2-4. SYSTEM SPECIFICATIONS
(2) Method for identifying MULTI-S model
(1) Outdoor Unit
Outdoor unit <When using model 125 >
PU M Y - SP 125 Y
K M - BS
Refrigerant
R410A
Indicates equivalent
to Cooling capacity
Power supply
V
: Single phase
220-230-240 V, 50 Hz
220 V, 60 Hz
Y
: 3-phase
380-400-415 V, 50 Hz
380 V, 60 Hz
Outdoor unit
model type
M-NET
control
Frequency
conversion
controller
Outdoor unit
MULTI-S
(kcal/ h)
Salt proof
type
Cooling capacity indicates the maximum value at operation under the following condition.
*Cooling Indoor
: D.B. 27°C/W.B. 19°C
Outdoor : D.B. 35°C
*Heating Indoor : D.B. 20°C
Outdoor : D.B. 7°C/W.B. 6°C
Outdoor unit
SP112
SP125
SP140
Capacity
Cooling (kW)
12.5
14.0
15.5
Heating (kW)
14.0
16.0
16.5
(3) Operating temperature range
Cooling
Heating
Indoor intake air temperature
W.B. 15 to 24°C
D.B. 15 to 27°C
Outdoor intake air temperature
D.B. −5 to 52°C
*1
W.B. −20 to 15°C
Notes: D.B.:
Dry Bulb Temperature
W.B.: Wet Bulb Temperature
*1
10 to 52°C D.B.: When connecting PKFY-P15/P20/P25VBM, PKFY-P10/15/20/25/32VLM, PFFY-P20/25/32VKM, PFFY-P20/25/32VCM,
PFFY-P20/25/32VLE(R)M(M) and; M series, S series, and P series type indoor unit.
■ When connecting fresh air type indoor unit
• PEFY-P·VMH-E-F
Cooling
Heating
Indoor and Outdoor intake air temperature
D.B. 21 to 43ºC
*2
W.B. 15.5 to 35ºC
D.B. −10 to 20ºC
*3
D.B. 21 to 43ºC
*2
W.B. 15.5 to 35ºC
D.B. −5 to 20ºC
*3
*2
Thermo-OFF (FAN-mode) automatically starts if the outdoor temperature is lower than 21ºC D.B.
*3
Thermo-OFF (FAN-mode) automatically starts if the outdoor temperature is higher than 20ºC D.B.
• PEFY-P·VMHS-E-F
Cooling
Heating
Indoor and Outdoor intake air temperature
D.B. 17 to 43ºC
*4
W.B. 15.5 to 35ºC
D.B. −5 to 20ºC
*5
*4
Thermo-OFF (FAN-mode) automatically starts if the outdoor temp. is lower than 17°C D.B..
*5
Thermo-OFF (FAN-mode) automatically starts if the outdoor temp. is higher than 21°C D.B..