- 65 -
(3) Details of Maintenance/Inspection
Parts
Fan motor
Bearing
Fan belt
Air filter
Linear
expansion valve
Display lamp
(LED)
Compressor
Fan motor
Linear
expansion valve
6
months
6
months
Check points
Inspection
Cycle
Unit
What to do
Assessment
Drain pan
Drain hose
Float switch
Heat exchanger
Accumulator
4-way valve
Indoor
Outdoor/Heat source unit
1
year
1
year
1
year
Heat exchanger
. Check for unusual noise
. Measure the insulation
resistance
. Check for excessive slack
. Check for wear and tear
. Check for unusual noise
. Check for unusual noise
. Free of unusual noise
. Insulation resistance over 1M
. Resistance (30~40N/belt)
. Adequate amount of slack=5mm
. Belt length=no longer than
102% of the original length
. Free of wear and tear
. Free of unusual noise
. Free of unusual noise
Replace when insulation
resistance is under 1M
. Check for clogging of the
drainage system
. Check for loosened bolts
. Check for corrosion
. Check for clogging of the
drainage system
. Check for corrosion
. Check the drainage of the drain
trap
. Clean, free of clogging
. Free of loose screws
. No major disintegration
Clean if dirty or clogged
Tighten bolts
Replace if extremely worn
. Perform an operation check
using the operation data
. Adequately controls the air
temperature
Replace if malfunctioning
. Check the outer appearance
. Clean, free of ruse
Repair with paint
Replace if extremely worn
. Perform an operation check
using the operation data
. Adequately controls the air
temperature
Replace if malfunctioning
. Check for clogging, dirt, and
damage
. Clean, free of clogging or
damage
Clean
. Check for unusual noise
. Measure insulation resistance
. Free of unusual sound
. Insulation resistance over 1M
Replace if insulation resistance
goes below 1M
. Make sure the lamp comes on
. Comes on when the output is on
. Rapid drop in brightness
Replace if the light does not
come on when the power is on
. Perform an operation check
using the operation data
. Adequately controls the refrigerant
temperature when the valve is switched
(Check temperature change when
cooling/heating is switched.)
Replace if malfunctioning
. Check for clogging and tear
. Clean the filter
. Clean, free of damage
Clean the filter
Replace if extremely dirty or
damaged
. Check the outer appearance
. Make sure its free of foreign
objects
. Free of frayed or cut wires
. Free of foreign objects
Replace if damaged or
extremely worn
Remove foreign objects
. Clean, free of clogging
. Free of wear and tear
Clean if dirty or clogged
Replace if extremely worn
Pour water into the drain trap
. Check for unusual noise
. Check insulation resistance
. Check for loosened terminals
. Free of unusual sound
. Insulation resistance over 1M
. Free of loosened terminals
Replace if insulation resistance
goes below 1M (under the
condition that the refrigerant
is not liquefied)
Tighten loosened bolts
Adjust the belt
Replace if the belt length
exceeds 2% of the original
length, worn, or used over 8000
hours
If the noise does not stop after
lubrication, change the oil.
Add lubricant once a year.
. Check for clogging, dirt, and
damage
. Clean, free of clogging or
damage
Clean
6
months
6
months
3
months
. Check for torn wire, fraying,
and unplugged connectors
. Check insulation resistance
. No frayed or cut wires or
unplugged connectors
. Insulation resistance over 1M
Pressure switch
Replace when cut or shorted,
when the insulation resistance
goes below 1M , or if there is a
history of abnormal operation