- 51 -
7. External input/output specifications
(1) Input/output specifications
Input
*1 Use minute-current contact (DC12V 1mA)
Output
* 20HP only
Function
Usage
Signals
Start/stop
Turning
ON/OFF
the indoor
unit
· Pulse [Factory setting: Dip SW1-9 ON]
(a-contact with voltage/without voltage) *1
<With voltage>
Power Source: DC12~24V
Electrical Current:
Approximately 10mA (DC12V)
<Standard Pulse>
· Level [Dip SW1-9 OFF]
(Short: operate Open: stop
Dehumidification
signal
Sending a
command
to perform
dehumidification
with priority
Level
Refer to the wiring diagram
<Dehumidification command> shown
on the page 53.
Function
Usage
Signals
No.1
Operation Status
Obtaining signals indicating operation
status of indoor units in each refrigerant
circuit.
Relay a-contact
output
DC 30V or
AC 220~240V
Standard Current :
1A
Minimum Current :
1mA
No. 1
Error Status
Obtaining signals indicating error status of
indoor units in each refrigerant circuit.
No. 2
Operation Status*
Obtaining signals indicating operation
status of indoor units in each refrigerant
circuit.
No. 2
Error Status*
Obtaining signals indicating error status of
indoor units in each refrigerant circuit.
over 200ms
(Pulse powering time)
over 200ms
(Pulse interval)