42
10-10. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS
(1) Function of switches
*1 Forced defrost should be done as follows.
1
Change the DIP SW1-1 on the outdoor controller board from OFF to ON.
2
Forced defrost will start by the above operation
1
if all these conditions written below are satisfied.
• Heat mode setting
• 10 minutes have passed since compressor started operating or previous compulsory defrosting finished.
• Pipe temperature is less than or equal to 8
:
.
Forced defrost will finish if certain conditions are satisfied.
Forced defrost can be done if above conditions are satisfied when DIP SW1-1 is changed from OFF to ON.
After DIP SW1-1 is changed from OFF to ON, there is no problem if DIP SW1-1 is left ON or changed to OFF again.
This depends on the service conditions.
*2 ‘Power failure automatic recovery’ can be set by either remote controller or this DIP SW. If one of them is set to ON, ‘Auto recovery’ acti-
vates. Please set “Auto recovery” basically by remote controller because all units do not have DIP SW.
Please refer to the indoor unit installation manual.
*3
SW7-1 is setting change over of Demand/Low noise. It is effective only in case of external input.
(Local wiring is necessary. Refer to next page: Special function)
*4
Please do not use SW7-3 to SW7-6 usually. Trouble might be caused by the usage condition.
w
5
With this switch setting, the capacity decreases up to 30% under peak load condition. Thus this setting is recommended only for Air to
water purposes.
The black square ( ) indicates a switch position.
Type of
Switch
Swich No.
Function
Action by the switch operation
Effective timing
ON
OFF
Dip
switch
SW1
1
Forced defrost *1
Start
Normal
When compressor is working
in heating operation. *1
2
Abnormal history clear
Clear
Normal
OFF or operating
3
Refrigerant address setting
1 2 3
0
1
2
3
4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3
4
5
4 5 6
ON
1 2 3 4 5 6
ON
When power supply ON
4
5
6
SW4
1
Test run
Operating
OFF
Under suspension
2
Test run mode setting
Heating
Cooling
Push
switch
SWP
Pump down
Start
Normal
Under suspension
Dip
switch
SW5
1
No function
—
—
—
2
Power failure
automatic recovery *2
Auto recovery
No auto recovery
When power supply ON
3,4,5
No function
—
—
—
6
Model select
Following SW5-6 reference
SW7
*4
1
Mode select *3
Demand function
Low noise mode
Always
2
No function
—
—
—
3
Max Hz setting (cooling)
Max Hz (cooling)
o
0.8
Normal
Always
4
Max Hz setting (heating)
Max Hz (heating)
o
0.8
Normal
Always
5
Breaker capacity setting *5
16A
25A
When power supply ON
6
Defrost setting
For high humidity
Normal
Always
SW8
1
No function
—
—
—
2
No function
—
—
—
3
No function
—
—
—
SW9
1
No function
—
—
—
2
Function switch
Valid
Normal
Always
3,4
No function
—
—
—
SW6
1
Model select
1 2 3
6
4
7 8
OFF
ON
40
MODEL
SW6
1 2 3
6
4
7
5
8
OFF
ON
50
5
1 2 3 4 5 6
OFF
ON
SW5-6
1 2 3 4 5 6
OFF
ON
The black square (
■
) indicates a switch position.
2
3
4
5
6
7
8
SW5
6
OCH525