11. M-NET CONTROL
11-4-2. Rule of setting address
Unit
Indoor unit
ME, LOSSNAY
Remote controller
(Main)
ME, LOSSNAY
Remote controller
(Sub)
Address setting
01 ~ 50
52 ~ 99, 100
101 ~ 150
151 ~ 199, 200
Note
Example
The address of heat source unit + 1
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
The smallest address of indoor unit in the group + 100
The place of "100" is fixed to "1"
ON/OFF remote
controller
000, 201 ~ 250
Local remote controller
System controller
The address of main remote cont 50
The address automatically becomes "200" if it is set
as "00"
10
1
10
1
0 1 2
3
4 5
6
7
8
9
0 1 2
3
4 5
6
7
8
9
10
1
10
1
0 1 2
3
4 5
6
7
8
9
0 1 2
3
4 5
6
7
8
9
0 1 2
3
4 5
6
7
8
9
0 1 2
3
4 5
6
7
8
9
10
1
0 1 2
3
4 5
6
7
8
9
0 1 2
3
4 5
6
7
8
9
0 1 2
3
4 5
6
7
8
9
10
1
100
LMAP04U-E
201 ~ 250
1
1
Fixed
Fixed
2
Fixed
Heat source unit
BC controller
(Main)
52 ~ 99, 100
Lowest address within the indoor units connected to
the BC controller (Sub) plus 50.
10
1
BC controller
(Sub)
51 ~ 99, 100
The smallest address of indoor unit in same refrigerant
50
Assign sequential address numbers to the heat source
units in one refrigerant circuit system. OC and OS are
automatically detected. (Note 2)
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
Use the most recent address within the same group of
indoor units. Make the indoor units address connected
to the BC controller (Sub) larger than the indoor units
address connected to the BC controller (Main).
If applicable, set the sub BC controllers in an PQRY
system in the following order:
(1) Indoor unit to be connected to the BC controller (Main)
(2) Indoor unit to be connected to the BC controller (No.1 Sub)
(3) Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)
0 1 2
3
4 5
6
7
8
9
0 1 2
3
4 5
6
7
8
9
0 1 2
3
4 5
6
7
8
9
0 1 2
3
4 5
6
7
8
9
0 1 2
3
4 5
6
7
8
9
0 1 2
3
4 5
6
7
8
9
0 1 2
3
4 5
6
7
8
9
0 1 2
3
4 5
6
7
8
9
10
1
(Note1)
Note1: To set the address to "100", set it to "50"
Note2: Heat source units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending
order of their address.
000, 201 ~ 250
10
1
100
0
0
0
PAC-YG50ECA
000, 201 ~ 250
10
1
100
BAC-HD150
000, 201 ~ 250
10
1
100
Settings are made on the initial screen of AG-150A-A.
Settings are made with setting tool of BM ADAPTER.
0
0
0
0
0
0
The smallest group No. to be managed is changeable.
The smallest group No. to be m 200
AE-200A/AE-50A
AG-150A-A
EB-50GU-A
EW-50A