background image

29

AC 198V to AC 264V?

Are there looseness or 

disconnection of the indoor/

outdoor connecting wire?

Is anything displayed?

DC 17V to DC 28V?

Is “E8” displayed?

Can all the indoor 

unit be operated?

Check the voltage between S2 

and S3 on the terminal block of 

the outdoor unit.

NO

YES

Not lighting.

Blinking.

NO

YES

NO

YES

Not displayed.

Displayed.

YES

NO

YES

NO

Check the voltage between S1 and S2 on the terminal block (TB4) 

of the indoor unit which is used to connect the indoor unit and the 

outdoor unit.

Check the refrigerant address of 

the outdoor unit. (SW1-3 to 1-6)

Check the looseness or disconnection 

of the indoor/outdoor connecting wire.

Check the LED display of the 

outdoor unit after turning on the 

main power again.

Can the unit be restarted?

• Breaking or poor contact 

  of the indoor/outdoor 

  connecting wire

• Fix the breaking or poor 

contact of the indoor/outdoor 

  connecting wire.

• Defective outdoor 

  controller circuit 

  board

• Replace the outdoor 

  controller circuit board.

• Normal. 

  Only the unit which 

  has the refrigerant 

  address “0” supplies 

  power to the remote 

  controller.

• Set the refrigerant 

  address to “0”. In case of 

  the multiple grouping 

  system, recheck the 

  refrigerant address again.

• Defective indoor 

  power board

• Replace the indoor 

  power board.

• Defective outdoor 

  power circuit board

• Replace the outdoor 

  power circuit board.

• Defective indoor 

  controller board

• Replace the indoor controller 

board of the indoor unit which 

  doesn’t operate.

• Defective outdoor 

  controller circuit 

  board

• Replace the outdoor 

  controller circuit board.

• Influence of 

electromagnetic noise

• Not abnormal. 

There may be the influence 

  of electromagnetic noise. 

Check the transmission wire 

  and get rid of the causes.

Symptoms: Nothing is displayed on the remote controller 

Diagnosis flow

Cause

Inspection method and 

troubleshooting

LED display of the indoor 

controller board

LED1 :

LED2 : 

LED3 :       or 

Check the status 

of the indoor controller 

board LED3 display.

Is the refrigerant 

address “0”?

NO

YES

NO

YES

Is “EA” or “Eb” 

displayed?

OCH525

Summary of Contents for PUHZ-SW40VHA

Page 1: ...NTENTS 1 REFERENCE MANUAL 2 2 SAFETY PRECAUTION 2 3 FEATURES 6 4 SPECIFICATIONS 6 5 DATA 8 6 OUTLINES AND DIMENSIONS 9 7 WIRING DIAGRAM 10 8 WIRING SPECIFICATIONS 11 9 REFRIGERANT SYSTEM DIAGRAM 12 10 TROUBLESHOOTING 14 11 DISASSEMBLY PROCEDURE 55 Note This manual describes only service data of the outdoor units Salt proof model PUHZ SW40VHA BS PUHZ SW50VHA BS PUHZ SW40VHA BS PUHZ SW50VHA BS ...

Page 2: ...pipes with specified thickness In case of using the existing pipes for R22 be careful with the followings Be sure to clean the pipes and make sure that the insides of the pipes are clean Change flare nut to the one provided with this product Use a newly flared pipe Avoid using thin pipes Do not use refrigerant other than R410A If other refrigerant R22 etc is used chlorine in refrige rant can cause...

Page 3: ... cause deterioration of refrigerant oil or malfunction of com pressor Do not use a charging cylinder If a charging cylinder is used the composition of refrigera nt will change and the efficiency will be lowered If dirt dust or moisture enters into refrigerant cycle that can cause deterioration of refrigerant oil or malfunction of com pressor If large amount of mineral oil enters that can cause det...

Page 4: ...r collecting in the base of the outdoor unit could cause rust 4 If the unit is installed in a coastal area clean the unit with water regularly to remove any salt build up 5 If the unit is damaged during installation or maintenance be sure to repair it 6 Be sure to check the condition of the unit regularly 7 Be sure to install the unit in a location with good drainage 2 4 PRECAUTIONS FOR SALT PROOF...

Page 5: ... 0 29 0 17 0 22 0 24 0 27 0 36 0 Nominal dimensions inch Flare nut dimensions Outside diameter Dimension B mm R410A R22 Gauge manifold Charge hose Gas leak detector Refrigerant recovery equipment Refrigerant cylinder Applied oil Safety charger Charge valve Vacuum pump Flare tool Bender Pipe cutter Welder and nitrogen gas cylinder Refrigerant charging scale Vacuum gauge or thermis tor vacuum gauge ...

Page 6: ... EN 14511 4 SPECIFICATIONS PUHZ SW40VHA PUHZ SW40VHA BS PUHZ SW50VHA PUHZ SW50VHA BS Nominal water flow L min 11 80 Heating A7 W35 Capacity kW 4 10 COP 4 80 Power input kW 0 85 Heating A7 W45 Capacity kW 4 10 COP 3 63 Power input kW 1 13 Heating A2 W35 Capacity kW 4 00 COP 3 24 Power input kW 1 24 Heating A2 W45 Capacity kW 4 00 COP 2 68 Power input kW 1 49 Nominal water flow L min 10 30 Cooling A...

Page 7: ...2 7 1 2 Flared Flared Max 10m Max 40m HP switch Comp surface thermo Discharge thermo Over current detection Single 50Hz 230V 13 45 45 46 46 OUTDOOR UNIT REFRIGERANT PIPING Rating conditions Nominal operating condition Heating A7 W35 Outside air temperature Dry bulb 7 C Outside air temperature Wet bulb 6 C Water temperature inlet outlet 30 C 35 C Heating A7 W45 Outside air temperature Dry bulb 7 C ...

Page 8: ... DATA 5 3 NOISE CRITERION CURVES 1 5m 1m MICROPHONE UNIT GROUND APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 PUHZ SW40VHA BS COOLING MODE HEATING 45 SPL dB 45 LINE 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 OCTAVE BAND SOUND PRESSURE LEVEL dB 0 dB 0 0002 μbar BAND CENTER FREQUENCIES Hz APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS N...

Page 9: ...door unit basic example Piping and wiring connection can be made from the rear direction only PIPING WIRING DIRECTION Handle for moving Handle for moving 18 69 10 600 300 287 5 800 Terminal connections Left Power supply wiring Right Indoor Outdoor wiring Service panel Earth terminal Service panel for charge plug Connection for liquid pipe FLARE 6 35 1 4F Connection for gas pipe FLARE 12 7 1 2F Ser...

Page 10: ...rgency Operation Connector Connection for Option Connector Connection for Option Connector Connection for Option Connector Connection for Option Connector Connection for Option LED Operation Inspection Indicators Fuse T6 3AL250V Relay C B P B TH8 TH6 TH7 TH4 TH3 U CB3 N F 21S4 L N S1 S2 S3 INDOOR UNIT POWER SUPPLY N 230V 50Hz TB1 V W 5 2 2 2 2 RED WHT BLK t t t t t t M C CN5 RED CNAC2 RED CNAC1 WH...

Page 11: ...g Wire No size mm 2 Outdoor unit power supply 3 Min 1 5 Indoor unit Outdoor unit 2 3 1 5 Polar Indoor unit Outdoor unit earth 2 1 Min 1 5 Remote controller Indoor unit 3 2 0 3 Non polar Circuit rating Outdoor unit L N single Outdoor unit L1 N L2 N L3 N 3 phase 4 AC 230 V Indoor unit Outdoor unit S1 S2 4 AC 230 V Indoor unit Outdoor unit S2 S3 4 DC 24 V Remote controller Indoor unit 4 DC 12 V 1 A b...

Page 12: ...itsubishi Electric Corporation For protection OFF 4 15MPa Change the refrigerant circuit Heating Cooling and for Defrosting High pressure Low pressure For production test use For calculation of the condensing temperature from high pressure Heating Secondary LEV Cooling Primary LEV Heating Primary LEV Cooling Secondary LEV Heating Evaporating temperature Cooling Sub cool liquid temperature For LEV ...

Page 13: ...t collection is not properly performed Open the liquid stop valve completely and then repeat step 2 after 3 minutes have passed If the refrigerant collecting operation has been completed normally LED1 off LED2 lit the unit will remain stopped until the power supply is turned off 4Turn off the power supply circuit breaker Note that when the extension piping is very long with large refrigerant amoun...

Page 14: ... when the trouble occurred matters related to wiring and etc 2 Reset error code logs and restart the unit after finishing service 3 There is no abnormality in electrical component controller board and etc Not logged 1 Re check the abnormal symptom 2 Conduct troubleshooting and ascertain the cause of the trouble 3 Continue to operate unit for the time being if the cause is not ascertained 4 There i...

Page 15: ... following items a Connection of power supply terminal block TB1 b Connection of terminal on outdoor power circuit board 3 Check connection of the connector CNDC on the outdoor controller circuit board Check connection of the connector LD1 and LD2 on the outdoor power circuit board Refer to 10 9 4 Check connection of reactor ACL Check connection of LO and NO on the outdoor noise filter circuit boa...

Page 16: ... and etc after power is turned on for 4 minutes 2 Abnormal if outdoor controller circuit board recognizes excessive number of indoor units 1 Check disconnection or looseness or polarity of indoor outdoor unit connecting wire of indoor and outdoor units 2 Check diameter and length of indoor outdoor unit connecting wire Total wiring length 80 m including wiring connecting each indoor unit and betwee...

Page 17: ...r 30 seconds after 90 seconds have passed since the defrosting operation started 2 Abnormal if discharge superheat Cooling TH4 T63HS Heating TH4 T63HS exceeds 70 continuously for 10 minutes High comp surface temperature Abnormal if comp surface temperature TH34 exceeds 125 In the case of high comp surface temperature error compressor does not restart unless the thermistor TH34 becomes less than 95...

Page 18: ...ing power module in case overcurrent is detected UF or UP error condition 1 Outdoor stop valve is closed 2 Decrease of power supply voltage 3 Looseness disconnection or converse of compressor wiring connection 4 Defective compressor 5 Defective outdoor power circuit board 1 Open stop valve 2 Check facility of power supply 3 Correct the wiring U V W phase to compressor Refer to 10 9 Outdoor power c...

Page 19: ...oard 3 Replace outdoor power circuit board 4 Replace outdoor controller circuit board 08 Abnormal power synchronous signal No input of power synchronous signal to power circuit board Power synchronous signal of 44 Hz or less or 65 Hz or more is detected on power circuit board 1 Distortion of power source voltage Noise superimposition 2 Disconnection or loose connection of earth wiring 3 Disconnect...

Page 20: ...1 Open stop valve 2 Check facility of power supply 3 Correct the wiring U V W phase to compressor Refer to 10 9 Outdoor power circuit board 4 Check compressor Refer to 10 6 5 Replace outdoor power circuit board 6 Check the dip switch setting of outdoor controller circuit board Refer to Model Select in 1 Function of switches in 10 10 Ud Over heat protection Abnormal if liquid thermistor TH3 detects...

Page 21: ...ctive transmitting receiving circuit of remote controller 5 Defective transmitting receiving circuit of indoor controller board of refrigerant address 0 6 Noise has entered into the transmission wire of remote controller E3 or E5 Remote controller transmission error E3 signal receiving error E5 1 Abnormal if remote controller could not find blank of transmission path for 6 seconds and could not tr...

Page 22: ...door unit or outdoor unit Check all the units in case of twin triple quadruple indoor unit system 2 4 Turn the power off and on again to check If abnormality generates again replace indoor controller board or outdoor controller circuit board w Other indoor controller board may have defect in case of twin triple quadruple indoor unit system 5 Turn the power off and detach fan motor from connector C...

Page 23: ... 20 6 3k 30 4 3k 40 3 0k If you put force on draw or bend the lead wire with measuring resistance value of thermis tor breaking of wire or contact failure can be detected 2 Check contact failure of TB61 No 5 6 on PCB of Interface unit Flow temp controller Refer to 7 WIRING DIAGRAM Turn the power on again and check restart after inserting connector again 4 Check actual tank temperature display on r...

Page 24: ...imer settings invalid If the timer can be set WEEKLY SIMPLE or AUTO OFF appears in the remote controller display PLEASE WAIT appears in the remote controller display The initial settings are being performed Wait approximately 3 minutes If the remote controller is not only for FTC change it An error code appears in the remote controller display The protection devices have operated to protect the FT...

Page 25: ...or miswiring Converse wiring of S1 and S2 or break of S3 wiring 2 When LED3 is blinking Indoor outdoor connecting wire is normal 4Check LED display on outdoor controller circuit board Refer to 10 9 Check protection device connector 63H for contact failure Refer to 10 9 4 Even controlling by the wireless remote controller no beep is heard and the unit does not start operat ing Operation display is ...

Page 26: ...ct leakage by checking the tem perature and opening Check pipe connections for gas leakage 3Check the insulation 4Open intake grille and check the filter Clean the filter by removing dirt or dust on it 5 If the filter is clogged indoor pipe tem perature rises and discharging pressure increases Check if heat exchanger is clogged by inspecting discharging pres sure Clean the heat exchanger 6Remove t...

Page 27: ... after turning on the main power Normal The start up diagnosis will be over in around 2 minutes Miswiring of indoor outdoor connecting wire Breaking of indoor outdoor connecting wire S3 Defective indoor controller board Defective outdoor controller circuit board Refer to Self diagnosis action table in order to solve the trouble In case of communication errors the display of remote controller may n...

Page 28: ... board are blown Check the wiring of the outdoor unit Check if the wiring is bad Check if the fuses are blown The fuses on the outdoor controller circuit board will be blown when the indoor outdoor connecting wire short circuits Bad wiring of the outdoor controller board The fuses on the outdoor controller circuit board are blown Check if miswiring breaking or poor contact is causing this problem ...

Page 29: ...tdoor controller circuit board Replace the outdoor controller circuit board Normal Only the unit which has the refrigerant address 0 supplies power to the remote controller Set the refrigerant address to 0 In case of the multiple grouping system recheck the refrigerant address again Defective indoor power board Replace the indoor power board Defective outdoor power circuit board Replace the outdoo...

Page 30: ...tact of the remote controller wire Check the voltage of the terminal block TB5 connecting the remote controller wire If it is not between DC 10V and DC16V the indoor controller board must be defective The remote controller wire short circuits Check if the remote controller wire is short circuited Defective indoor controller board Replace the indoor controller board Diagnosis flow Cause Inspection ...

Page 31: ...ear FILTER from the display See the operation manual that came with the product for how to clean the filters STANDBY is displayed on the screen This is displayed when the unit starts HEAT operation when the thermostat puts the compressor in operation mode or when the outdoor unit ends DEFROST operation and returns to HEAT operation The display will automatically disappear around 10 minutes later W...

Page 32: ...or unit is controlling the airflow amount in order to keep the optimum operating condition A sound similar to water flowing is heard from the unit This is not a malfunction This is the sound which is heard when the refrigerant is flowing inside the indoor unit The fan speed does not match the setting of the remote controller in HEAT operation The up down vane will be automatically set to horizonta...

Page 33: ... airflow direction does not change Up down vane left right louver 1 Check if the vane is set to a fixed position Check if the vane motor connector is removed 2 Check if the air conditioner has a function for switching the air direction 3 If the air conditioner doesn t have that function NOT AVAILABLE will be displayed on the remote controller when AIR DIRECTION or LOUVER button is pressed Somethin...

Page 34: ...nnector then measure the resistance with a tester At the ambient temperature 10 30 Disconnect the connector then measure the resistance with a tester Winding temperature 20 Thermistor TH3 Liquid Thermistor TH4 Discharge Thermistor TH6 2 phase pipe Thermistor TH7 Ambient Thermistor TH8 Heatsink Thermistor TH34 Comp Surface Normal 160k 410k 4 3k 9 6k 39k 105k TH4 TH34 TH3 TH6 TH7 TH8 Abnormal Open o...

Page 35: ...ctor CNF1 2 Measure the voltage in the outdoor controller circuit board TEST POINT VDC between 1 and 4 of the fan connector VDC DC250 330V TEST POINT VCC between 5 and 4 of the fan connector VCC DC15V Recover wiring Replace outdoor controller board Replace the fan motor Replace outdoor controller board C B and fan motor MF1 2 Replace outdoor controller board Replace the fan motor Is the voltage no...

Page 36: ...B constant 4150 3 Rt 17exp 4150 273 t 323 1 1 Thermistor R120 7 465k 2 B constant 4057 2 Rt 7 465exp 4057 273 t 393 1 1 Medium temperature thermistor Thermistor Heatsink TH8 20 250k 30 160k 40 104k 50 70k 60 48k 70 34k 80 24k 90 17 5k 100 13 0k 110 9 8k High temperature thermistor Thermistor Discharge TH4 Thermistor Comp surface TH34 0 10 20 30 40 50 20 10 0 10 20 30 40 50 Temperature Resistance k...

Page 37: ...ocked more sound can be heard No sound is heard when the pulse number moves from B to A in case coil is burnt out or motor is locked by open phase Sound can be detected by placing the ear against the screw driv er handle while putting the screw driver to the linear expansion valve LEV M 1 6 4 4 3 2 1 2 1 Red Blue Orange Yellow White 3 4 5 Connector LEV A LEV B DC12V Outdoor controller board Drive ...

Page 38: ...sure to attach the stopper to pipe B B A How to attach the coil Hold the lower part of the main body shown as A firmly so that the main body does not move and attach the coil by inserting it downward into the main body Then securely attach the coil stop per to pipe B At this time be careful that stress is not added to lead wire and main body is not wound by lead wire If the stop per is not firmly ...

Page 39: ...cross signal 0 5V DC 3 4 Not used 6 5 16V DC 7 5 16V DC CNF1 Connect to the fan motor 1 4 250 330V DC 5 4 15V DC 6 4 0 6 5V DC 7 4 15V DC When stopped 7 5V DC When operated 0V 15V pulse 63H High pressure switch SW4 Test operation SW6 Model select SW5 Function switch Model select SW1 Forced defrost detect history record reset refrigerant address TH4 Thermistor Discharge TH3 Thermistor Liquid pipe T...

Page 40: ...52C relay signal Connect to the outdoor controller circuit board CN52C CN5 Primary current Connect to the outdoor power circuit board CN5 CNAC1 CNAC2 230V AC Connect to the outdoor control ler circuit board CNAC EI Connect to the earth LI NI Voltage of 230V AC is input Connect to the terminal block TB1 E3 Connect to the earth E2 Connect to the earth OCH525 ...

Page 41: ...gram are not actually printed on the board P1 N L N1 N1 N2 W V U P2 CN2 Connect to the outdoor controller circuit board CN2 1 5 Outdoor power circuit board Transmitting signal to the outdoor controller circuit board 0 5V DC 2 5 Zero cross signal 0 5V DC 3 4 Not used 6 5 16V DC 7 5 16V DC 1 2 6 7 5 LD1 LD2 280 380V DC Connect to the outdoor controller circuit board CNDC R S Connect to the ACL 230V ...

Page 42: ...is switch setting the capacity decreases up to 30 under peak load condition Thus this setting is recommended only for Air to water purposes The black square indicates a switch position Type of Switch Swich No Function Action by the switch operation Effective timing ON OFF Dip switch SW1 1 Forced defrost 1 Start Normal When compressor is working in heating operation 1 2 Abnormal history clear Clear...

Page 43: ...t PAC SC36NA E 2 Turn SW1 to on for Low level sound priority mode Turn SW1 to off to release Low level sound priority mode and normal operation b On demand control Local wiring Demand control is available by external input In this mode power consumption is decreased within the range of usual 0 100 How to wire Basically the wiring is the same as a Connect an SW 1 which is procured at field to the b...

Page 44: ...r unit I F or FTC or outdoor unit communication error transmitting error is detected by outdoor unit Remote controller signal receiving error is detected by remote controller Remote controller transmitting error is detected by remote controller Remote controller signal receiving error is detected by I F or FTC unit Remote controller transmitting error is detected by I F or FTC unit 1 Error code di...

Page 45: ...ector CN3 on outdoor power board are not disconnected Measure resistance value of outdoor thermistors Abnormality of heatsink temperature Check if indoor outdoor units have a short cycle on their air ducts Measure resistance value of outdoor thermistor TH8 Check the outdoor fan motor Check if connector TH3 on outdoor controller board is disconnected Abnormality of voltage Check looseness disconnec...

Page 46: ...isplay blinks Inspection code is displayed when compressor stops due to the work of protection devices Display Contents to be inspected When power is turned on F3 F5 F9 E8 E9 EA Eb EC E0 E7 63L connector red is open 63H connector yellow is open 2 connectors 63H are open Indoor outdoor communication error Signal receiving error Outdoor unit Indoor outdoor communication error Transmitting error Outd...

Page 47: ...ds digit tens digit and ones digit are displayed by turns Example When 2450 hours 245 10 hours 0 5 secs 0 5secs 2 secs 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 Compressor operating current 0 50 LEV A opening pulse 0 480 0 50 wOmit the figures after the decimal fractions 0 480 When it is 100 pulse or more hundreds digit tens digit and ones digit are displayed by turns Example When 150 pulse 0 5...

Page 48: ...er and code 3 217 When the temperature is 100 C or more the hundreds digit tens digit and ones digit are displayed by turns Example When 130 C 0 5 secs 0 5secs 2 secs A Code display Code display 0 50 When no error history 0 and are displayed by turns When no error history 0 and are displayed by turns 1 ON 2 3 4 5 6 Thermostat ON time 0 999 Test run elapsed time 0 120 0 999 When it is 100 minutes o...

Page 49: ...Cooling only 0 Single phase 2 3 phase Setting details Defrosting switch Display details 0 Normal 1 For high humidity Example When heat pump 3 phase and defrosting normal are set up 20 is displayed 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 Indoor pipe temperature Cond Eva TH5 1 Indoor 1 39 88 39 88 When the temperature is 0 C or less and temperature are displayed by turns 39 88 When the temperature is 0 or les...

Page 50: ...tage error Undervoltage error Input current sensor error Abnormal power synchronous signal PFC error Overvoltage Undervoltage Overcurrent PFC IGBT error Undervoltage Display examples for multiple errors Overvoltage 01 Undervoltage 02 03 Undervoltage 02 Power sync signal error 08 0A Input current sensor error 04 PFC error 10 14 Description Display 00 01 02 04 08 10 20 U9 error detail history latest...

Page 51: ...d code When no error history 0 and are displayed by turns 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 Error thermistor display When there is no error thermistor is displayed Code display Operation frequency on error occurring 0 255 0 255 When it is 100Hz or more hundreds digit tens digit and ones digit are displayed by turns Example When 125Hz 0 5 secs 0 5secs 2 secs 1 ON 2 3 4 5 6...

Page 52: ...he temperature is 0 C or less and temperature are displayed by turns Example When 15 C 0 5 secs 0 5secs 2 secs Outdoor pipe temperature 2 phase TH6 on error occurring 39 88 39 88 When the temperature is 0 C or less and temperature are displayed by turns Example When 15 C 0 5 secs 0 5secs 2 secs Outdoor ambient temperature TH7 on error occurring 39 88 39 88 When the temperature is 0 C or less and t...

Page 53: ... unit 00 is displayed 50 1 1 ON 2 3 4 5 6 Discharge superheat on error occurring SHd 0 255 Cooling TH4 T63HS Heating TH4 T63HS 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 Minute 15 1 15 4 The black square indicates a switch position Controlling status of compressor operat ing frequency 1 ON 2 3 4 5 6 Code display The following code will be a help to know the operating status of uni...

Page 54: ...are indicates a switch position 1 ON 2 3 4 5 6 No error Overvoltage error Undervoltage error Input current sensor error Abnormal power synchronous signal PFC error Overvoltage Undervoltage Overcurrent PFC IGBT error Undervoltage Display examples for multiple errors Overvoltage 01 Undervoltage 02 03 Undervoltage 02 Power sync signal error 08 0A Input current sensor error 04 PFC error 10 14 Descript...

Page 55: ...rews 4 10 4 from the right and 3 from the rear side and detach the back panel 2 Removing the fan motor 1 Remove the top panel See Photo 1 2 Remove the front panel See Photo 1 3 Remove 1 nut M6 left screw and detach the propeller 4 Disconnect the connector CNF1 on the controller circuit board in the electrical parts box 5 Loosen the clamp for the lead wire in the motor support 6 Remove 4 fan motor ...

Page 56: ...l parts box 1 Remove the service panel See Photo 2 2 Remove the top panel See Photo 1 3 Remove the front panel See Photo 1 4 Disconnect the indoor outdoor connecting wire from terminal block 5 Disconnect the connector CNF1 LEV A and LEV B on the controller circuit board Symbols on the board CNF1 Fan motor LEV A LEV B LEV 6 Disconnect the pipe side connections of the following parts Thermistor Liqu...

Page 57: ...e front panel See Photo 1 4 Remove the back panel See Photo 1 5 Remove the electrical parts box See Photo 5 Thermistor Discharge TH4 6 Pull out the thermistor Discharge TH4 from the sensor holder Thermistor Comp surface TH34 6 Pull out the thermistor Comp surface TH34 from the sensor holder 7 Removing the 4 way valve 21S4 and LEV coil LEV A LEV B 1 Remove the service panel See Photo 2 2 Remove the...

Page 58: ...s are not oxidized 10 Removing the high pressure switch 63H and high pres sure sensor 63HS 1 Remove the service panel See Photo 2 2 Remove the top panel See Photo 1 3 Remove the front panel See Photo 1 4 Remove the back panel See Photo 1 5 Remove the electrical parts box See Photo 5 Removing the high pressure switch 63H 6 Pull out the lead wire of high pressure switch 7 Recover refrigerant 8 Remov...

Page 59: ... 9 Remove 3 compressor fixing nuts by using a spanner or an adjustable wrench 10 Remove the welded pipe of motor for compressor inlet and outlet Note Recover refrigerant without spreading it in the air Receiver leg fixing screw Receiver leg 13 Removing the power receiver 1 Remove the service panel See Photo 2 2 Remove the top panel See Photo 1 3 Remove the front panel See Photo 1 4 Remove the back...

Page 60: ... 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN cCopyright 2012 MITSUBISHI ELECTRIC CORPORATION Distributed in Oct 2012 No OCH525 Made in Japan New publication effective Oct 2012 Specifications are subject to change without notice ...

Reviews: