- 28 -
(2) PFD-P500VM-E (two refrigerant circuit system)
Table: I V - 1 - ( 2 ) - 2 . Bent equivalent length "M"
M (m/bent)
Outdoor Model
PQHY-P250
0.42
Table: I V- 1 - ( 2 ) - 1 . Piping length
(m)
Max. length
Piping in the figure
Item
Max. equivalent length
A
Height between OU/HU and IU (OU/HU above IU)
Height between OU/HU and IU (OU/HU under IU)
OU: Outdoor Unit, IU: Indoor Unit, HU: Heat source Unit
190
165
Farthest IU from OU/HU (L)
H
H'
50
40
-
-
(mm)
Outdoor
Pipe(Gas)
Pipe(Liquid)
PQHY-P250
ø22.20
ø9.52
*1
*1. A>=90m, ø12.70mm
Table: I V- 1 - ( 2 ) - 3 . Piping "A" size selection rule
(mm)
Indoor Unit size
Pipe(Gas)
Pipe(Liquid)
P500
ø22.20
ø9.52
Table: IV-1-(2)-4. Indoor unit piping size selection rule
PUHY-P250
ø22.20
ø9.52 *1
PUHY-P250
0.42
IU: Indoor unit, OU: Outdoor unit, HU: Heat source unit
Note1. If the PUHY system is designed to use cooling mode under outdoor temperature 10°C, H’<=15m.
Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m)=Actual piping "M" x Quantity of bent.
L
L
A
OU
OU
L
L
A
Fig.IV-1-(2)A: PUHY Piping Design
H (OU abo
v
e
IU)
H' (OU under IU)
Fig.IV-1-(2)B: PQHY Piping Design
H (HU ab
o
v
e IU)
H' (HU under IU)
HU
HU
IU
IU