background image

2

1.2. Before installation (relocation)

 Caution:

• Be extremely careful when transporting the units. Two or more persons are

needed to handle the unit, as it weighs 20 kg [44 lbs] or more. Do not grasp the
packaging bands. Wear protective gloves to remove the unit from the packag-
ing and to move it, as you can injure your hands on the fins or other parts.

• Be sure to safely dispose of the packaging materials. Packaging materials, such

as nails and other metal or wooden parts may cause stabs or other injuries.

• The base and attachments of the outdoor unit must be periodically checked

for looseness, cracks or other damage. If such defects are left uncorrected,
the unit may fall down and cause damage or injuries.

 Warning:

• The unit must not be installed by the user. Ask a dealer or an authorized

technician to install the unit. If the unit is installed incorrectly, water leakage,
electric shock, or fire may result.

• For installation work, follow the instructions in the Installation Manual and use

tools and pipe components specifically made for use with R410A refrigerant.
The R410A refrigerant in the HFC system is pressurized 1.6 times the pressure
of usual refrigerants. If pipe components not designed for R410A refrigerant
are used and the unit is not installed correctly, the pipes may burst and cause
damage or injuries. In addition, water leakage, electric shock, or fire may result.

• The unit must be installed according to the instructions in order to minimize

the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.

• The unit must be securely installed on a structure that can sustain its weight.

If the unit is mounted on an unstable structure, it may fall down and cause
damage or injuries.

• If the air conditioner is installed in a small room, measures must be taken to

prevent the refrigerant concentration in the room from exceeding the safety
limit in the event of refrigerant leakage. Consult a dealer regarding the appro-
priate measures to prevent the allowable concentration from being exceeded.
Should the refrigerant leak and cause the concentration limit to be exceeded,
hazards due to lack of oxygen in the room may result.

• Ventilate the room if refrigerant leaks during operation. If refrigerant comes

into contact with a flame, poisonous gases will be released.

• All electric work must be performed by a qualified technician according to

local regulations and the instructions given in this manual. The units must be
powered by dedicated power lines and the correct voltage and circuit break-
ers must be used. Power lines with insufficient capacity or incorrect electri-
cal work may result in electric shock or fire.

• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,

to connect the refrigerant pipes. If the pipes are not connected correctly, the
unit will not be properly grounded and electric shock may result.

• Use only specified cables for wiring. The connections must be made securely

without tension on the terminals. If the cables are connected or installed in-
correctly, overheating or fire may result.

• The terminal block cover panel of the outdoor unit must be firmly attached. If

the cover panel is mounted incorrectly and dust and moisture enter the unit,
electric shock or fire may result.

• When installing or moving the air conditioner, use only the specified refriger-

ant (R410A) to charge the refrigerant lines. Do not mix it with any other refrig-
erant and do not allow air to remain in the lines. Air enclosed in the lines can
cause pressure peaks resulting in a rupture and other hazards.

• Use only accessories authorized by Mitsubishi Electric and ask a dealer or

an authorized technician to install them. If accessories are incorrectly in-
stalled, water leakage, electric shock, or fire may result.

• Do not alter the unit. Consult a dealer for repairs. If alterations or repairs are

not performed correctly, water leakage, electric shock, or fire may result.

• The user should never attempt to repair the unit or transfer it to another loca-

tion. If the unit is installed incorrectly, water leakage, electric shock, or fire
may result. If the air conditioner must be repaired or moved, ask a dealer or
an authorized technician.

• After installation has been completed, check for refrigerant leaks. If refriger-

ant leaks into the room and comes into contact with the flame of a heater or
portable cooking range, poisonous gases will be released.

1.1. Before installation

 Caution:

• Do not use the unit in an unusual environment. If the air conditioner is in-

stalled in areas exposed to steam, volatile oil (including machine oil), or sulfuric
gas, areas exposed to high salt content such as the seaside, or areas where
the unit will be covered by snow, the performance can be significantly re-
duced and the internal parts can be damaged.

• Do not install the unit where combustible gases may leak, be produced, flow,

or accumulate. If combustible gas accumulates around the unit, fire or explo-
sion may result.

• The outdoor unit produces condensation during the heating operation. Make

sure to provide drainage around the outdoor unit if such condensation is
likely to cause damage.

• When installing the unit in a hospital or communications office, be prepared

for noise and electronic interference. Inverters, home appliances, high-fre-
quency medical equipment, and radio communications equipment can cause
the air conditioner to malfunction or breakdown. The air conditioner may also
affect medical equipment, disturbing medical care, and communications equip-
ment, harming the screen display quality.

• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all flare nuts to specification using a torque wrench. If tightened too

much, the flare nut can break after an extended period and refrigerant can
leak out.

Contents

1. Safety precautions ................................................................................... 2
2. Installation location .................................................................................. 3
3. Installing the outdoor unit ......................................................................... 5
4. Installing the refrigerant piping ................................................................. 5

5. Drainage piping work ............................................................................... 8
6. Electrical work .......................................................................................... 8
7. Test run ................................................................................................... 11

1. Safety precautions

s

Before installing the unit, make sure you read all the “Safety precau-
tions”.

s

Please report to or take consent by the supply authority before connec-
tion to the system.

 Warning:

Describes precautions that must be observed to prevent danger of injury or
death to the user.

 Caution:

Describes precautions that must be observed to prevent damage to the unit.

After installation work has been completed, explain the “Safety Precautions”, use,
and maintenance of the unit to the customer according to the information in the Op-
eration Manual and perform the test run to ensure normal operation. Both the Instal-
lation Manual and Operation Manual must be given to the user for keeping. These
manuals must be passed on to subsequent users.

: Indicates a part which must be grounded.

 Warning:

Carefully read the labels affixed to the main unit.

Confirmation of parts attached

In addition to this manual, the following parts are supplied with the outdoor unit.
They are used for grounding the S terminals of transmission terminal blocks TB3,
TB7. For details refer to “6. Electrical work”.

Grounding lead wire (

×

 2)

Summary of Contents for PUMY-P36NHMU

Page 1: ...l MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado PARA EL INSTALADOR For use with R410A Français MANUEL D INSTALLATION Avant d installer le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil intérieur pour une utilisation sûre ...

Page 2: ...frig erant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly in stalled water leakage electric shock or fire may result Do not alter the unit Consult a dealer for repa...

Page 3: ... or moisture enters the refrig erant lines refrigeration oil deterioration may result Do not use a charging cylinder If a charging cylinder is used the composi tion of the refrigerant will change and the efficiency will be lowered 2 Installation location 2 1 Refrigerant pipe Refer to Fig 4 1 2 2 Choosing the outdoor unit installation location Avoid locations exposed to sources of heat Select a loc...

Page 4: ... 500 mm 19 11 16 inch or more 6 Obstacles at rear sides and above only Fig 2 7 Do not install the optional air outlet guides for upward airflow 2 4 2 When installing multiple outdoor units Leave 10 mm 13 32 inch space or more between the units 1 Obstacles at rear only Fig 2 8 2 Obstacles at rear and above only Fig 2 9 No more than three units must be installed side by side In addition leave space ...

Page 5: ... on site Warning The unit must be securely installed on a structure that can sustain its weight If the unit is mounted on an unstable structure it may fall down and cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An incor rectly installed unit may fall down and cause damage or injuri...

Page 6: ...ring of R410A refrigerant pipes The size adjustment gauge can be used to confirm A measurements A mm inch Å Liquid pipe ı Gas pipe PUMY ø9 52 3 8 ø15 88 5 8 B C D mm inch Ç Total capacity of indoor units Å Liquid pipe ı Gas pipe ø9 52 3 8 ø15 88 5 8 a b c d e f mm inch Î Model number Å Liquid pipe ı Gas pipe P06 P08 P12 P15 P18 ø6 35 1 4 ø12 7 1 2 P24 P30 P36 P48 P54 ø9 52 3 8 ø15 88 5 8 Branch ki...

Page 7: ... surrounding temperature and refrigerant pressure 3 If the specified pressure holds for about one day and does not decrease the pipes have passed the test and there are no leaks If the surrounding temperature changes by 1 C 1 8 F the pressure will change by about 0 01 MPa 1 5 PSIG Make the necessary corrections 4 If the pressure decreases in steps 2 or 3 there is a gas leak Look for the source of ...

Page 8: ...s sometimes removed at the time of service work 5 Never connect the main power source to terminal block of transmission line If connected electrical parts will be burnt out 6 Use 2 core shield cable for transmission line If transmission lines of different systems are wired with the same multiplecore cable the resultant poor transmit ting and receiving will cause erroneous operations 6 Electrical w...

Page 9: ...the transmission cable terminal block of the indoor unit IC that has the most recent address within the same group to the terminal block on the remote controller RC d Connect together terminals M1 M2 and terminal S on the terminal block for central control TB7 for the outdoor unit OC e The jumper connector CN41 on the control panel does not change f Connect the terminal S on the terminal block for...

Page 10: ...r than breaker and fuse with correct capacity Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire 30 A 30 mA 0 1 sec or less 30 A 5 3 AWG10 5 3 AWG10 Indoor Unit Main Cable 2 Minimum Wire Thickness mm2 AWG Breaker for Current Leakage Model Outdoor Unit P36 P48 Breaker for Wiring 1 Ground 6 Electrical work Thickness of Wire for Main Power Supply and On...

Page 11: ...manifold valve and put the cap back onto each stop valve Note 1 Never carry out pump down operation if the amount of refrigerant inside the indoor unit is larger than the amount of charge less refrigerant Carrying out a pump down operation when the amount of refrigerant ex ceeds the amount of charge less refrigerant will cause an extreme pres sure rise and may result in an accident 2 Do not contin...

Page 12: ...220 y tubos de aleación de cobre sin costuras para conectar los tubos del refrigerante Si los tubos no se co nectan correctamente la unidad no estará bien puesta a tierra y puede pro vocar descargas eléctricas Utilice sólo cables especificados para el cableado Las conexiones se deben realizar con seguridad sin corriente en los terminales Si los cables no están bien conectados o no se han instalado...

Page 13: ...n refrigerante R22 Sustituya las tuercas de abocardado existentes y vuelva a abocardar las seccio nes abocardadas No use tuberías de poco grosor Consulte la página 15 Almacene las tuberías que se deban instalar en el interior y mantenga los orificios tapados hasta el momento de instalarlas Deje las juntas articula das y otras piezas en sus embalajes Si el polvo los restos o la humedad entran en la...

Page 14: ...ólo en la parte trasera y superior Fig 2 9 No se deben instalar más de tres unidades correlativas Además se debe dejar el espacio indicado No utilice las guías para salida de aire opcionales para corriente de aire hacia arriba 3 Obstáculos sólo en la parte delantera Fig 2 10 Si utiliza una guía para salida de aire opcional el espacio libre deberá ser de 1000 mm 39 3 8 inch o más 4 Obstáculos sólo ...

Page 15: ...le con otro tipo de refrigerante y vacíe completamente de aire los tubos El aire que quede en los tubos puede provocar picos de presión que causarían su rotura y otros daños Tipo de unidad interior P06 P18 P24 P54 Tubo de líquido ø6 35 mm 1 4 inch ø9 52 mm 3 8 inch grosor 0 8 mm 1 32 inch grosor 0 8 mm 1 32 inch Tubo de gas ø12 7 mm 1 2 inch ø15 88 mm 5 8 inch grosor 0 8 mm 1 32 inch grosor 1 0 mm...

Page 16: ...te Cuando utilice un sellador de tubos normal consulte la Tabla 1 para abocardar tuberías para refrigerante R410A Para confirmar las medidas de A se puede utilizar el ajustador del tamaño A mm inch Å Tubo de líquido ı Tubo de gas PUMY ø9 52 3 8 ø15 88 5 8 B C D mm inch Ç Capacidad total de las unidades interiores Å Tubo de líquido ı Tubo de gas ø9 52 3 8 ø15 88 5 8 a b c d e f mm inch Î Número de ...

Page 17: ...n no se ha reducido 3 Presurice a 3 8 MPa 550 PSIG y tome la temperatura ambiental y la presión del refrigerante 3 Si la presión especificada se mantiene estable durante un día y no se reduce las tuberías han pasado la prueba y no existe riesgo de fugas Si la temperatura ambiental cambia 1 C 1 8 F la presión variará unos 0 01 MPa 1 5 PSIG Haga las correcciones necesarias 4 Si la presión se reduce ...

Page 18: ...uando se realiza el trabajo de man tenimiento 5 No conecte nunca la fuente principal de energía al bloque de terminal de la línea de transmisión Si está conectado las piezas eléctricas se quemarán 6 Use cable blindado de dos almas para la línea de transmisión Si las líneas de transmisión de sistemas diferentes están conectados con los mismos cables de varias almas la pobre transmisión y recepción ...

Page 19: ...s IC que no sea el de IC máster IC máster debe ser secuencial Unidad exterior de 51 a 100 Ajuste la dirección más reciente de las unidades interiores en el mismo sistema de refrigeración 50 La dirección se establece automáticamente en 100 si se configura como 01 50 M NET R C máster de 101 a 150 Ajuste la dirección IC máster 100 M NET R C subordinada de 151 a 200 Ajuste la dirección IC máster 150 M...

Page 20: ... fuga de tierra Si no se instala un disyuntor de fuga de tierra puede producirse un electroshock Use los fusibles y el disyuntor con la capacidad correcta Si emplea un fusible o cable con demasiada capacidad puede haber una disfunción de la unidad o incluso puede producirse un incendio 6 Trabajo eléctrico Grosor del cable para el suministro principal de energía y capacidades on off 6 4 Cableado de...

Page 21: ...cio exterior SW2 4 de ON a OFF 8 Extraiga la válvula distribuidora del medidor y vuelva a colocar el tapón a cada válvula de parada Notas 1 Nunca realice el vaciado si la cantidad de refrigerante del interior de la unidad interior es superior a la cantidad de refrigerante no cargado Si realiza este procedimiento cuando la cantidad de refrigerante es supe rior a la cantidad de refrigerante sin carg...

Page 22: ...duire N utiliser que les câbles spécifiés pour les raccordements Les connexions doi vent être correctement effectuées sans tension sur les bornes Si les câbles ne sont pas correctement connectés ou installés une surchauffe ou un incendie peut se produire Le couvercle du bloc de sortie de l appareil extérieur doit être solidement fixé S il n est pas correctement installé et si des poussières et de ...

Page 23: ...éléphoniques Une mise à la terre incorrecte de l appareil peut provoquer un choc électrique Utiliser des coupe circuits disjoncteur de fuite à la terre interrupteur d isolement fusi ble B et disjoncteur à boîtier moulé à la capacité spécifiée Si la capacité du coupe circuit est supérieure à celle spécifiée une défaillance ou un incendie peut se produire Ne pas toucher les interrupteurs les mains h...

Page 24: ...s Espacer également les appareils comme illustré Ne pas utiliser les guidages de sortie d air en option pour un débit d air vers le haut 3 Obstacles uniquement à l avant Fig 2 10 Lors de l utilisation d un guidage de sortie d air en option le jeu est de 1000 mm 39 3 8 inch minimum 4 Obstacles uniquement à l avant et à l arrière Fig 2 11 Lors de l utilisation d un guidage de sortie d air en option ...

Page 25: ...mélanger avec un autre réfrigérant et faire le vide d air dans les tuyaux La présence d air dans les tuyaux peut provoquer des pointes de pression entraînant une rupture et d autres risques Type d appareil intérieur P06 P18 P24 P54 Conduit de liquide ø6 35 mm 1 4 inch ø9 52 mm 3 8 inch épaisseur 0 8 mm 1 32 inch épaisseur 0 8 mm 1 32 inch Conduit de gaz ø12 7 mm 1 2 inch ø15 88 mm 5 8 inch épaisse...

Page 26: ...e d huile réfrigérante application sur site Si un procédé d étanchéité traditionnel est utilisé pour les tuyaux se reporter au tableau 1 pour l évasement des tuyaux de réfrigérant R410A La jauge de réglage de la taille peut être utilisée pour confirmer les mesures A A mm inch Å Conduit de liquide ı Conduit de gaz PUMY ø9 52 3 8 ø15 88 5 8 B C D mm inch Ç Puissance totale des appareils intérieurs Å...

Page 27: ...nt ou d être endommagé à cause d une infiltration d eau et de poussières A Vanne d arrêt côté liquide B Vanne d arrêt côté gaz C Orifice pour l entretien D Section d ouverture fermeture E Tuyau local A Couvercle de la tuyauterie avant B Couvercle de la tuyauterie C Vanne d arrêt D Panneau de service E Rayon de cintrage 100 mm 150 mm F Hermétique idem pour le côté gaz G Fourrure du tuyau H Ne pas u...

Page 28: ...5 Ne jamais raccorder la source d alimentation principale au bloc terminal de la ligne de transmission car cela brûlerait les composants électriques 6 Utiliser un câble blindé à deux fils comme ligne de transmission Si les lignes de trans mission des différents systèmes devaient être reliées par le même câble à fils multi ples la transmission et la réception seraient mauvaises ce qui conduirait à ...

Page 29: ...eils extérieurs OC e Le cavalier CN41 du panneau de commande ne change pas f Raccorder la borne S du bloc de sorties du contrôle centralisé de l unité d alimentation à la borne de terre du boîtier des composants électriques g Régler les commutateurs d adresses comme indiqué ci dessous 6 Installations électriques 2 Câbles de la télécommande M NET Type de câble de télécommande Diamètre du câble Rema...

Page 30: ...ce coupe circuit n est pas installé il peut y avoir danger d électrocu tion Ne jamais utiliser de coupe circuits ou de fusibles autres que ceux possédant la valeur adéquate L utilisation de fusibles et de fils fils en cuivre surdimensionnés risque de provoquer un mauvais fonctionnement de l appareil voir un incendie 6 Installations électriques Section des câbles pour l alimentation principale et c...

Page 31: ...la vanne collective à jauge et remettre le capuchon en place sur chacune des vannes d arrêt Remarque 1 Ne jamais procéder au pompage si la quantité de réfrigérant dans l appareil inté rieur est supérieure à la quantité de réfrigérant sans charge supplémentaire Le pompage lorsque la quantité de réfrigérant dépasse la quantité de réfrigérant sans charge provoquera une forte augmentation de pression ...

Page 32: ... on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U872H02 ...

Reviews: