FEATURES
CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT
Max. 10m (PUHZ-SW40/SW50)
The refrigerant circuit with LEV (Linear Expansion Valve) and power receiver always control the optimal refrigerant level
regardless of the length (10 m max. and 5 m min.) of piping. The additional refrigerant charging work during installation
often causes problems. It is completely eliminated by chargeless system. This unique system improves the quality and reli-
ability of the work done. It also helps to speed up the installation time.
PUHZ-SW40VHA PUHZ-SW50VHA
<Reference data> Plate heat exchanger (ACH50-50 plates) *2pcs [connected in parallel]
Note: "COP" and "Power input" in the above table are values that does
NOT
contains the "pump input (based on EN 14511)".
4
SPECIFICATIONS
PUHZ-SW40VHA
PUHZ-SW40VHA-BS
PUHZ-SW50VHA
PUHZ-SW50VHA-BS
Nominal water fl ow
L/min
11.80
Heating
(A7/W35)
Capacity
kW
4.10
COP
4.80
Power input
kW
0.85
Heating
(A7/W45)
Capacity
kW
4.10
COP
3.63
Power input
kW
1.13
Heating
(A2/W35)
Capacity
kW
4.00
COP
3.24
Power input
kW
1.24
Heating
(A2/W45)
Capacity
kW
4.00
COP
2.68
Power input
kW
1.49
Nominal water fl ow
L/min
10.30
Cooling
(A35/W7)
Capacity
kW
3.60
EER
2.71
Power input
kW
1.33
Cooling
(A35/W18)
Capacity
kW
3.60
EER
4.65
Power input
kW
0.77
(SW40)
Nominal water fl ow
L/min
17.2
Heating
(A7/W35)
Capacity
kW
6.00
COP
4.42
Power input
kW
1.36
Heating
(A7/W45)
Capacity
kW
6.00
COP
3.32
Power input
kW
1.81
Heating
(A2/W35)
Capacity
kW
5.00
COP
2.97
Power input
kW
1.68
Heating
(A2/W45)
Capacity
kW
5.00
COP
2.47
Power input
kW
2.03
Nominal water fl ow
L/min
12.9
Cooling
(A35/W7)
Capacity
kW
4.50
EER
2.38
Power input
kW
1.90
Cooling
(A35/W18)
Capacity
kW
5.00
EER
3.96
Power input
kW
1.26
(SW50)
OCH525