Outdoor-side heat exchanger
Electric expansion valve
Capillary tube
Indoor-side
heat exchanger
Strainer
Strainer
Accumulator
High pressure switch
(Protection)
Low pressure
switch
(Protection)
Service port
Muffler
Compressor
Solenoid valve
Strainer
Service port
High pressure
switch (Control)
Strainer
[2] Refrigerant Circuit
Cooling
✻
There are 2 circuits
for PRH-P16 and 20MYA.
operation
Heating operation
<
<
[3] Refrigerant Charge
[4] Operation Range
-5
43
Outdoor air temperature (
°
CDB)
24
15
Indoor air temper
ature
(
°
CWB)
–12
18
Outdoor air temperature (
°
CWB)
27
15
Indoor air temper
ature
(
°
CDB)
Amount of infusion of coolant at ex-factory
R407C 7.7 kg
R407C 8.2 kg x 2
Model
PRH-P8MYA
PRH-P20MYA
R407C 8.2 kg
PRH-P10MYA
R407C 7.7 kg x 2
PRH-P16MYA
Cooling
Heating
- 38 -