 1211
U4
5103 Gas pipe temperature thermistor (TH23) open/short
U4
5105 Outdoor liquid pipe temperature thermistor (TH3) open/short
Check delay code 1205
U4
5106 Ambient temperature thermistor (TH7) open/short
Check delay code 1221
U4
5109
HIC pipe temperature thermistor (TH2) open/short
Check delay code 1222
U4
5110
Heat sink temperature thermistor (TH8) open/short
Check delay code 1214
F5
5201 High pressure sensor (63HS) trouble
Check delay code 1402
F3
5202
Low pressure sensor (63LS) trouble
Check delay code 1400
UH
5300 Primary current error
Check delay code 4310
P4
5701
Contact failure of drain float switch
A0
6600 Duplex address error
Only M-NET Remote controller is detected.
A2
6602
Transmission processor hardware error
Only M-NET Remote controller is detected.
A3
6603 Transmission bus BUSY error
Only M-NET Remote controller is detected.
A6
6606
Signal communication error with transmission processor
Only M-NET Remote controller is detected.
A7
6607 No ACK error
Only M-NET Remote controller is detected.
A8
6608
No response frame error
Only M-NET Remote controller is detected.
E0/E4
6831 MA communication receive error
Only MA Remote controller is detected.
E3/E5
6832 MA communication send error
Only MA Remote controller is detected.
E3/E5
6833 MA communication send error
Only MA Remote controller is detected.
E0/E4
6834 MA communication receive error
Only MA Remote controller is detected.
EF
7100 Total capacity error
EF
7101 Capacity code error
EF
7102
Connecting excessive number of units and branch boxes
EF
7105 Address setting error
EF
7130 Incompatible unit combination
Notes:
1. When the outdoor unit detects No ACK error/No response error, an object indoor unit is treated as a stop, and not assumed to be abnormal.
2. The check codes displayed on the units may be different between the error source and others. In that case, please refer to the check code
of error source by displayed attribute and address.
3. Refer to the service manual of indoor unit or remote controller for the detail of error detected in indoor unit or remote controller.