13

8. Electrical work

• Perform wiring as shown in the diagram to the lower left. (Procure the cable

locally.)
Make sure to use cables of the correct polarity only.

[Fig. 8-2-5] (P.6)

• Connect the terminal blocks as shown in the diagram below.

Caution:

• Use care not to make mis-wiring.
• Firmly tighten the terminal screws to prevent them from loosening.
• After tightening, pull the wires lightly to confirm that they do not move.

8.3. Remote controller

8.3.1. For wired remote controller

1) Two wired remote controllers setting

If two wired remote controllers are connected, set one to “Main” and the other to
“Sub”. For setting procedures, refer to “Function selection of remote controller” in the
operation manual for the indoor unit.

8.3.2. For IR wireless remote controller

1) Installation area

• Area in which the IR wireless remote controller is not exposed to direct

sunshine.

• Area in which there is no near by heating source.
• Area in which the IR wireless remote controller is not exposed to cold (or hot)

winds.

• Area in which the IR wireless remote controller can be operated easily.
• Area in which the IR wireless remote controller is beyond the reach of children.

* The signal can travel up to approximately 7 meters [23 ft] (in a streight line) within

45 degrees to both right and left of the center line of the receiver.

2) Setting the Model No.

[Fig. 8-3-1] (P.6)

8.4. Function settings

8.4.1. Function setting on the unit (Selecting the unit functions)

1) For wired remote controller [Fig. 8-4-1] (P.7)
1. Changing the external static pressure setting.

• Be sure to change the external static pressure setting depending on the duct and

the grill used.

1

Go to the function setting mode.

2

Use the

C

button to set the refrigerant address (

III

) to 00.

3

Press

D

 and [--] will start to flash in the unit number (

IV

) display.

4

Use the

C

 button to set the unit number (

IV

) to 01-04 or AL.

5

Press the

E

MODE button to designate the refrigerant address/unit number.

[--] will flash in the mode number (

I

) display momentarily.

6

Press the

F

buttons to set the mode number (

I

) to 08.

7

Press the

G

 button and the current set setting number (

II

) will flash.

Use the

F

button to switch the setting number in response to the external static

pressure to be used.

8

Press the MODE button

E

and mode and the setting number (

I

) and (

II

) will

change to being on constantly and the contents of the setting can be confirmed.

9

Press the FILTER

A

and TEST RUN

B

 buttons simultaneously for at least two

seconds. The function selection screen will disappear momentarily and the air
conditioner OFF display will appear.

0

To set the static pressure at 70,100,150Pa [0.28, 0.40, 0.60 in. WG], repeat steps

3

 to

9

. (Set the mode number to 10 for step

6

.)

2. Other functions

1

Select unit number 00 for the settings. (Settings for all indoor units)
Refer to Function table 1.

2

Select unit number 01 to 04 or AL for the settings. (Settings for each indoor unit)
To set the indoor unit in the individual system, select unit number 01.
To set each indoor unit of two, three or four indoor units, which are connected
when these units are simultaneously in operation, select unit number 01 to 04.
To set all indoor units of two, three or four indoor units which are connected when
these units are simultaneously in operation, select AL.
Refer to Function table 2.

2) For IR wireless remote controller [Fig. 8-4-2] (P.7)
1. Changing the external static pressure setting.

• Be sure to change the external static pressure setting depending on the duct and

the grill used.

1

Go to the function select mode
Press the CHECK button

F

twice continuously.

(Start this operation from the status of remote controller display turned off.)

is lighted and “00” blinks.

Press the TEMP button

C

once to set “50”. Direct the wireless remote controller

toward the receiver of the indoor unit and press the Hour button

A

.

2

Setting the unit number
Press the TEMP button

C

and

D

 to set the unit number to 01-04 or AL. Direct the

wireless remote controller toward the receiver of the indoor unit and press the
Minute button

B

.

3

Selecting a mode
Enter 08 to change the external static pressure setting using the

C

and

D

buttons.
Direct the wireless remote controller toward the receiver of the indoor unit and
press the Hour button

A

.

Current setting number:

1 = 1 beep (one second)
2 = 2 beeps (one second each)
3 = 3 beeps (one second each)

4

Selecting the setting number
Use the

C

and

D

buttons to change the external static pressure setting to be

used.
Direct  the  wireless remote  controller toward  the sensor of  the  indoor  unit  and
press the Hour button

A

.

5

To set the external static pressure
Repeat steps

3

 and

4

to set the mode number to 10.

6

Complete function selection
Direct  the  wireless remote  controller toward  the sensor of the  indoor  unit  and
press the ON/OFF button

E

.

Note:
• Whenever changes are made to the function settings after installation or

main-tenance, be sure to record the changes with a mark in the “Setting”
column of the Function table.

3) Changing the power voltage setting (Function table 1)

• Be sure to change the power voltage setting depending on the voltage used.

A

Indoor terminal block

B

Earth wire (green/yellow)

C

Indoor/outdoor unit connecting wire 3-core 1.5 mm

2

[AWG 16] or more

D

Outdoor terminal block

1

Connecting cable
Cable 3-core 1.5 mm

2

[AWG 16], in conformity with Design 245 IEC 57.

2

Indoor terminal block

3

Outdoor terminal block

4

Always install an earth wire (1-core 1.5 mm

2

[AWG 16]) longer than other cables

5

Wired remote controller cable
Wire No

size (mm

2

) : Cable 2C

0.3

This wire accessory of remote controller
(wire length : 10 m [32 ft], non-polar. Max. 500 m [1640 ft])

6

Wired remote controller

1

Insert batteries.

2

Press the SET button with something sharp at the end.
Start this operation from the status of IR wireless remote controller display
turned off.

blinks and Model No. is lighted.

3

Press the temp

button to set the Model No.

4

Press the SET button with something sharp at the end.

and Model No. are lighted for three seconds, then turned off.

Indoor Unit Model

A

Model No.

PEAD

026

Switch OFF the remote controller.
Press the

A

 and

B

buttons simultaneously and hold them for at least 2

seconds. FUNCTION will start to flash.

MODEL SELECT

MODEL SELECT

External static pressure

Setting no. of mode

no. 08

Setting no. of mode

no. 10

35 Pa [0.14 in. WG]

2

1

50 Pa [0.20 in. WG] (before shipment)

3

1

70 Pa [0.28 in. WG]

1

2

100 Pa [0.40 in. WG]

2

2

150 Pa [0.60 in. WG]

3

2

CHECK

KD79P399H01.book  Page 13  Tuesday, July 1, 2014  4:51 PM

Summary of Contents for PEAD-42AA5

Page 1: ...read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER Français MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte POUR L INSTALLATEUR ...

Page 2: ...200 3 15 16 7 7 8 Fig 3 2 4 Viewed from the direction of the arrow B 777 30 5 8 S 50 2 50 2 P 700 27 9 16 Min 300 11 13 16 G H K F A I Fig 3 2 5 Unit mm in A Electric box B Ceiling C Ceiling beam D Access door 2 450 mm x 450 mm 17 3 4 in x 17 3 4 in E Access door 1 450 mm x 450 mm 17 3 4 in x 17 3 4 in F Maintenance access space G Supply air H Intake air I Bottom of indoor unit J Access door 3 K A...

Page 3: ... b c d c A c b a d e f g h i Fig 6 2 1 Fig 6 2 2 Fig 6 2 3 Fig 6 2 4 Fig 6 2 5 a d c b e f 90 a Copper tubes d Tilted b Good e Uneven c No good f Burred a Smooth all around d Too much g Cracked b Inside is shining without any scratches e Tilted h Uneven c Even length all around f Scratch on flared plane i Bad examples a Flaring tool d Flare nut b Die e Yoke c Copper tube a Flare nut b Copper tube ...

Page 4: ...D D E K M B H I Max 20m 65ft 1 5 2m 5 7ft G F F F B J O N F Max 300mm 11 13 16in I B C D D G F E H A 32 1 1 4 35 1 7 16 25 1 Fig 6 5 2 Fig 6 5 1 A Indoor unit B Tie band accessory C Visible part D Insertion margin E Drain hose accessory F Drain pipe O D ø32 mm 1 1 4 in PVC TUBE field supply G Insulating material field supply H Tie band accessory I To be gap free The joint section of the insulation...

Page 5: ...utlet G Leave distance enough to prevent short cycle A In case of rear inlet B In case of bottom inlet A Filter B Bottom plate C Nail for the bottom inlet D Nail for the rear inlet S1 S2 L1 L2 G 1 2 S1 S2 S3 CN105 RED S3 A B C D E F H J G Fig 8 1 1 A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit outdoor unit connecting c...

Page 6: ...controller P Indoor controller board Q Radio frequency interface is installed on Indoor controller board R CN105 RED 5P S Wiring for radio frequency interface A Indoor terminal block B Earth wire green yellow C Indoor outdoor unit connecting wire 3 core 1 5 mm2 AWG 16 or more D Outdoor terminal block 1 Connecting cable Cable 3 core 1 5 mm2 AWG 16 in conformity with Design 245 IEC 57 2 Indoor termi...

Page 7: ...nter button B TEST button C Set Time button D Timer On Off button Set Day button E Mode selection button F Set temperature button G Timer Menu button Monitor Set button A Hour button B Minute button C TEMP button D TEMP button E ON OFF button F CHECK button B A G H K L M I J C D E F Fig 11 1 1 A Indoor unit B Union C Liquid pipe D Gas pipe E Stop valve F Outdoor unit G Refrigerant gas cylinder ope...

Page 8: ... an injury or leakage of water due to a fire an electric shock the unit falling etc Ventilate the room if refrigerant leaks during operation If the refrigerant comes in contact with a flame poisonous gases will be released Caution Perform grounding Do not connect the ground wire to a gas pipe water pipe arrester or telephone ground wire Defective grounding could cause an electric shock Do not inst...

Page 9: ...ate access door 4 below the electric box and the unit as shown in Fig 3 2 5 Fig 3 2 1 P 2 Fig 3 2 2 Viewed from the direction of the arrow A P 2 Fig 3 2 3 P 2 Fig 3 2 4 Viewed from the direction of the arrow B P 2 Fig 3 2 5 Viewed from the direction of the arrow B P 2 3 3 Indoor unit accessories The unit is provided with the following accessories 4 Fixing hanging bolts 4 1 Fixing hanging bolts Fig...

Page 10: ... Internally pressurized Remove the flare nut as follows 1 Loosen the nut until you hear a hissing noise 2 Do not remove the nut until the gas has been completely released i e hissing noise stops 3 Check that the gas has been completely released and then remove the nut Outdoor unit connection Connect pipes to stop valve pipe joint of the outdoor unit in the same manner applied for indoor unit For t...

Page 11: ...ontroller operation Make sure using a transparent hose that drain is discharged 4 After confirmation cancel the test run mode and turn off the main power If the connector is connected to the ON side of SWE disconnect it and connect it to the OFF side and attach the water supply port cover into its original position Tighten the screws of the water supply port cover to the torque of 2 0 0 2 N m Fig ...

Page 12: ...ectric wires securely to the CN105 RED of indoor controller board Connect the electric wires securely to the corresponding terminals 5 Secure the cables with clamps inside the electric component box 6 Attach the electric component cover as it was Tighten the screws of the terminal box cover to the torque of 2 0 0 2 N m Fix power supply cable and indoor outdoor cable to control box by using buffer ...

Page 13: ...mber 01 to 04 To set all indoor units of two three or four indoor units which are connected when these units are simultaneously in operation select AL Refer to Function table 2 2 For IR wireless remote controller Fig 8 4 2 P 7 1 Changing the external static pressure setting Be sure to change the external static pressure setting depending on the duct and the grill used 1Go to the function select mo...

Page 14: ...least 12 hours before starting operation Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the power switch turned on during the operational season 9 2 Test run Refer to the installation manual that comes with each remote controller for details Mode Settings Mode no Setting no Initial setting Check Power failure automatic recov...

Page 15: ...iving error 10 11 12 Fb Indoor unit control system error memory error etc No sound No corresponding IR wireless remote controller Wired remote controller RF thermostat Symptom Remark Beeper sounds OPERATION INDICATOR lamp flashes Number of times Check code 1 E9 Indoor outdoor unit communication error Transmitting error Outdoor unit For details check the LED display of the outdoor controller board ...

Page 16: ...INDOOR UNIT INLET TEMP INDOOR UNIT H EXC TEMP INDOOR UNIT FILTER USE H Indoor room temperature Heat exchanger temperature Filter operation time Display Indoor unit information The filter operation time displayed is the number of hours the filter has been used since the filter reset was performed 4 Press the FILTER button 5 The data is displayed in Airflow temperature display example Blinking Waiti...

Page 17: ... the gas cylinder If the refrigerant is charged from the gas phase composition change may occur in the refrigerant inside the cylinder and the outdoor unit In this case ability of the refrigerating cycle decreases or normal operation can be impossible However charging the liquid refrigerant all at once may cause the compressor to be locked Thus charge the refrigerant slowly To maintain the high pr...

Page 18: ...osition etc ce qui résulterait en une blessure ou une fuite d eau Aérez le local en cas de fuite de liquide frigorigène en cours de fonctionne ment Tout contact du liquide frigorigène avec une flamme libère des gaz toxiques Attention Mettre l appareil à la terre Ne pas relier le câble de terre au tuyau de gaz d eau un parafoudre ou un câble de terre téléphonique Toute mise à la terre défectueuse p...

Page 19: ...ement d installation pour l appareil intérieur sans poutres ou autres objets pouvant obstruer son espace d accès pour l entretien 1 Lorsqu un espace de 300 mm 11 13 16 in ou plus est disponible sous l appareil entre l appareil et le plafond Fig 3 2 1 Créez les portes d accès 1 et 2 450 450 mm 17 3 4 17 3 4 in chacune comme indiqué sur la Fig 3 2 2 La porte d accès 2 n est pas nécessaire si l espac...

Page 20: ...êchera le stockage derrière l appareil intérieur et un isolant trop mince ne pourra éviter le suintage de condensation 6 2 Evasement La cause principale de fuite de gaz est un évasement défectueux Veuillez effectuer l évasement selon la méthode suivante 6 2 1 Couper le tuyau Fig 6 2 1 P 3 Utiliser un coupe tuyaux pour couper le tube en cuivre correctement 6 2 2 Enlever les bavures Fig 6 2 2 P 3 En...

Page 21: ... Fig 6 5 1 P 4 Tuyaux groupés Diam ext Tuyau en cuivre mm in Diam ext raccord conique mm in Couple de serrage N m ø6 35 1 4 17 11 16 14 18 ø9 52 3 8 22 7 8 34 42 ø12 7 1 2 26 1 1 32 49 61 ø15 88 5 8 29 1 5 32 68 82 A Couvre tube petit accessoire B Précaution Sur place retirer l isolation thermique des tuyaux de réfrigérant insérer l écrou évasé pour évaser l extrémité et remettre l isolation therm...

Page 22: ... filtre à air Retirer d abord la vis de blocage du filtre 2 Retirer la plaque inférieure 3 Attacher la plaque de fond à l arrière de l appareil Fig 7 0 3 P 5 La position des trous de fixation sur la plaque diffère de ceux de l orifice d entrée arrière Serrer les vis de la plaque de fond au couple de serrage de 1 4 0 2 N m 4 Fixer le filtre sous le corps Vérifier le côté du filtre à ajuster Fig 7 0...

Page 23: ...ons dans le mode d emploi de l appareil inté rieur 8 3 2 Pour télécommande sans fil infrarouge 1 Lieu d installation A l abri des rayons directs du soleil A l ecart de toute source de chaleur A l abri des courants d air froids ou chauds Lieu ou la telecommande sans fil infrarouge peut etre facilement utilisee Hors de la portee des enfants Le signal peut parcourir environ 7 mètres 23 ft ligne droit...

Page 24: ...l vers le récepteur de l unité intérieure et appuyer sur la touche Minute B 3Sélection d un mode Entrer 08 pour modifier le réglage de la pression statique externe à l aide des touches C et D Dirigez la télécommande sans fil vers le récepteur de l appareil intérieur et appuyez sur le bouton des heures A Numéro de réglage actuel 1 1 bip une seconde 2 2 bips une seconde chacun 3 3 bips une seconde c...

Page 25: ...sistance de l isolation chute en raison de l accumulation de réfrigérant dans le compresseur La résistance dépassera 1 MΩ après que le compresseur a chauffé pendant deux ou trois heures Le temps mis par le compresseur pour chauffer varie selon les conditions atmosphériques et l accumulation de réfrigérant Pour faire fonctionner le compresseur dans lequel s est accumulé du réfrigé rant il est néces...

Page 26: ...onction de redémarrage automatique remet l appareil en service au moment où la tension secteur est rétablie après une coupure de courant Régler la FONCTION DE REMISE EN MARCHE AUTOMATIQUE avec la télécom mande Mode No 01 Symptôme Cause Télécommande sans fil LED 1 2 CCI de l appareil extérieur VEUILLEZ ATTENDRE Pendant les 2 minutes environ qui suivent la mise sous tension Après l éclairage de la L...

Page 27: ...écharge du comp Température ambiante extérieur Affichage Informations sur l appareil intérieur Température ambiante intérieur Affichage Température de l échangeur thermique Durée de fonctionnement du filtre La durée de fonctionnement du filtre affichée correspond au nombre d heures d utilisation du filtre depuis sa réinitialisation 4 Appuyer sur la touche FILTER 5 Les données s affichent en Exempl...

Page 28: ... for use in the residential commercial and light industrial environment Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: