- 41 -
(6) Pump interlock circuit
Operating the heat source unit without circulation water inside the water piping can cause a trouble.
Be sure to provide interlocking for the unit operation and water circuit.
Since the terminal block is being provided inside the unit, use it as required.
TM1
TM2
1
TB8
2
3
4
1
TB8
2
3
4
MP
~ / N 240/230/220V
52P
MCB
L
N
52P
TM1
TM2
Heat source equipment
Operation
ON signal
Pump interlock
Operation
ON signal
Pump interlock
Heat source equipment
To next equipment
Site control panel
X :
Relay
Rated voltage : L - N
: 220 ~ 240V
Rated load : 1A
TM1, 2 : Timer relay
(closes after elapsing
the set time when it is
powered, while opens
promptly when it is not
powered)
52P : Magnetic contactor
for heat source
water pump
MP :
Heat
source
water pump
MCB : Circuit breaker
*Remove the short circuit
wire between 3 and 4
when wiring to TB8.
This circuit uses the “Terminal block for pump interlock (TB8)” inside the electrical parts box of the heat source equipment.
This circuit is for interlocking of the heat source equipment operation and the heat source water pump.
Wiring diagram
Operation ON signal
Pump Interlock
Terminal No.
Output
Operation
TB8-1, 2
Relay contacts output
Rated voltage : L - N : 220 ~ 240V
Rated load : 1A
• When Dip switch 2-7 is OFF
The relay closes during compressor operation.
• When DIP switch 2-7 is ON.
The relay closes during reception of cooling or the heating operation signal from the controller.
(Note : It is output even if the thermostat is OFF (when the compressor is stopped).)
Terminal No.
Input
Operation
TB8-3, 4
Level signal
If the circuit between TB8-3 and TB8-4 is open, compressor operation is prohibited.