PQRY-P-T(S)LMU, Y(S)LMU (April 2017 Ver2)
WR2-119
© 2017 Mitsubishi Electric US, Inc.
10. ELECTRICAL WORK
10-4. Power Supply Examples
The local standards and/or regulations is applicable at a higher priority.
10-4-1. PQRY-P72, 96, 120, 144, 168, 192, 216, 240TLMU/YLMU
Note4
Note3
To *1 or *2
*1
*2
Note8
Connector
CN41 CN40
Power supply
3-phase 3-wire
208-230V 60Hz(TLMU)
460V 60Hz(YLMU)
Note11,13
Power supply
1-phase
208-230V 60Hz
Note11
Power supply
1-phase
208-230V 60Hz
Central control
transmission cable
>=1.25mm
2
Shield cable
(CVVS, CPEVS
MVVS)
Indoor-heat source
transmission cable
>=1.25mm
2
Shield cable
Indoor-heat source
transmission cable
>=1.25mm
2
Shield cable
(Using MA remote controller)
Connecting TB5 terminal.
BC controller
(Using ME remote controller)
Connecting TB5 terminal.
<In the case a system controller is connected.>
G
G
TB7
(S)
TB1
(L1,L2,L3)
TB3
(M1,M2)
TB5
(M1,M2)
TB2
(L,N)
S
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
S
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
S
S
S
E
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
TB1
(R,S)
TB2 TB3
S
TB15
(1,2)
TB7
(M1,M2)
Power supply
1-phase
208-230V 60Hz
SC
Transmission
booster
Note9
Note10
MA R/C
MA R/C
MA R/C
ME R/C
ME R/C
ME R/C
MA R/C cable
0.3-1.25mm
2
<=200m
Note5
ME R/C cable
0.3~1.25mm
2
<=10m
Note5
HU
IU
(Shield)
TB02
(M1,M2)
TB01
S L,N
(Shield)
BC controller
TB02
(M1,M2)
S
(Shield)
(Shield)
(Shield)
(Shield)
(Shield)
(Shield)
Note4
To other HU
Note7
Note8
Note7
Note8
* Power supply
specifications vary with the
model of connected indoor
units or BC controller
Note8
Power supply
1-phase
208-230V 60Hz
Note11
G
TB5
(M1,M2)
TB2
(L,N)
S
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
S
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
S
S
S
E
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
TB1
(R,S)
TB2 TB3
S
TB15
(1,2)
Transmission
booster
Note9
Note10
IU
(Shield)
(Shield)
(Shield)
(Shield)
(Shield)
(Shield)
* Power supply
specifications vary with the
model of connected indoor
units or BC controller
Note12
Pull box
Pull box
TB01
L,N
Note:
1 The transmission cable is not-polarity double-wire.
2 Symbol means a screw terminal for wiring.
3 The shield wire of transmission cable should be connected to the grounding terminal at
Heat source unit. All shield wire of M-Net transmission cable among Indoor units should be
connected to the S terminal at Indoor unit or all shield wire should be connected
together.
The broken line at the scheme means shield wire.
4 When the Heat source unit connected with system controller, power-supply to TB7 of the
heat source unit(s) is needed. The connector change from CN41 to CN40 at one of the
heat source units will enable the heat source unit to supply power to TB7, or an extra power
supply unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm
2
,
shielded, CVVS/CPEVS/MVVS) among Heat source units and system controllers is called
central control transmission cable. The shield wire of the central control transmission
cable must be grounded at the Heat source unit whose CN41 is changed to CN40.
When
the power supply unit PAC-SC51KUA is used, connect the shielded cable to the ground
terminal on the PAC-SC51KUA.
5 MA R/C transmission cable (0.3-1.25mm
2
) must be less than 200m in length, while ME
R/C transmission cable (0.3-1.25mm
2
) must be less than 10m in length. But transmission
cable to the ME R/C can be extend using a M-NET cable (>=1.25mm
2
) when the length
is counted in the M-Net length.
7 MA remote controller and ME remote controller should not be grouped together.
6 To wire PAC-YT53CRAU, use a wire with a diameter of 0.3mm
2
[AWG 22].
8 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
transmission cable to connect all the TB15 terminals of the Indoor units. It is called
"Grouping".
If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address
setting".
9 Indoor board consumes power from TB3. The power balance should be considered
according to System Design 2-3 "System configuration restrictions".
10 If Transmission booster is needed, be sure to connect the shield wires to the both sides
to the booster.
11 The critical current for choosing power source equipment is approximate
1.4 times of total rated current of the Heat source unit(s) or Indoor unit(s).
12 When System controller (SC) is connected to the system, turn the SW2-1 on.
13 The phases of electricity power must be confirmed to be right used. Phase-reverse, or
phase-missing could break the controllers.
G
G
Breakers for
current leakage
Switch
Breakers for
current leakage
Switch
Breakers for
current leakage
Switch
Breakers for
current leakage
Switch
Breakers for
current leakage
Switch
BKC
OCP
NFB
HU
IU
SC
MA R/C
ME R/C
Breaker capacity
Over-current protector
Non-fuse breaker
Heat source unit
Indoor unit
System controller
MA remote controller
ME remote controller
Minimum Wire thickness
G wire
<mm
2
/AWG>
Power wire
<mm
2
/AWG>
Model
Symbol
PQRY-P72TLMU-A
3.3/12
3.3/12
PQRY-P96TLMU-A
5.3/10
5.3/10
PQRY-P120TLMU-A
8.4/8
8.4/8
PQRY-P144TLMU-A
13.3/6
13.3/6
PQRY-P168TLMU-A
13.3/6
13.3/6
PQRY-P192TLMU-A
21.2/4
21.2/4
PQRY-P216TLMU-A
33.6/2
33.6/2
PQRY-P240TLMU-A
33.6/2
33.6/2
PQRY-P72YLMU-A
2.1/14
2.1/14
PQRY-P96YLMU-A
2.1/14
2.1/14
PQRY-P120YLMU-A
3.3/12
3.3/12
PQRY-P144YLMU-A
3.3/12
3.3/12
PQRY-P168YLMU-A
5.3/10
5.3/10
PQRY-P192YLMU-A
5.3/10
5.3/10
PQRY-P216YLMU-A
8.4/8
8.4/8
PQRY-P240YLMU-A
13.3/6
13.3/6