WR2-6
PQRY-P-T(S)LMU, Y(S)LMU (April 2017 Ver2)
© 2017 Mitsubishi Electric US, Inc.
1. SPECIFICATIONS
Note:
*1 Nominal cooling conditions (subject to JIS B8615-1)
*2 Nominal heating conditions (subject to JIS B8615-1) Unit converter
Indoor:
81degF D.B./ 66degF W.B. (27degC D.B./ 19degC W.B.) 68degF D.B. (20degC D.B.)
BTU/h =kW x 3,412
Water Temp.:
86degF (30degC)
68degF (20degC)
cfm =m
3
/min x 35.31
lb =kg / 0.4536
Pipe length:
24-9/16ft.(7.5m)
25ft.(7.6m)
* Above specification data is subject to rounding
variation.
Level difference: 0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.
Model
PQRY-P216TLMU-A
PQRY-P240TLMU-A
Power source
3-phase 3-wire 208 / 230 ±10% 60Hz
3-phase 3-wire 208 / 230 ±10% 60Hz
Cooling capacity (Nominal) *1 (208/230V)
Btu/h
216,000
240,000
kW
63.3
70.3
Power input
kW
19.23
21.14
Current input
A
59.3 / 53.6
65.1 / 58.9
Temp. range of
cooling
Indoor
W.B.
59~75° F (15~24° C)
59~75° F (15~24° C)
Circulating water *3
50~113° F (10~45° C)
50~113° F (10~45° C)
Heating capacity (Nominal) *2
(208/230V)
Btu/h
243,000
270,000
kW
71.2
79.1
Power input
kW
13.04
15.12
Current input
A
40.2 / 36.3
46.6 / 42.1
Temp. range of
heating
Indoor
D.B.
59~81° F (15~27° C)
59~81° F (15~27° C)
Circulating water *3
50~113° F (10~45° C)
50~113° F (10~45° C)
Indoor unit connectable
Total capacity
50~150% of heat source unit capacity
50~150% of heat source unit capacity
Model / Quantity
P06~P96/2~50
(Connectable branch pipe number is max. 48.)
P06~P96/2~50
(Connectable branch pipe number is max. 48.)
Sound pressure level (measured in anechoic room)
dB <A>
58
58
Refrigerant piping
diameter
High pressure
in.(mm)
7/8 (22.2) Brazed (1-1/8 (28.58)
Brazed for the part that exceeds 65 m)
7/8 (22.2) Brazed (1-1/8 (28.58)
Brazed for the part that exceeds 65 m)
Low pressure
in.(mm)
1-1/8 (28.58) Brazed
1-3/8 (34.93) Brazed
External finish
Galvanized steel sheets
Galvanized steel sheets
External dimension HxWxD
in.
57-1/8 x 34-11/16 x 21-11/16
57-1/8 x 34-11/16 x 21-11/16
mm
1,450 x 880 x 550
1,450 x 880 x 550
Net weight
lbs(kg)
556 (252)
556 (252)
Heat exchanger
Type
Plate
Plate
Water volume in plate
G
2.64
2.64
I
10
10
Water pressure Max.
psi
290
290
MPa
2
2
Compressor
Type
Inverter scroll hermetic compressor
Inverter scroll hermetic compressor
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Motor output
kW
14.5
16.1
Case heater
kW
0.045 (240 V)
0.045 (240 V)
Lubricant
MEL32
MEL32
Circulating water *3
Water flow rate
G/h
3,044
3,044
G/min(gpm)
50.7
50.7
m
3
/ h
11.52
11.52
L/min
192
192
cfm
6.8
6.8
Pressure drop
psi
6.53
6.53
kPa
45
45
Operating volume range
range
G/h
1,585 ~ 3,804
1,585 ~ 3,804
G/min(gpm)
26.4 ~ 63.4
26.4 ~ 63.4
m
3
/ h
6.0 ~ 14.4
6.0 ~ 14.4
Protection devices
High pressure protection
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit(comp)
Over-heat protection, Over-current protection
Compressor
Over-heat protection
Minimum Circuit Ampacity(MCA)
A
69 / 63
79 / 71
Maximum Overcurrent Protection(MOP)
A
110 / 110
125 / 125
Refrigerant
Type x original charge
R410A x 25 lbs + 13 oz (11.7 kg)
R410A x 25 lbs + 13 oz (11.7 kg)
Control
Indoor LEV and BC controller
Indoor LEV and BC controller
Drawing
External
KJ94T172
KJ94T172
Wiring
KE94G037
KE94G037
Standard attachment
Document
Installation Manual
Installation Manual
Accessory
Details refer to External Drw
Details refer to External Drw
Optional parts
Joint: CMY-Y102SS-G2, CMY-Y102LS-G2, CMY-Y202S-G2, CMY-Y302S-G2, CMY-R160-J1
Main BC controller: CMB-P108, 1010, 1013, 1016NU-GA1, 108, 1010, 1016NU-HA1
Sub BC controller: CMB-P104, 108NU-GB1, CMB-P1016NU-HB1
Remarks
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
The ambient temperature of the Heat Source Unit needs to be kept below 104°F DB(40° C DB).
The ambient relative humidity of the Heat Source Unit needs to be kept below 80%.
The Heat Source Unit should not be installed at outdoor.
Mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
A field provided flow switch is required for minimum flow protection on each module, field installed and
wired to TB8 (terminal 3-4).
*3 If using Circulating water temperatures that are between 23 and 50° F, Dip switch 3-9 must be
turned on and glycol must be used in the water loop to prevent freezing down to 5° F.