70
(2) Spacing
• PFAV-P300,600VM-E-F
(Unit mm)
Wood base
100 or more
Through hole for
the remote controller
wiring to outdoor unit
Power cable hole
(380V or more)
Wire hole for the
device power
supply
Drain pipe
Refrigerant pipes
50 or more
90 or more
Duct space (if a
duct is connected)
300
P300: 500 or more
P600: 100 or more
(Front space)
• PFAV-P250,500VM-E
(Unit mm)
Optional plenum chamber
(Front space)
Power cable hole
(380V or more)
Wire hole for the
device power supply
Through hole for
the remote controller
wiring to outdoor unit
Wood base
Refrigerant pipes
Drain pipe
30
0
85 or more
P250: 800 or more
P500: 1000 or more
50 or more
100 or more
P250: 500 or more
P500: 100 or more
Duct space (if a
duct is connected)