[3] Self-diagnosis
Use the remote controller to look up the unit error history.
1. Change to self-diagnosis mode
Press the CHECK button twice within three seconds to show
the following
2. Select the refrigerant address number to be self-
diagnosed
Press the
buttons to scroll through the
refrigerant address numbers (00 to 15)and select the
refrigerant address number to be self-diagnosed.
After three seconds from making the change,the lit refrigerant
address to be self-diagnosed will start to flash,and self-
diagnosis will commence.
1.
2.
Item
Operation mode/relay output
Outdoor-side control condition
Indoor-side control
condition
Error code history 1
Error code history 2
Display contents
tens place
O: stop
C: cooling
H: heating
d: defrosting
units place
1: SV1
Relay output = SV1 + 21S4 + 52C
2: 21S4
4: 52C
Ex. During cooling mode, when 52C and
SV1 are ON: C5
When an error occurs, the error
code and error signal (*1) are
displayed in alternation.
Control mode display system
The error code (ex. U8, UA) and error indicator (*1) are displayed in alter-
nation.
• Depending on the position of the SW2 switch on the outdoor-side controller board, the segments light up to indicate
the running condition of the unit and the particulars of the check code.
SW2 setting
123456
000000
011110
010110
011100
111100
*1 Display system for error indicator
The indicator corresponds to the following numbers
0 .......... Outdoor-side
1 .......... Indoor-side
Indoor-side
Outdoor-side
Nothing
(IC1)
Control mode
Indoor-side
Ordinary
Hot adjustment
Defrosting
—
Heater ON
Freeze prevention
Surge prevention
Compressor OFF
Display
0
1
2
3
4
5
6
7
Outdoor-side
←
←
←
←
←
←
←
←