background image

12

7. Duct work

• Connect canvas duct between unit and duct.

[Fig. 7-0-1] (P.5)

• Use incombustible material for duct parts.
• Provide full insulation to inlet duct flange and outlet duct to prevent condensation.
• Be sure to change the position of air filter to a position where it can be serviced.

• Procedure for changing the rear inlet to the bottom inlet.

[Fig. 7-0-2] (P.5)

1. Remove air filter. (First remove filter lock screw.)
2. Remove the bottom plate.
3. Fit the bottom plate to the rear of the body.

[Fig. 7-0-3] (P.5)

(Position of lug-holes on the plate are different from those for rear inlet.)
(Tighten the screws of the bottom plate to the torque of 1.4 ±0.2 N·m.)

4. Fit filter to the underside of the body.

(Be careful of which side of the filter to fit.)

[Fig. 7-0-4] (P.5)

Caution:

• Inlet duct of 850 mm [33-1/2 in] or more should be construted.

To  connect  the  air  conditioner main body  and  the  duct for  potential
equalization.

• To reduce the risk of injury from metal sheet edges, wear protective gloves.
• To  connect the  air conditioner main body  and the  duct  for  potential

equalization.

• The noise from the intake will increase dramatically if intake is fitted directly

beneath the main body. Intake should therefore be installed as far away from
the main body as possible.
Particular care is required when using it with bottom inlet specifications.

• Install sufficient thermal insulation to prevent condensation forming on

outlet duct flanges and outlet ducts.

• Keep the distance between the inlet grille and the fan over 850 mm [33-1/2 in].

If it is less than 850 mm [33-1/2 in], install a safety guard not to touch the fan.

• To avoid electrical noise interference, do not run transmission lines at the

bottom of the unit.

8. Electrical work

8.1. Power supply

8.1.1. Indoor unit power supplied from outdoor unit

The following connection patterns are available.
The outdoor unit power supply patterns vary on models.

1:1 System

[Fig. 8-1-1] (P.5)

* Affix a label A that is included with the manuals near each wiring diagram for the

indoor and outdoor units.

Field electrical wiring

*1. The 10 m [32 ft] wire is attached in the wired remote controller accessory. Max. 500 m [1640 ft]
*2. The figures are NOT always against the ground.

S3 terminal has 24 V DC against S2 terminal. However between S3 and S1, these terminals
are not electrically insulataed by the transformer or other device.

Caution:

Do not use anything other than the correct capacity breaker and fuse. Using
fuse, wire or copper wire with too large capacity may cause a risk of
malfunction or fire.

8.2. Indoor wire connection

Work procedure
1. Remove 2 screws to detach the electric component cover.
2. Route each cable through the wiring intake into the electric component box.

(Procure power cable and in-out connecting cable locally and use wired remote
control cable supplied with the unit.)

3. Securely connect the power cable and the in-out connecting cable and the wired

remote control cable to the terminal blocks.

4. For radio frequency interface

Connect the electric wires securely to the CN105 (RED) of indoor controller board.
Connect the electric wires securely to the corresponding terminals.

5. Secure the cables with clamps inside the electric component box.
6. Attach the electric component cover as it was.

(Tighten the screws of the terminal box cover to the torque of 2.0 ±0.2 N·m.)

• Fix power supply cable and indoor/outdoor cable to control box by using buffer

bushing for tensile force. (PG connection or the like.)

Warning:

• Attach the electrical part cover securely. If it is attached incorrectly, it could

result in a fire, electric shock due to dust, water, etc.

• Use the specified indoor/outdoor unit connecting wire to connect the indoor

and outdoor units and fix the wire to the terminal block securely so that no
stress is applied to the connecting section of the terminal block. Incomplete
connection or fixing of the wire could result in a fire.

[Fig. 8-2-1] (P.6)

[Fig. 8-2-2] (P.6)

[Fig. 8-2-3] (P.6)

[Fig. 8-2-4] (P.6)

<A> In case of rear inlet
<B> In case of bottom inlet

A

Duct

B

Air inlet

C

Access door

D

Canvas duct

E

Ceiling surface

F

Air outlet

G

Leave distance enough to prevent short cycle

A

Filter

B

Bottom plate

When the plate is attached on
the rear side, it exceeds the
height of the rear body panel.

Replicate the plate along the slit

when there is not enough room

above for the entire unit.

Screw holes are hidden under

the insulation. Screw through

the insulation to screw the plate

down.

C

Nail for the bottom inlet

D

Nail for the rear inlet

A

Outdoor unit power supply

B

Earth leakage breaker

C

Wiring circuit breaker or isolating switch

D

Outdoor unit

E

Indoor unit/outdoor unit connecting cords

F

Wired remote controller

G

Indoor unit

H

Indoor controller board

J

Radio frequency interface for RF thermostat

Indoor unit model

PEAD

Wir

in

g

W

ire

N

o.

×

siz

e

(m

m

2

) Indoor unit power supply (Heater)

–

Indoor unit power supply (Heater) earth

–

Indoor unit-Outdoor unit

3 × 1.5 (polar)

Indoor unit-Outdoor unit earth

1 × Min. 1.5

Wired remote controller-Indoor unit

*1 2 × 0.3 (Non-polar)

Ci

rc

uit

ra

tin

g

Indoor unit (Heater) L-N

*2

–

Indoor unit-Outdoor unit S1-S2

*2

230 V AC

Indoor unit-Outdoor unit S2-S3

*2

24 V DC

Wired remote controller-Indoor unit

*2

14 V DC

Notes: 1. Wiring size must comply with the applicable local and national

code.

2. Power supply cords and indoor unit/outdoor unit connecting cords

shall not be lighter than polychloroprene sheathed flexible cord.
(Design 245 IEC57)

3. Install an earth longer than other cables.
4. Perform wiring in compliance with the safety regulations detailed in

UL1995.

A

Screw holding cover (1pc)

B

Cover

C

Terminal box

D

Knockout hole

E

Remove

F

Use PG bushing to keep the weight of the cable and external force from being applied to the
power supply terminal connector. Use a cable tie to secure the cable.

G

Power source wiring

H

Use ordinary bushing

I

Transmission wiring

J

Conduit

K

Side frame

L

Knockout hole (for power source wiring)

M

Washer (accessory)

N

Terminal block for power source and indoor transmission

O

Terminal block for wired remote controller

P

Indoor controller board

Q

Radio frequency interface is installed on Indoor controller board

R

CN105 (RED/5P)

S

Wiring for radio frequency interface

KD79P399H01.book  Page 12  Tuesday, July 1, 2014  4:51 PM

Summary of Contents for PEAD-42AA5

Page 1: ...read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER Français MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte POUR L INSTALLATEUR ...

Page 2: ...200 3 15 16 7 7 8 Fig 3 2 4 Viewed from the direction of the arrow B 777 30 5 8 S 50 2 50 2 P 700 27 9 16 Min 300 11 13 16 G H K F A I Fig 3 2 5 Unit mm in A Electric box B Ceiling C Ceiling beam D Access door 2 450 mm x 450 mm 17 3 4 in x 17 3 4 in E Access door 1 450 mm x 450 mm 17 3 4 in x 17 3 4 in F Maintenance access space G Supply air H Intake air I Bottom of indoor unit J Access door 3 K A...

Page 3: ... b c d c A c b a d e f g h i Fig 6 2 1 Fig 6 2 2 Fig 6 2 3 Fig 6 2 4 Fig 6 2 5 a d c b e f 90 a Copper tubes d Tilted b Good e Uneven c No good f Burred a Smooth all around d Too much g Cracked b Inside is shining without any scratches e Tilted h Uneven c Even length all around f Scratch on flared plane i Bad examples a Flaring tool d Flare nut b Die e Yoke c Copper tube a Flare nut b Copper tube ...

Page 4: ...D D E K M B H I Max 20m 65ft 1 5 2m 5 7ft G F F F B J O N F Max 300mm 11 13 16in I B C D D G F E H A 32 1 1 4 35 1 7 16 25 1 Fig 6 5 2 Fig 6 5 1 A Indoor unit B Tie band accessory C Visible part D Insertion margin E Drain hose accessory F Drain pipe O D ø32 mm 1 1 4 in PVC TUBE field supply G Insulating material field supply H Tie band accessory I To be gap free The joint section of the insulation...

Page 5: ...utlet G Leave distance enough to prevent short cycle A In case of rear inlet B In case of bottom inlet A Filter B Bottom plate C Nail for the bottom inlet D Nail for the rear inlet S1 S2 L1 L2 G 1 2 S1 S2 S3 CN105 RED S3 A B C D E F H J G Fig 8 1 1 A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit outdoor unit connecting c...

Page 6: ...controller P Indoor controller board Q Radio frequency interface is installed on Indoor controller board R CN105 RED 5P S Wiring for radio frequency interface A Indoor terminal block B Earth wire green yellow C Indoor outdoor unit connecting wire 3 core 1 5 mm2 AWG 16 or more D Outdoor terminal block 1 Connecting cable Cable 3 core 1 5 mm2 AWG 16 in conformity with Design 245 IEC 57 2 Indoor termi...

Page 7: ...nter button B TEST button C Set Time button D Timer On Off button Set Day button E Mode selection button F Set temperature button G Timer Menu button Monitor Set button A Hour button B Minute button C TEMP button D TEMP button E ON OFF button F CHECK button B A G H K L M I J C D E F Fig 11 1 1 A Indoor unit B Union C Liquid pipe D Gas pipe E Stop valve F Outdoor unit G Refrigerant gas cylinder ope...

Page 8: ... an injury or leakage of water due to a fire an electric shock the unit falling etc Ventilate the room if refrigerant leaks during operation If the refrigerant comes in contact with a flame poisonous gases will be released Caution Perform grounding Do not connect the ground wire to a gas pipe water pipe arrester or telephone ground wire Defective grounding could cause an electric shock Do not inst...

Page 9: ...ate access door 4 below the electric box and the unit as shown in Fig 3 2 5 Fig 3 2 1 P 2 Fig 3 2 2 Viewed from the direction of the arrow A P 2 Fig 3 2 3 P 2 Fig 3 2 4 Viewed from the direction of the arrow B P 2 Fig 3 2 5 Viewed from the direction of the arrow B P 2 3 3 Indoor unit accessories The unit is provided with the following accessories 4 Fixing hanging bolts 4 1 Fixing hanging bolts Fig...

Page 10: ... Internally pressurized Remove the flare nut as follows 1 Loosen the nut until you hear a hissing noise 2 Do not remove the nut until the gas has been completely released i e hissing noise stops 3 Check that the gas has been completely released and then remove the nut Outdoor unit connection Connect pipes to stop valve pipe joint of the outdoor unit in the same manner applied for indoor unit For t...

Page 11: ...ontroller operation Make sure using a transparent hose that drain is discharged 4 After confirmation cancel the test run mode and turn off the main power If the connector is connected to the ON side of SWE disconnect it and connect it to the OFF side and attach the water supply port cover into its original position Tighten the screws of the water supply port cover to the torque of 2 0 0 2 N m Fig ...

Page 12: ...ectric wires securely to the CN105 RED of indoor controller board Connect the electric wires securely to the corresponding terminals 5 Secure the cables with clamps inside the electric component box 6 Attach the electric component cover as it was Tighten the screws of the terminal box cover to the torque of 2 0 0 2 N m Fix power supply cable and indoor outdoor cable to control box by using buffer ...

Page 13: ...mber 01 to 04 To set all indoor units of two three or four indoor units which are connected when these units are simultaneously in operation select AL Refer to Function table 2 2 For IR wireless remote controller Fig 8 4 2 P 7 1 Changing the external static pressure setting Be sure to change the external static pressure setting depending on the duct and the grill used 1Go to the function select mo...

Page 14: ...least 12 hours before starting operation Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the power switch turned on during the operational season 9 2 Test run Refer to the installation manual that comes with each remote controller for details Mode Settings Mode no Setting no Initial setting Check Power failure automatic recov...

Page 15: ...iving error 10 11 12 Fb Indoor unit control system error memory error etc No sound No corresponding IR wireless remote controller Wired remote controller RF thermostat Symptom Remark Beeper sounds OPERATION INDICATOR lamp flashes Number of times Check code 1 E9 Indoor outdoor unit communication error Transmitting error Outdoor unit For details check the LED display of the outdoor controller board ...

Page 16: ...INDOOR UNIT INLET TEMP INDOOR UNIT H EXC TEMP INDOOR UNIT FILTER USE H Indoor room temperature Heat exchanger temperature Filter operation time Display Indoor unit information The filter operation time displayed is the number of hours the filter has been used since the filter reset was performed 4 Press the FILTER button 5 The data is displayed in Airflow temperature display example Blinking Waiti...

Page 17: ... the gas cylinder If the refrigerant is charged from the gas phase composition change may occur in the refrigerant inside the cylinder and the outdoor unit In this case ability of the refrigerating cycle decreases or normal operation can be impossible However charging the liquid refrigerant all at once may cause the compressor to be locked Thus charge the refrigerant slowly To maintain the high pr...

Page 18: ...osition etc ce qui résulterait en une blessure ou une fuite d eau Aérez le local en cas de fuite de liquide frigorigène en cours de fonctionne ment Tout contact du liquide frigorigène avec une flamme libère des gaz toxiques Attention Mettre l appareil à la terre Ne pas relier le câble de terre au tuyau de gaz d eau un parafoudre ou un câble de terre téléphonique Toute mise à la terre défectueuse p...

Page 19: ...ement d installation pour l appareil intérieur sans poutres ou autres objets pouvant obstruer son espace d accès pour l entretien 1 Lorsqu un espace de 300 mm 11 13 16 in ou plus est disponible sous l appareil entre l appareil et le plafond Fig 3 2 1 Créez les portes d accès 1 et 2 450 450 mm 17 3 4 17 3 4 in chacune comme indiqué sur la Fig 3 2 2 La porte d accès 2 n est pas nécessaire si l espac...

Page 20: ...êchera le stockage derrière l appareil intérieur et un isolant trop mince ne pourra éviter le suintage de condensation 6 2 Evasement La cause principale de fuite de gaz est un évasement défectueux Veuillez effectuer l évasement selon la méthode suivante 6 2 1 Couper le tuyau Fig 6 2 1 P 3 Utiliser un coupe tuyaux pour couper le tube en cuivre correctement 6 2 2 Enlever les bavures Fig 6 2 2 P 3 En...

Page 21: ... Fig 6 5 1 P 4 Tuyaux groupés Diam ext Tuyau en cuivre mm in Diam ext raccord conique mm in Couple de serrage N m ø6 35 1 4 17 11 16 14 18 ø9 52 3 8 22 7 8 34 42 ø12 7 1 2 26 1 1 32 49 61 ø15 88 5 8 29 1 5 32 68 82 A Couvre tube petit accessoire B Précaution Sur place retirer l isolation thermique des tuyaux de réfrigérant insérer l écrou évasé pour évaser l extrémité et remettre l isolation therm...

Page 22: ... filtre à air Retirer d abord la vis de blocage du filtre 2 Retirer la plaque inférieure 3 Attacher la plaque de fond à l arrière de l appareil Fig 7 0 3 P 5 La position des trous de fixation sur la plaque diffère de ceux de l orifice d entrée arrière Serrer les vis de la plaque de fond au couple de serrage de 1 4 0 2 N m 4 Fixer le filtre sous le corps Vérifier le côté du filtre à ajuster Fig 7 0...

Page 23: ...ons dans le mode d emploi de l appareil inté rieur 8 3 2 Pour télécommande sans fil infrarouge 1 Lieu d installation A l abri des rayons directs du soleil A l ecart de toute source de chaleur A l abri des courants d air froids ou chauds Lieu ou la telecommande sans fil infrarouge peut etre facilement utilisee Hors de la portee des enfants Le signal peut parcourir environ 7 mètres 23 ft ligne droit...

Page 24: ...l vers le récepteur de l unité intérieure et appuyer sur la touche Minute B 3Sélection d un mode Entrer 08 pour modifier le réglage de la pression statique externe à l aide des touches C et D Dirigez la télécommande sans fil vers le récepteur de l appareil intérieur et appuyez sur le bouton des heures A Numéro de réglage actuel 1 1 bip une seconde 2 2 bips une seconde chacun 3 3 bips une seconde c...

Page 25: ...sistance de l isolation chute en raison de l accumulation de réfrigérant dans le compresseur La résistance dépassera 1 MΩ après que le compresseur a chauffé pendant deux ou trois heures Le temps mis par le compresseur pour chauffer varie selon les conditions atmosphériques et l accumulation de réfrigérant Pour faire fonctionner le compresseur dans lequel s est accumulé du réfrigé rant il est néces...

Page 26: ...onction de redémarrage automatique remet l appareil en service au moment où la tension secteur est rétablie après une coupure de courant Régler la FONCTION DE REMISE EN MARCHE AUTOMATIQUE avec la télécom mande Mode No 01 Symptôme Cause Télécommande sans fil LED 1 2 CCI de l appareil extérieur VEUILLEZ ATTENDRE Pendant les 2 minutes environ qui suivent la mise sous tension Après l éclairage de la L...

Page 27: ...écharge du comp Température ambiante extérieur Affichage Informations sur l appareil intérieur Température ambiante intérieur Affichage Température de l échangeur thermique Durée de fonctionnement du filtre La durée de fonctionnement du filtre affichée correspond au nombre d heures d utilisation du filtre depuis sa réinitialisation 4 Appuyer sur la touche FILTER 5 Les données s affichent en Exempl...

Page 28: ... for use in the residential commercial and light industrial environment Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: